![Ferroli HGP 45.2 Technical Manual Download Page 11](http://html1.mh-extra.com/html/ferroli/hgp-45-2/hgp-45-2_technical-manual_2282183011.webp)
11
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - HIGH TEMPERATURE plants
IP
Heating A7W55
( source : air in 7°C d.b. 6°C w.b. / plant : water in 47°C out 55°C )
Heating capacity
45,1
51,9
61,2
68,4
77,1
90,0
kW
Power input
14,4
16,7
19,7
22,1
24,8
29,0
kW
COP
3,13
3,11
3,11
3,10
3,11
3,10
-
Water flow rate plant side
4914
5655
6658
7442
8390
9796
l/h
Pressure drops plant side
8
8
9
9
8
8
kPa
Heating A2W55
( source : air in 2°C d.b. 1°C w.b. / plant : water in 47°C out 55°C )
Heating capacity
37,0
42,5
50,1
56,0
63,1
73,6
kW
Power input
14,3
16,5
19,4
21,8
24,5
28,7
kW
COP
2,59
2,58
2,58
2,57
2,58
2,56
-
Water flow rate plant side
4032
4631
5459
6102
6876
8020
l/h
Pressure drops plant side
5
5
6
6
5
5
kPa
Heating A-7W55
( source : air in -7°C d.b. -8°C w.b. / plant : water in 47°C out 55°C )
Heating capacity
-
-
-
-
-
-
kW
Power input
-
-
-
-
-
-
kW
COP
-
-
-
-
-
-
-
Water flow rate plant side
-
-
-
-
-
-
l/h
Pressure drops plant side
-
-
-
-
-
-
kPa
Data declared according to
EN 14511 .
The values are referred to units without options or accessories.
Frame
1
2
3
Model
45 .2
55 .2
65 .2
75 .2
85 .2
95 .2
U.M.
Power supply
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
400 - 3 - 50
V-ph-Hz