28
Festo — CMMP-AS-...-M0 — 2022-07c
Commissioning
Characteristics
Display
Status
Output X40.C1/C2:
Display of the relay contact
Orange
Safety function active, relay contact closed
Grey
Safety function inactive, relay contact open
Tab. 10: Status of the safety function
5.2.2
Displaying log file of the motor controller
Error and status messages are logged non-volatile in the permanent diagnostic memory of the
CMMPAS-...-M0. You can read this out in the online ‘Diagnostics’ tab
Fig. 8: FCT plug-in CMMP-AS: "Diagnostics" tab
5.3
Function test, validation
NOTICE
The STO function must be validated after installation and after changes to the installation.
This validation must be documented by the person who commissions the device. To assist you with
the commissioning, questions for risk reduction are summarised below in the form of sample check
lists.
The following check lists are no substitute for training in safety engineering.
The completeness of the check lists cannot be guaranteed.
No. Questions
Relevant
Done
1.
Have all operating conditions and interventions been taken
into account?
Yes
0
No
0
0
2.
Has the 3-step method for risk reduction been applied,
i.e.: 1. Inherently safe design, 2. Technical and any addi-
tional protective measures, 3. User information about the
residual risk?
Yes
0
No
0
0
3.
Have the hazards been eliminated or the hazard risks
reduced as far as practically possible?
Yes
0
No
0
0
4.
Can it be guaranteed that the implemented measures do not
create new hazards?
Yes
0
No
0
0