![Ferroli ENERGY TOP W 125 Instructions For Use, Installation And Maintenance Download Page 55](http://html1.mh-extra.com/html/ferroli/energy-top-w-125/energy-top-w-125_instructions-for-use-installation-and-maintenance_2281994055.webp)
ENERGY TOP W 70 - W 80 - W 125
55
EN
Table of faults
Table. 5 - List of faults
5. TECHNICAL DATA AND CHARACTERISTICS
Key of figures cap. 5
7
Gas inlet
10
System delivery
11
System return
16
Fan
22
Main burner
29
Fume outlet manifold
32
Heating circulating pump (not supplied)
36
Automatic air vent
38
Flow switch
44
Gas valve
72
Room thermostat (not supplied)
72b
Second room thermostat (not supplied)
81
Ignition electrode
82
Detection electrode
95
Diverter valve (not supplied)
A
= Heating phase
B
= DHW phase
C
= Neutral
NOTE:
For valves with 2 wires and spring return, use the connections B and C
98
Switch
114
Water pressure switch
130
DHW circulating pump (not supplied)
138
External probe (not supplied)
139
Remote timer control (not supplied)
154
Condensate drain pipe
155
Hot water tank temperature probe (not supplied)
186
Return sensor
191
Fume temperature sensor
193
Trap
196
Condensate tray
215
Air inlet reducer
220
Ignition card
256
Modulating heating circulating pump signal
278
Double sensor ( Heating)
298
Cascade temperature sensor (not supplied)
299
Input 0-10 Vdc
300
Burner lit contact (voltage-free contact)
301
Fault contact (voltage-free contact)
302
Remote reset input (230 Volt)
306
Heating system circulating pump (not supplied)
307
Heating system second circulating pump (not supplied)
345
Exchanger safety thermostat
Fault
code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the
boiler and that the air has been
eliminated from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Faulty gas valve
Check the gas valve and replace it if
necessary
Insufficient gas supply pressure
Check the gas supply pressure
Trap blocked
Check the trap and clean it if
necessary
A02
Flame present signal with
burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
A03
Overtemperature protection
activated
Heating sensor damaged
Check the correct positioning and
operation of the heating sensor
No water circulation in the system Check the circulating pump
Air in the system
Vent the system
A04
Fume extraction duct safety
device activated
Fault F07 generated 3 times in
the last 24 hours
See fault F07
A05
Fan protection activated
Fault F15 generated for 1 hour
(consecutive)
See fault F15
A06
No flame after ignition stage (6
times in 4 minutes)
Ionisation electrode fault
Check the position of the ionisation
electrode and replace it if necessary
Flame unstable
Check the burner
Gas valve Offset fault
Check the Offset adjustment
at minimum power
air/fume ducts obstructed
Remove the obstruction from the flue,
fume extraction ducts and air inlet and
terminals
Trap blocked
Check the trap and clean it if
necessary
F07
High fume temperature
Flue partially obstructed or
insufficient
Check the efficiency of the flue, fume
extraction ducts and outlet terminal
Fume sensor position
Check the correct positioning and
operation of the fume sensor
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace
the sensor
Wiring shorted
Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace
the sensor
Wiring shorted
Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace
the sensor
Wiring shorted
Wiring disconnected
F13
Fume sensor fault
Sensor damaged
Check the wiring or replace
the sensor
Wiring shorted
Wiring disconnected
EXCHANGER SAFETY THER-
MOSTAT ACTIVATED
CHECK THE BOILER SHELL AND
CLEAN IT IF NECESSARY
Check the thermostat and replace it if
necessary
Check the thermostat wiring
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace
the sensor
Wiring shorted
Wiring disconnected
F15
Fan fault
No 230V power supply
Check the 3-pin connector wiring
Tachometric signal interrupted
Check the 5-pin connector wiring
Fan damaged
Check the fan
F26
RESET button on DBM12
controller on gas valve, fault
RESET button on DBM12 controller
on gas valve, blocked or faulty
Check the RESET button and replace
the DBM12 controller if necessary
F34
Supply voltage under 170V
Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F37
Flowswitch or pressure switch
contact open
Insufficient system pressure or
circulation
Check the system water pressure or
for air in the system
Circulating pump not working
Check the circulating pump
Wrong card parameter setting
Check the card parameter and modify
it if necessary
F38
Flowswitch contact blocked
closed
Flowswitch dirty or blocked
Clean the flowswitch or replace it if
necessary
F39
External probe fault
Probe damaged or wiring shorted
Check the wiring or replace
the sensor
Probe disconnected after
activating the sliding temperature
Reconnect the external probe
or disable the sliding temperature
A41
Sensor positioning
Delivery sensor disconnected
from the pipe
Check the correct positioning and
operation of the heating sensor
A42
Heating sensor fault
Sensor damaged
Replace the sensor
F42
Heating sensor fault
Sensor damaged
Replace the sensor
F50
Cascade temperature sensor
fault
Sensor damaged
Check the wiring or replace
the sensor
Wiring shorted
Wiring disconnected
A61
Controller DBM12 fault
Controller DBM12 internal error
Check the earth connection and
replace the controller if necessary.
A62
No communication between
controller and gas valve
Controller not connected
Connect the controller to the gas
valve
Valve damaged
Replace the valve
A63
A64
A65
F66
Controller DBM12 fault
Controller DBM12 internal error
Check the earth connection and
replace the controller if necessary.
A80
Fume sensor fault
Fault F13 generated 3 times in
the last 24 hours
See fault F13
Fault
code
Fault
Possible cause
Cure
cod. 3541G330 - Rev. 00 - 07/2015