10
TECHNICAL DATA AND PERFORMANCE
Nominal performance IR
Nominal performance IP
Frame
1
2
3
Model
6.1
7.1
9.1
11.1
14.1
17.1
U.M.
Electrical power supply
230-1-50
230-1-50
400-3N-50
230-1-50
400-3N-50
400-3N-50
V-ph-Hz
Cooling
(air 35 °C bs / water 12 - 7 °C )
Refrigerating capacity
(E)
6,20
7,40
9,40
9,40
10,8
10,8
13,8
17,3
kW
Total input
(VB) (E)
2,15
2,85
3,70
3,70
4,15
4,15
5,15
6,65
kW
total EER
(VB) (E)
2,88
2,60
2,54
2,54
2,60
2,60
2,68
2,60
-
Water delivery
1066
1273
1617
1617
1858
1858
2374
2976
l/h
Pressure losses
(VB) (E)
28
38
26
26
33
33
40
35
kPa
Useful head
(VP-VA)
73
58
170
170
152
152
122
96
kPa
Cooling
(air 35 °C bs / water 23 - 18 °C )
Refrigerating capacity
7,40
8,90
11,3
11,3
13,0
13,0
16,6
20,8
kW
Total input
(VB)
2,20
2,90
3,80
3,80
4,25
4,25
5,30
6,85
kW
Total EER
(VB)
3,36
3,07
2,97
2,97
3,06
3,06
3,13
3,04
-
Water delivery
1273
1531
1944
1944
2236
2236
2855
3578
l/h
Pressure losses
(VB) (E)
38
53
36
36
46
46
56
49
kPa
Useful head
(VP-VA)
58
37
146
146
122
122
82
49
kPa
ESEER
(VB)(E)
3,26
2,94
2,88
2,88
2,94
2,94
3,04
2,94
-
Frame
1
2
3
Model
6.1
7.1
9.1
11.1
14.1
17.1
U.M.
Electrical power supply
230-1-50
230-1-50
230-1-50
400-3N-50
230-1-50
400-3N-50 400-3N-50 400-3N-50 V-ph-Hz
Cooling
(air 35 °C bs / water 12 - 7 °C )
Refrigerating capacity
(E)
6,00
7,10
9,20
9,20
10,6
10,6
13,6
17,1
kW
Total input
(VB) (E)
2,15
2,85
3,70
3,70
4,15
4,15
5,15
6,65
kW
Total EER
(VB) (E)
2,79
2,49
2,49
2,49
2,55
2,55
2,64
2,57
-
Water delivery
1032
1221
1582
1582
1823
1823
2339
2941
l/h
Pressure losses
(VB) (E)
26
35
25
25
32
32
39
34
kPa
Useful head
(VP-VA)
75
62
173
173
155
155
124
99
kPa
Cooling
(air 35 °C bs / water 23 - 18 °C )
Refrigerating capacity
7,20
8,50
11,0
11,0
12,8
12,8
16,3
20,5
kW
Total input
(VB)
2,20
2,90
3,80
3,80
4,25
4,25
5,30
6,85
kW
Total EER
(VB)
3,27
2,93
2,89
2,89
3,01
3,01
3,08
2,99
-
Water delivery
1238
1462
1892
1892
2202
2202
2804
3526
l/h
Pressure losses
(VB) (E)
36
49
34
34
45
45
54
48
kPa
Useful head
(VP-VA)
60
43
150
150
125
125
86
53
kPa
ESEER
(VB)(E)
3,16
2,82
2,82
2,82
2,89
2,89
2,99
2,91
-
Heating
(air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heat output
(E)
7,00
8,20
10,4
10,4
11,5
11,5
15,3
18,6
kW
Total input
(VB) (E)
2,25
2,75
3,65
3,65
4,05
4,05
4,95
6,40
kW
Total COP
(VB) (E)
3,11
2,98
2,85
2,85
2,84
2,84
3,09
2,91
-
Water delivery
1204
1410
1789
1789
1978
1978
2632
3199
l/h
Pressure losses
(VB) (E)
34
46
31
31
37
37
48
40
kPa
Useful head
(VP-VA)
63
47
157
157
143
143
101
79
kPa
Heating
(air 7 °C bs - 6 °C bu / water 30 - 35 °C )
Heat output
7,20
8,40
10,6
10,6
11,7
11,7
15,6
19,0
kW
Total input
(VB)
1,90
2,35
3,05
3,05
3,40
3,40
4,15
5,40
kW
Total COP
(VB)
3,79
3,57
3,48
3,48
3,44
3,44
3,76
3,52
-
Water delivery
1238
1445
1823
1823
2012
2012
2683
3268
l/h
Pressure losses
(VB) (E)
36
48
32
32
38
38
50
42
kPa
Useful head
(VP-VA)
60
44
155
155
140
140
97
74
kPa
(VB) :
only for base version
VB
(VP-VA) :
only for pump version
VP
and tank version
VA
(E) :
data declared according to
EUROVENT