NOMINAL performances - RADIANT plants

Data declared according to 

EN 14511 .

 The values are referred to units without options or accessories.

TECHNICAL DATA AND PERFORMANCES

IP

Heating  A7W35  

( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )

Heating capacity

48,2

55,4

65,2

72,9

82,2

95,8

kW

Power input

10,3

11,9

14,0

15,7

17,7

20,7

kW

COP

4,68

4,66

4,66

4,64

4,64

4,63

-

Water flow rate plant side

8313

9559

11257

12573

14183

16538

l/h

Pressure drops plant side

20

20

22

22

20

20

kPa

Heating  A2W35  

( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )

Heating capacity

40,0

46,0

54,1

60,5

68,3

79,6

kW

Power input

10,1

11,7

13,7

15,4

17,3

20,3

kW

COP

3,96

3,93

3,95

3,93

3,95

3,92

-

Water flow rate plant side

6910

7949

9352

10443

11793

13750

l/h

Pressure drops plant side

14

15

16

16

14

14

kPa

Heating  A-7W35  

( source : air in -7°C d.b. -8°C w.b. / plant : water in 30°C out 35°C )

Heating capacity

32,4

37,3

43,9

49,0

55,3

64,4

kW

Power input

9,72

11,3

13,3

14,8

16,7

19,5

kW

COP

3,33

3,30

3,30

3,31

3,31

3,30

-

Water flow rate plant side

5594

6442

7585

8468

9559

11135

l/h

Pressure drops plant side

10

10

11

11

10

10

kPa

Cooling  A35W18 

 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )

Cooling capacity

50,9

58,7

69,0

77,1

87,0

102,0

kW

Power input

13,2

15,3

18,1

20,2

22,7

26,7

kW

EER

3,86

3,84

3,81

3,82

3,83

3,82

-

Water flow rate plant side

8811

10156

11949

13345

15052

17570

l/h

Pressure drops plant side

23

23

25

25

22

22

kPa

Frame

1

2

3

Model

45 .2

55 .2

65 .2

75 .2

85 .2

95 .2

U.M.

Power supply

400 - 3 - 50

400 - 3 - 50

400 - 3 - 50

400 - 3 - 50

400 - 3 - 50

400 - 3 - 50

V-ph-Hz

Summary of Contents for HGP 45.2

Page 1: ...HGP AIR WATER HEAT PUMPS FOR INDOOR INSTALLATION TECHNICAL MANUAL R E F R I G E R A N T G A S E C O FRIEND L Y...

Page 2: ...s all the responsabilities regarding inaccuracies contained in this manual if due to printing or typing mi stakes The manufacturer reserves the right to apply changes and improvements to the products...

Page 3: ...ata 10 NOMINAL performances HIGH TEMPERATURE plants 11 NOMINAL performances STANDARD plants 12 NOMINAL performances RADIANT plants 13 HEATING performances 14 COOLING performances 15 Plant side hydraul...

Page 4: ...4...

Page 5: ...air flow to simplify the maintenance operations is equipped with two scroll compressors mounted on damper supports brazed plate heat exchangers electronic expansion valve reverse cycle valve centrifu...

Page 6: ...lter dryer 5 to restrain impurity and moisture residuals that could be present in the circuit high and low pressure switches in order to assure the compressor to operate inside the permitted limits 4...

Page 7: ...rmostats are available which allow to control all the operating parameters of the unit and to acquire the temperature in the different zones in order to realize a more precise and comfortable control...

Page 8: ...e temperature difference between inlet and outlet Domestic hot water production 3 way valve Allow to divert the hot water produced by the heat pump from the heating circuit to the domestic hot water c...

Page 9: ...sensor can be used in order to realize a climatic control Remote control wired or wireless Replicates all the control and visualization functionalities of the controller installed on the unit The on...

Page 10: ...0 mm Maximum rotational speed 1560 1560 1560 1560 1560 1560 rpm Total installed power 6 20 6 20 9 30 9 30 12 4 12 4 kW Plant side hydraulic circuit Safety valve set point 6 6 6 6 6 6 bar Expansion ves...

Page 11: ...47 C out 55 C Heating capacity 37 0 42 5 50 1 56 0 63 1 73 6 kW Power input 14 3 16 5 19 4 21 8 24 5 28 7 kW COP 2 59 2 58 2 58 2 57 2 58 2 56 Water flow rate plant side 4032 4631 5459 6102 6876 8020...

Page 12: ...15 3 14 3 16 3 12 Water flow rate plant side 6726 7751 9124 10184 11505 13417 l h Pressure drops plant side 14 14 15 15 14 14 kPa Heating A 7W45 source air in 7 C d b 8 C w b plant water in 40 C out...

Page 13: ...93 3 95 3 92 Water flow rate plant side 6910 7949 9352 10443 11793 13750 l h Pressure drops plant side 14 15 16 16 14 14 kPa Heating A 7W35 source air in 7 C d b 8 C w b plant water in 30 C out 35 C...

Page 14: ...der to obtain the real performances in the selected operating conditions The reference nominal condition is A7W35 source air in 7 C d b 6 C w b plant water in 30 C out 35 C Outlet temperature plant si...

Page 15: ...45 50 Cooling capacity Inlet air temperature d b C Inlet air temperature d b C Inlet air temperature d b C Power input EER A B C D A B C D A B C D The graphs allow to get the corrective factors to be...

Page 16: ...density 1000 kg m3 Flow rate l h Flow rate l h Pressure drops unit without options Pressure drops to be added unit with option Domestic hot water production 3 way valve Pressure drops kPa Pressure dro...

Page 17: ...option Plant side flow rate management Standard pump and Modulating pump Available static head unit with option Plant side flow rate management High head pump Available static head kPa Available stat...

Page 18: ...section must guarantee that the medium air velocity does not exceed 2 5 m s in order to avoid noise problems and to keep the pressure drops as lower as possible The rotational speed of the fans can b...

Page 19: ...6916 7980 9387 10486 11824 13798 l h Pressure drops plant side 15 15 16 16 15 15 kPa Heating capacity desuperheater 11 9 13 7 16 2 18 1 20 4 23 8 kW EER with heat recovery 4 38 4 39 4 40 4 34 4 37 4 3...

Page 20: ...lant side DT max Maximum value 11 C DT min Minimum value 3 C HEATING Inlet air temperature d b C Outlet temperature plant side C The graphs reported below show the operating area inside which the corr...

Page 21: ...V ph Hz F L A Maximum total current input 2 5 2 5 2 5 2 5 2 5 2 5 A F L I Maximum total power input 1 5 1 5 1 5 1 5 1 5 1 5 kW Power supply 400 3 50 400 3 50 400 3 50 400 3 50 400 3 50 400 3 50 V ph H...

Page 22: ...y octave bands Hz Sound power level Sound pressure level at 1 metre at 5 metres at 10 metres 63 125 250 500 1000 2000 4000 8000 dB dB A dB A dB A dB A 45 2 88 9 83 2 78 1 77 0 75 1 72 2 66 4 61 4 91 8...

Page 23: ...ons 727 764 920 932 1085 1104 kg Options Version Desuperheater version VD 19 19 23 27 31 31 kg Acoustic setting up Low noise setting up AS 65 65 75 75 85 85 kg Plant side flow rate management Standard...