background image

19

CONNECTIONS

Electrical connections

The electrical wiring must be carried out by qualified personnel in conformity with the current regulations in the country of use at
the time of installation. Before carrying out any work on the electrical system make sure the unit’s power supply line is
disconnected at the start.

N.B.

Refer to the wiring diagram attached to the unit.

Connection to the power supply

The units come completely factory-wired and arranged for connection to the mains.
The power cables of the unit’s supply line must be taken :
-

for units with 

single-phase

power supply : from a single-phase voltage system provided with neutral wire and separate

earth wire;

V = 230 V ± 10 %

f = 50 Hz

-

for units with 

three-phase

power supply : from a symmetrical three-phase voltage system provided with neutral wire and

separate earth wire.

V = 400 V ± 10 %

f = 50 Hz

The power cables must enter the unit through the holes provided in the side panel  and be connected to the unit’s main switch.
The earth wire coming from the power supply line must be connected directly to the plate on the electrical panel to ensure the
equipotential connections of all the metal earths and the structural parts of the unit. The cables must be integrally fixed to the
unit’s structure using the special cable clamp on the electrical panel.

IMPORTANT

The power cables must have a section adequate for the power absorbed by the unit and be sized in conformity with the current
regulations. For sizing of the power supply line, always refer to the unit’s total FLI and FLA values, taking into account any
accessories fitted.

Protection upstream

An automatic switch suitable for ensuring protection against overcurrents and indirect contacts must be installed upstream.
Coordination between the line and switch must be carried out in compliance with the current regulations on electrical safety,
regarding the type of installation and the installation ambient conditions.

Connections to be made by the user

The wiring board inside the electrical panel contains dedicated terminals for the following connections.
General alarm
Live output (230V - max 2A) to be used for signalling the presence of an active alarm.
Output active : alarms present
Output not active : alarms absent
Remote standby
A remote device for turning the unit On/Off (selector, programmer clock, centralised supervision device, etc.) with a voltage-free
contact suitable for switching loads of very low power can be connected.
This function must be enabled by means of parameter (see the section “Adjustment and control”) and has priority over settings
made from keyboard.
Remote cooling-heating
It is possible to switch between cooling mode and heating mode from remote by connecting a device equipped with a voltage-
free contact suitable for switching loads of very low power.
This function must be enabled by means of parameter (see the section “Adjustment and control”) and has priority over settings
made from keyboard.
Remote control
It is possible to connect a remote control that has all the control and display functions available on the unit’s interface and
therefore enable complete remote control.
Pump control
The unit’s controller can directly activate the circulating pump by means of a voltage-free contact (max. absorption 4A).

The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors.

Summary of Contents for RXA

Page 1: ...RXA AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS TECHNICAL MANUAL...

Page 2: ...2...

Page 3: ...ICAL DATA 9 NOMINAL PERFORMANCE IR 10 NOMINAL PERFORMANCE IP 10 PERFORMANCE IN COOLING IR AND IP 11 PERFORMANCE IN HEATING IP 12 WEIGHTS OF UNITS 13 ELECTRICAL DATA 13 NOISE LEVELS 13 PRESSURE LOSSES...

Page 4: ...4...

Page 5: ...temperature in cooling mode and with high outdoor temperature in heating mode as well as to reduce noise emissions in such operating conditions All three phase power supply units are provided with a p...

Page 6: ...e and to limit heat loss to the outside It is protected against the risk of ice forming by an antifreeze heating element activated according to the water temperature and by a differential pressure swi...

Page 7: ...rface are accessible from the outside by opening a hermetic door The main components are main switch thermal magnetic microprocessor controller with user interface and incorporated phase cut card comp...

Page 8: ...also substitute the tank antifreeze heating element accessory RAG Remote control CR The remote control is suitable for wall mounting and has all the control and display functions available on the unit...

Page 9: ...ion speed 900 rpm Total installed power 0 15 0 21 0 42 kW Plate type heat exchanger Type braze welded plates Quantity 1 n Water content 0 29 0 29 0 46 0 46 0 46 0 46 0 53 0 72 l Finned coil Type coppe...

Page 10: ...15 6 65 kW Total EER VB E 2 79 2 49 2 49 2 49 2 55 2 55 2 64 2 57 Water delivery 1032 1221 1582 1582 1823 1823 2339 2941 l h Pressure losses VB E 26 35 25 25 32 32 39 34 kPa Useful head VP VA 75 62 17...

Page 11: ...pplied to the nominal performance values air 35 C bs air 12 7 C for obtaining the real performance values in the chosen operating conditions 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 30 1 40 15 20 25 30 35...

Page 12: ...he nominal performance values air 7 C bs 6 C bu water 40 45 C for obtaining the real performance values in the chosen operating conditions 0 60 0 70 0 80 0 90 1 00 1 10 1 20 1 30 1 40 15 10 5 0 5 10 1...

Page 13: ...8 5 8 5 8 6 7 6 7 8 4 10 1 kW M I C Total max peak current 49 8 68 8 89 1 48 1 121 1 51 1 67 1 70 1 A Supplementary electrical heating elements 3 3 kW F L A Total max absorbed current 14 3 14 3 14 3 4...

Page 14: ...00 1500 2000 2500 3000 3500 4000 Portata l h Perdite di carico kPa 0 20 40 60 80 100 120 140 160 180 200 220 240 260 0 500 1000 1500 2000 2500 3000 3500 4000 Portata l h Prevalenza residua kPa 7 1 6 1...

Page 15: ...cellation of the product warranty contract Thermal head of water treated by the unit Minimum 3 C Maximum 8 C 10 5 0 5 10 15 20 25 30 35 5 0 5 10 15 20 25 30 35 40 45 50 55 Tbs aria esterna C T acqua p...

Page 16: ...me 1 2 3 U M Model 6 1 7 1 9 1 11 1 14 1 17 1 Version VB VP VA VB VP VA VB VP VA A 903 1153 1453 mm B 509 759 1059 mm C1 570 820 1120 mm C2 545 646 946 mm C3 799 928 1228 mm D 839 1089 1389 mm E 142 9...

Page 17: ...the refrigerating capacity input water delivery and pressure losses 3 Keep the unit electrically connected throughout the winter The plate type exchanger is protected by the antifreeze heating element...

Page 18: ...efilling pressure increases the maximum volume of the system supported by the expansion tank supplied standard decreases If the actual volume of the system is greater than that maximum value an additi...

Page 19: ...ed Protection upstream An automatic switch suitable for ensuring protection against overcurrents and indirect contacts must be installed upstream Coordination between the line and switch must be carri...

Page 20: ...Cod 3QE23691...

Reviews: