3.4 Diagnosis and parametrizing
Valve terminal type CPV..-GE-ASI-4-... supports the evalu
ation of valve faults.
Any valve faults which occur will be registered as periph
eral faults of the slave on the AS-Interface master.
The following valve faults are monitored:
–
short circuit on the valve solenoid coil,
–
wire fracture on the vale solenoid coil,
–
valve does not switch (no movement of the plunger).
The diagnosis of the valve module can be deactivated via
the AS-Interface parameter port P3.
Parameter port P3
Description
P3 = 1
(diagnosis active,
factory setting)
Valve faults are registered as periph
eral faults and displayed via the fault
LED (see section 2).
P3 = 0
(diagnosis inactive)
Valve faults are not registered as pe
ripheral faults and are not displayed
via the fault LED.