ENERGY TOP W 70 - W 80 - W 125
53
EN
fig. 30 - model ENERGY TOP W 125
6.
Undo the screws
“C”
and remove the fan
“D”
(fig. 31 - only model
ENERGY TOP W 125
)
fig. 31 - model ENERGY TOP W 125
7.
Undo the fixing screws
“E”
(fig. 32 model
ENERGY TOP W 70 - W 80
and fig. 33
model
ENERGY TOP W 125
) and remove the gas valve.
fig. 32 - model ENERGY TOP W 70 - W 80
fig. 33 - model ENERGY TOP W 125
8.
Replace the gas nozzle
“F”
(see fig. 32 for the model
ENERGY TOP W 70 - W 80
and fig. 33 the model
ENERGY TOP W 125
) with the one contained in the conver-
sion kit, positioning it inside the seal
“G”
. Refit the parts and check the tightness.
9.
Modify the parameter for the type of gas:
•
put the boiler in standby mode
•
press the DHW buttons (details 1 and 2 - fig. 1) together for 10 seconds: the
display shows "
P01
" flashing.
•
press the DHW buttons (details 1 and 2 - fig. 1) together to set the parameter
00
(for natural gas) or
01
(for LPG).
•
press the DHW buttons (details 1 and 2 - fig. 1) together for 10 seconds. The
boiler will return to standby mode
10. Apply the label, contained in the conversion kit, near the dataplate.
11. Using a combustion analyser connected to the boiler fume outlet, make sure the
CO
2
content in the fumes, with the boiler operating at max. and min. output, com-
plies with that given in the technical data table for the corresponding type of gas.
B
B
A
D
C
C
C
2
1
2
1
3
3
E
G
F
G
F
E
TEST mode activation
Press the heating buttons
+/-
(details 3 and 4 - fig. 1) together for 5 seconds to activate
TEST
mode. The boiler lights at the maximum heating power (Range Rated) set as de-
scribed in the following section.
The heating symbol (detail 13 - fig. 1) and DHW symbol (detail 9 - fig. 1) flash; the heat-
ing power will appear alongside.
fig. 34 - TEST mode (heating power = 100%)
To deactivate Test mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes.
Heating Capacity Adjustment (RANGE RATED)
A
This is a
“RANGE RATED”
boiler (according to EN 483) and can be adjusted
to the system's thermal requirement by setting the maximum heating capacity
for operation in heating mode, as follows:
•
Put the boiler in TEST mode (see sec. 4.1).
•
Press the
heating buttons
(details 3 and 4 - fig. 1) to increase or decrease the power (min.
= 00 - max. = 100). See the diagram “Heating Capacity Adjustment” (fig. 35).
•
Press the
reset button
(detail 8 - fig. 1) within 5 seconds and the maximum heating
capacity will remain that just set. Exit TEST mode (see sec. 4.1).
A
THE HEATING CAPACITY ADJUSTMENT THUS SET ENSURES KEEPING
OF THE EFFICIENCY VALUES DECLARED ON cap. 5.4
Heating power adjustment diagram
A =
kW -
B =
Electronic Board Parameter
fig. 35
reset
eco
comfort
RANGE RATED
IIIIIIII
IIIII
IIII
IIII
IIIIIIIIIIIII
IIIIIII
III
100
90
80
70
60
50
40
30
20
10
0
0
20
40
60
80
100
120
140
A
B
80 kW
125 kW
cod. 3541G330 - Rev. 00 - 07/2015