54
EN
Cod. 3541V950 - Rev. 00 - 05/2021
OMNIA S 3.2
9.3.2 Temperature curves for cooling mode
CLIMATIC CURVES (WTS) COOLING MODE
T4 (T_outdoor_air) [°C]
-10
14
15
21
22
29
30
46
id Climatic curve
Terminal Type
selected on remote
controller
Climatic curves
set
T1S or T2S
(Water flow Temp) [°C]
16,0
16,0
11,0
11,0
8,0
8,0
5,0
5,0
1
Fancoil
C1
17,0
17,0
12,0
12,0
9,0
9,0
6,0
6,0
2
18,0
18,0
13,0
13,0
10,0
10,0
7,0
7,0
3
19,0
19,0
14,0
14,0
11,0
11,0
8,0
8,0
4
20,0
20,0
15,0
15,0
12,0
12,0
9,0
9,0
5
21,0
21,0
16,0
16,0
13,0
13,0
10,0
10,0
6
22,0
22,0
17,0
17,0
14,0
14,0
11,0
11,0
7
23,0
23,0
18,0
18,0
15,0
15,0
12,0
12,0
8
20,0
20,0
18,0
18,0
17,0
17,0
16,0
16,0
1
Radiant floor Heating
or radiator
C2
21,0
21,0
19,0
19,0
18,0
18,0
17,0
17,0
2
22,0
22,0
20,0
20,0
19,0
19,0
17,0
17,0
3
23,0
23,0
21,0
21,0
19,0
19,0
18,0
18,0
4
24,0
24,0
21,0
21,0
20,0
20,0
18,0
18,0
5
24,0
24,0
22,0
22,0
20,0
20,0
19,0
19,0
6
25,0
25,0
22,0
22,0
21,0
21,0
19,0
19,0
7
25,0
25,0
23,0
23,0
21,0
21,0
20,0
20,0
8
4
6
8
10
12
14
16
18
20
22
24
-10
0
10
20
30
40
50
COOLING MODE (climatic curves set C1)
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
14
16
18
20
22
24
26
-10
0
10
20
30
40
50
COOLING MODE (climatic curves set C2)
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Climatic curve 9 in cooling mode settable by the user
The climatic curve 9 is defined by 4 parameters that can be set by the user (T4C1, T4C2, T1SETC1, T1SETC2, refer to “9.2 Service parameters table” on page 50).
T4C1
T4C2
T1SETC2
T1SETC1
T4
T1S (T1S2)
fig. 39 - Climatic curve 9 in cooling mode