Commissioning
86
© Festo Didactic 696688
6.7.3 Allen Bradley controllers
•
Controller: Micrologix (ML) 1500
•
Programming software: RSLogix 500/RSLINXLite
1. Connect the PC and controller using the RS232-programming cable
2. Switch on the power pack
3. Release the EMERGENCY-STOP pushbutton (if available)
Note
•
The prerequisite to the steps below is a previously effected configuration of the
required online parameters (network node, driver) using RSLINXLite/RSLogix
500!
•
To avoid any conflict with the serial interface, also complete RSLINXLite after
using RSLogix 500!
CPU ML 1500
- Configuration of online parameters
–
Wait until the PLC has completed its test routines.
–
Start RSLINXLite.
Under
Communications
Configure Drivers…
select the setting “RS-232 DF1 devices“ in the list “Available
Driver Types“ and click onto
Add New…
confirm message (“Choose a name…“, Default: AB_DF1-1) with
OK
Auto configure
OK
Close