12
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - STANDARD plants
Data declared according to
EN 14511 .
The values are referred to units without options or accessories.
IP
Heating A7W45
( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
46,9
54,1
63,7
71,1
80,2
93,6
kW
Power input
12,5
14,5
17,0
19,0
21,4
25,1
kW
COP
3,75
3,73
3,75
3,74
3,75
3,73
-
Water flow rate plant side
8133
9367
11036
12322
13903
16215
l/h
Pressure drops plant side
19
20
21
22
19
19
kPa
Heating A2W45
( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
38,8
44,7
52,6
58,7
66,3
77,4
kW
Power input
12,3
14,3
16,7
18,7
21,0
24,8
kW
COP
3,15
3,13
3,15
3,14
3,16
3,12
-
Water flow rate plant side
6726
7751
9124
10184
11505
13417
l/h
Pressure drops plant side
14
14
15
15
14
14
kPa
Heating A-7W45
( source : air in -7°C d.b. -8°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
31,2
36,0
42,3
47,3
53,3
62,2
kW
Power input
11,9
13,9
16,3
18,2
20,5
24,0
kW
COP
2,62
2,59
2,60
2,60
2,60
2,59
-
Water flow rate plant side
5422
6239
7334
8203
9246
10792
l/h
Pressure drops plant side
9
9
10
10
9
9
kPa
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
38,7
44,6
52,5
58,6
66,1
77,1
kW
Power input
12,2
14,1
16,6
18,6
20,9
24,6
kW
EER
3,17
3,16
3,16
3,15
3,16
3,13
-
Water flow rate plant side
6659
7671
9027
10074
11361
13266
l/h
Pressure drops plant side
14
14
15
15
13
14
kPa
Frame
1
2
3
Model
45 .2
55 .2
65 .2
75 .2
85 .2
95 .2
U.M.
Power supply
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
V-ph-Hz