7.3.1
CiA 402
Open-loop operation objects
Parameters
Index.Subindex
Name
Data type
Px.
Manufacturer-specific objects: saved basic unit for the object is effective.
270
0x219C.02
Reactive current setpoint value
FLOAT32
662
0x219C.03
Time current increase
FLOAT32
4001
0x219C.04
Activation of open-loop operation
BOOL
4004
0x219C.07
Active control structure
UINT32
4005
0x219C.08
Selection of mode of operation open-
loop/closed loop
UINT32
4006
0x219C.09
Selection of mode of operation
UINT32
4007
0x219C.0A
Active mode of operation
UINT32
4008
0x219C.0B
Velocity switching threshold
FLOAT32
4010
0x219C.0D
Current rise time
FLOAT32
4026
0x219C.15
Current reduction activation
BOOL
4027
0x219C.16
Current reduction delay time
FLOAT32
4028
0x219C.17
Current reduction scaling factor
FLOAT32
6694
0x219C.14
Factor current setpoint value
FLOAT32
Tab. 405 Objects
7.4
Field weakening
Function
Synchronous motors can only be operated at a specific rotational speed. If the induced motor voltage
reaches the level of the DC link voltage, the torque rapidly decreases.
The objective of field weakening is to reach higher rotational speeds. In field weakening the motor
negative field voltage is reduced by a negative reactive current. This enables the motor to be operated
above the nominal rotary speed. The negative reactive current must be limited for some motors.
Parameters and diagnostic messages
ID Px.
Parameters
Description
Specifies whether the field weakening is active or inactive.
Access
read/write
Update
effective immediately
102201
Activation of field
weakening
Unit
−
Technology functions
427
Festo — CMMT-ST-SW — 2019-02