background image

WARNING

Risk of injury from electric shock in the event of incomplete insulation at the
power connections [X6A], [X9A] and [X9B].
Before operating, plugging in or unplugging the operator unit CDSB or a con-
nector from a hot-plug-capable interface, the following points must be fulfilled:
• The conducting lines at the device are completely insulated.
• The protective earthing (PE) and the shield connection are correctly connected

to the device.

• The housing is free of damage.

WARNING

Risk of injury due to overheating and electric shock with faulty live components
Closing the branch-circuit protective device with faulty live components may
cause fire or electric shock.
• The opening of the branch-circuit protective device may be an indication that a

fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the controller should be exam-
ined and replaced if damaged. If burnout of the current element of an overload
relay occurs, the complete overload relay must be replaced.

Information for operation with safety functions

NOTICE

Check the safety functions to conclude the installation process and after every
modification to the installation.

During installation of safety-related inputs and outputs, also observe the fol-
lowing:

Comply with all specified requirements, e.g.:

Surrounding area (EMC)

Logic and load voltage supply

Mating plug

Connecting cables

Cross-wiring

Additional information 

è

 Manual Assembly, Installation.

The maximum permissible cable length between the safety relay unit and the
plug of the I/O interface is 3 m.

Comply with the requirements of EN 60204-1 for the installation. In the event of
a fault, the voltage must not exceed 60 V DC. The safety relay unit must switch
off its outputs in the event of a fault.

Install wiring between the safety relay unit and the I/O interface of the servo
drive in such a way as to eliminate the risk of a short circuit between the
conductors or to 24 V, as well as a cross circuit 

è

 EN 61800-5-2, Annex

D.3.1. Otherwise, the safety relay unit must feature detection of shorts across
contacts and, in the event of a fault, must switch off the control signals on 2
channels.

Use only suitable mating plugs and connecting cables 

è

 Manual Assembly,

Installation.

Prevent conductive contamination between neighbouring plug pins.

Make sure that no bridges or similar can be inserted parallel to the safety
wiring. For example, use the maximum wire cross section or appropriate plastic
wire end sleeves.

Use twin wire end sleeves for cross-wiring safety-related inputs and outputs.
A maximum of 10 devices may be cross-wired when cross-wiring inputs and
outputs 

è

 Manual Assembly, Installation.

The safety relay unit and its inputs and outputs must meet the necessary safety
classification of the safety function that is required for the specific case.

Connect each of the control inputs to the safety relay unit on 2 channels using
parallel wiring.

Only use permitted motor cables for the BR+/BR– connection.

If the diagnostic output of the safety sub-function concerned has to be evalu-
ated: connect diagnostic output directly to the safety relay unit. Evaluation
of the diagnostic output is either mandatory or optional depending on which
safety classification is desired.

If diagnostic outputs are cross-wired for a device compound: wire diagnostic
outputs as a ring. Run the two ends of the ring to the safety relay unit and
monitor for discrepancies.

7.2

Residual current protective device

WARNING

Risk of injury from electric shock.
This product can cause a DC current in the residual-current conductor in case of
error. In cases where a residual current device (RCD) or a residual current monitor
(RCM) is used to protect against direct or indirect contact, only the type B kind of
RCD or RCM is permitted on the power supply side of this product.

Information on the residual current protective device 

è

 Manual Assembly, Instal-

lation.
The touch current in the protective earthing conductor can exceed an alternating
current of 3.5 mA or a DC current of 10 mA. Always connect both protective
earthing connections to the mains-side PE connection, the PE pin of [X9A] and
PE earthing screw on the housing. The minimum cross section of the protective
earthing conductor must comply with the local safety regulations for protective
earthing conductors for equipment with high leakage current.

7.3

Mains fuse

The CMMT-AS does not have an integrated fuse at the mains input or in the DC
link circuit. An external fuse is required at the mains supply of the device. A device
group coupled in the DC link circuit must be protected by a common mains fuse.

Use only circuit breakers and fuses that have the relevant approval and meet
the specifications and protection requirements stated below.

Requirements for circuit breakers (automatic circuit breakers)
Type of protection

Circuit breaker

max. permissible rated cur-
rent

[A]

40
Restrictions concerning line protection 

è

 Tab. 14 Line

protection requirements

Short circuit current rating
SCCR of mains fuse

[kA]

min. 10

Approvals

IEC 60947-2

Rated voltage

[V AC]

min. 400

Overvoltage category

III

Pollution degree

2

Characteristic

C

Tab. 13: Requirements for circuit breakers and fuses
The circuit breaker is used for line protection. The rated current of the circuit
breaker must be less than or equal to the approved current rating of the selected
conductor cross section. The circuit breaker must also take into account the
overload case and must not trip (overload case: a 3-fold increase in the input
current for 2 s).

Line protection requirements
Description

Cable cross
section at
[X9A] in
[mm²]

Mains fuse [A]

1)

CMMT-AS-

C7-11A-P3

C12-11A-P3

Minimum fuse protec-
tion

1.5

2)

10

16

Maximum fuse protection of an individual device or a device group
without heat-resistant
cable

4

25

6

32

with heat-resistant
cable

3)

4

32

6

40

1) Specifications according to DIN VDE 0298-4:2013, permissible currents according to EN 60204-1 may

differ (depending on installation type and temperature)

2) depending on the type of installation of the cables, wiring with min. 2.5 mm² may be required for the

CMMT-AS-C12-11A-P3.

3) no derating up to an ambient temperature of 50 °C and a cable temperature higher than 70 °C (max. cable

temperature 90 °C)

Tab. 14: Line protection requirements

Fuse protection when load circuit is supplied with DC power
The CMMT-AS allows the load circuit to be supplied with DC power. With DC
power, external fuse protection is once again required in the form of short circuit
protection and line protection. The fuse that is used must be capable of reliably
disconnecting the maximum DC supply voltage that could occur and the potential
short circuit current (SCCR

DC

).

Maximum fuse protection: 40 A

If fuse protection is to be avoided on the DC side, check whether the fuse protec-
tion could alternatively be installed on the AC side upstream of the DC fixed power
supply.

7.4

Permissible and impermissible mains types of system earthing

Information on allowed and prohibited mains types of system earthing and neces-
sary measures for use in IT networks 

è

 Manual Assembly, Installation.

Leakage currents in IT systems
High-frequency leakage currents to protective earthing (PE) may be encountered
even in IT systems (IT = Isolé Terre) during operation of the servo drive. The
leakage currents flow to the PE through the coupling capacitances of the motor
cable and the motor and back to the servo drive through the coupling capacitance
of the isolating transformer via the load supply. The coupling capacitances can be
minimised by selection of a suitable isolating transformer and keeping the motor
cable as short as possible.

WARNING

Risk of injury from electric shock.
The servo drive generates high-frequency leakage currents, which can lead to
dangerous contact currents on the external conductors and the neutral conductor
of the IT system. Touching the mains conductor or the neutral conductor can result
in serious injuries or death.
• Before working on the IT systems, disconnect the servo drive from the mains.

7.5

Connection of the mains side PE conductor

All PE conductors must always be connected prior to commissioning for safety
reasons. Observe the regulations of EN 60204-1 when implementing protective
earthing.

Summary of Contents for CMMT-AS-C7/12-11A-P3-S1

Page 1: ...and an 11 character alphanumeric code Festo SE Co KG Manufacturer DE 73734 Esslingen Manufacturer s address Made in Germany Country of origin Germany Tab 2 Product labelling example Warning symbols on the front of the product Warnin g symbol Meaning with the CMMT AS Attention Hot surface Metallic housing parts of the device can reach high temperatures during operation In the event of a fault inter...

Page 2: ...hold the motor and axis in position at standstill The safety sub function SS1 is intended for performing a rapid stop with subse quent torque switch off 2 2 1 Application areas The device is intended for use in an industrial environment and with appropriate measures in commercial residential and mixed areas The device is intended for installation in a control cabinet The minimum degree of protecti...

Page 3: ...24 V DC PELV 5 External braking resistor optional 6 Servo drive CMMT AS 7 Servo motor here EMME AS 8 PC with Ethernet connection for parameterisation 4 2 1 Overview of connection technology 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Fig 2 Connections of the CMMT AS C7 C12 11A P3 example 1 PE connection housing 2 X9A Mains and DC link circuit connection 3 X9C Logic voltage 4 XF2 OUT RTE interface port ...

Page 4: ...BC may only be used for holding brakes or clamping units which engage in the de energised state Ensure the lines are protected when installed SBC request The safety sub function SBC is requested on 2 channels by simultaneously switching off the control voltage at both control inputs SBC A and SBC B The SBC A request switches off the power to the signals BR BR The SBC B request switches off the pow...

Page 5: ...ring For DC link coupling higher power devices must be placed closer to the mains supply If there is a voltage supply to the device when the control cabinet is open vertical access to the bottom and top of the device must be prevented For mounting on the rear wall of the control cabinet the servo drive cooling element has a slot on the top in the shape of a keyhole and an ordinary slot on the bott...

Page 6: ...current of 3 5 mA or a DC current of 10 mA Always connect both protective earthing connections to the mains side PE connection the PE pin of X9A and PE earthing screw on the housing The minimum cross section of the protective earthing conductor must comply with the local safety regulations for protective earthing conductors for equipment with high leakage current 7 3 Mains fuse The CMMT AS does no...

Page 7: ...t up and commissioning are performed by a professional with the neces sary experience for setting up and commissioning drive systems including their EMC aspects category C2 devices can be used in the first environment residential area For operation of category C2 devices limit values for the harmonic currents in the network EN 61000 3 2 or EN 61000 3 12 apply depending on the connected load of the...

Page 8: ...Control input Safe torque off channel B 10 SBC A Control input Safe brake control channel A X1A Pin Function Description 9 SBC B Control input Safe brake control channel B 8 reserved do not connect 7 6 5 4 ERR RST Error acknowledgement 3 CTRL EN Power stage enable 2 AIN0 Differential analogue input 1 AIN0 Tab 16 Inputs and outputs for the higher order PLC with the CMMT AS S1 Requirements for the c...

Page 9: ...der emulation Incremental encoder input Input of a slave axis for receiving the encoder signals of a master axis Tab 23 Possible functions of the connection X10 Requirements for the connecting cable Characteristics Encoder cable for servo drives shielded Optical shield cover 85 Separately twisted signal pairs recommended design 4 x 2 x 0 25 mm2 Max cable length 3 m Tab 24 Requirements for the conn...

Page 10: ...mperature posi tive potential 4 FE Functional earth con nected to protective earth 3 BR Holding brake negative potential 2 BR Holding brake positive potential 1 FE Functional earth con nected to protective earth Tab 33 Motor auxiliary connection Requirements for the connecting cable Design 2 wires for the line to the holding brake twisted in pairs separately shielded 2 wires for the line to the te...

Page 11: ...ase of block mounting the shield clamp makes full contact with the base of the housing cable diameter 12 mm Minimum tightening torque with larger cable diameter 12 mm 23 mm 0 5 Nm 15 With a higher tightening torque make sure the con necting cable does not get crushed in the clamping area due to excessive pressure Tab 36 Tightening torque and clamping range CMMT AS C7 C12 11A P3 1 2 3 4 5 Fig 11 Sh...

Page 12: ...h 2 m Wiring inside the control cabinet shield connected to PE Tightening torque of the screw terminals on the mating plug GIC 2 5 HCV 2 ST 7 62 0 5 0 6 Nm1 1 Specification of the manufacturer at the time the documentation was approved Tab 42 Requirements for the connecting cable Selection of suitable braking resistors Information on selecting suitable braking resistors è Manual Assembly Installa ...

Page 13: ...Establish the connection to the CMMT AS and set network configuration 5 Identify the technical data of the components that is required for configura tion 8 3 Commissioning steps NOTICE Unwanted drive movements or damage to components Incorrect parameterisation may result in unwanted drive movements or overload when the closed loop controller is enabled or may lead to connected components becoming ...

Page 14: ... safety sub function has been requested Tab 49 Safety LED 11 2 Repair Repair or maintenance of the product is not permissible If necessary replace the complete product 1 If there is an internal defect Always replace the product 2 Send the defective product unchanged together with a description of the error and application back to Festo 3 Check with your regional Festo contact person to clarify the...

Page 15: ...onformity The protection objectives of the Low Voltage Directive are fulfilled in accordance with the requirements of the EC Machinery Directive The requirements of the Low Voltage Directive are based on the product standard EN 61800 5 1 The valid version of the product standard is listed in the declaration of conformity General technical data Type ID code CMMT AS Type of mounting Mounting plate a...

Page 16: ... power VRMS 380 Output frequency Hz 0 599 Duration for maximum current fs 5 Hz s 2 Duration for maximum current at standstill fs 5 Hz min imum cycle time 1 s s 0 1 Tab 63 Power specifications motor connection X6A 13 4 Technical data UL CSA certification In combination with the UL inspection mark on the product the information in this section must also be observed in order to comply with the certif...

Reviews: