background image

ECONCEPT TECH 35 A

24

EN

cod. 3540I341  -  04/2008  (Rev. 00)

3.4 Troubleshooting

Diagnostics

In case of operation faults or problems, the display flashes and the fault identification code appears. 

There are faults that cause permanent shutdown (marked with the letter “

A

”): to restore operation just press the RESET

button  (detail 8 - fig. 1) for 1 second or RESET on the optional remote timer control if installed; if the boiler fails to start,
it is necessary to first eliminate the fault.

Other faults (marked with the letter “

F

”) cause temporary shutdowns that are automatically reset as soon as the value

returns within the boiler's normal working range.

Table. 5 - List of faults

Fault 
code

Fault

Possible cause

Cure

A01

The burner fails to light

No gas

Check the regular gas flow to the boiler and that the air 
has been eliminated from the pipes

Ignition/detection electrode fault

Check the wiring of the electrode and that it is correctly 
positioned and free of any deposits

Faulty gas valve

Check the gas valve and replace it necessary

Insufficient gas supply pressure

Check the gas supply pressure

Trap clogged

Check the trap and clean it if necessary

A02

Flame present signal with 
burner off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature protection 
activated

Heating sensor damaged

Check the correct positioning and operation of the 
heating sensor

No water circulation in the sys-
tem

Check the circulating pump

Air in the system

Vent the system

A04

Fume exhaust duct safety 
activated

Fault F07 generated 3 times in 
the last 24 hours

See fault F07

A05

Fan protection activated

Fault F15 generated for 1 hour 
(consecutive)

See fault F15

A06

No flame after ignition 
stage (6 times in 4 minutes)

Ionisation electrode fault

Check the position of the ionisation electrode and 
replace it if necessary

Flame unstable

Check the burner

Gas valve Offset fault

Check the Offset adjustment at minimum power

air/fume ducts obstructed

Remove the obstruction from the flue, fume exhaust 
ducts and air inlet and terminals

Trap clogged

Check the trap and clean it if necessary

F07

High fume temperature

Flue partially obstructed or insuf-
ficient

Check the efficiency of the flue, fume exhaust ducts 
and outlet terminal

Fume sensor position

Check the correct positioning and operation of the 
fume sensor

F10

Delivery sensor 1 fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F11

Return sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

F12

DHW sensor fault

Sensor damaged

Check the wiring or replace the sensor

Wiring shorted

Wiring disconnected

Summary of Contents for ECONCEPT TECH 35 A

Page 1: ...2008 Rev 00 ECONCEPT TECH 35 A INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE INSTRUCTIONS D UTILISATION D INSTALLATION ET D ENTRETIEN ȅǻǾīǴǼȈ ȋȇdzȈǾȈ ǼīȀǹȉDZȈȉǹȈǾȈ Ȁǹǿ ȈȊȃȉdzȇǾȈǾȈ KULLANMA KURULUM VE BAKøM TALIMATLARø ...

Page 2: ... regulations and the manufacturer s instructions Incorrect installation or poor maintenance can cause damage or physical injury The manufacturer de clines any responsibility for damage caused by er rors in installation and use or by failure to follow the manufacturer s instructions Before carrying out any cleaning or maintenance op eration disconnect the unit from the electrical power supply using...

Page 3: ...Plumbing connections 11 2 4 Gas connection 13 2 5 Electrical connections 14 2 6 Fume ducts 15 2 7 Condensate drain connection 19 3 Service and maintenance 20 3 1 Adjustments 20 3 2 Start up 21 3 3 Maintenance 22 3 4 Troubleshooting 24 4 Technical characteristics and data 26 4 1 Dimensions and connections 26 4 2 General view and main components 27 4 3 Plumbing circuit 28 4 4 Technical data table 29...

Page 4: ...d ionization flame control modulating speed fan and modulating gas valve The boiler is arranged for connection to an external storage tank for hot water production optional In this manual all the functions relevant to domestic hot water production are only active with the optional hot water tank connected as indicated in sec 2 3 1 2 Control panel fig 1 Control panel Key 1 DHW temperature setting d...

Page 5: ...hot water under the tap de tails 8 and 9 fig 1 The display detail 11 fig 1 shows the actual hot water outlet temperature and during DHW standby time the mes sage d1 fig 3 Exclude hot water storage tank economy Hot water storage tank temperature maintaining heating can be excluded by the user If excluded domestic hot water will not be delivered The hot water tank can be deactivated by the user ECO ...

Page 6: ...ready to operate automatically whenever domestic hot water is drawn or in case of a room thermostat demand Turning the boiler off Press the button detail 7 fig 1 for 5 seconds fig 5 Turning the boiler off When the boiler is turned off the electronic board is still powered Domestic hot water and heating operation are disabled The antifreeze system remains activated To relight the boiler press the b...

Page 7: ...nter changeover Press the button detail 6 fig 1 for 2 seconds fig 7 The display activates the Summer symbol detail 10 fig 1 the boiler will only deliver domestic hot water The anti freeze system remains activated To deactivate Summer mode press the button detail 6 fig 1 again for 2 seconds Heating temperature adjustment Operate the heating buttons details 3 and 4 to adjustfig 1the temperature from...

Page 8: ...conditions in order to ensure high comfort and energy saving throughout the year As the outside temperature increases the temperature of the heat ing system is decreased according to a fixed compensation curve With Sliding Temperature adjustment the temperature set with the heating buttons details 3 and 4 fig 1 becomes the maximum system delivery temperature It is advisable to set a maximum value ...

Page 9: ...e is lower than the required value it is advisable to set a higher order curve and vice versa Pro ceed by increasing or decreasing in steps of one and check the result in the room fig 12 Compensation curves fig 13 Example of parallel compensation curve shift A If the Remote Timer Control optional is connected to the boiler the above adjustments are managed accord ing to that given in table 1 eco c...

Page 10: ...justment can be made from the Remote Timer Control menu and the boiler control panel DHW temperature adjustment Adjustment can be made from the Remote Timer Control menu and the boiler control panel Summer Winter changeover Summer mode has priority over a possible Remote Timer Control heating demand Eco Comfort selection On disabling DHW from the Remote Timer Control menu the boiler selects the Ec...

Page 11: ...r normal maintenance operations 2 3 Plumbing connections The heating capacity of the unit must be previously established by calculating the building s heat requirement according to current regulations The system must be provided with all the components for correct and regular operation It is ad visable to install shut off valves between the boiler and heating system allowing the boiler to be isola...

Page 12: ...tifreeze fluids additives and inhibitors The boiler is equipped with an antifreeze system that turns on the boiler in heating mode when the system delivery water temperature falls under 6 C The device will not come on if the electricity and or gas supply to the unit are cut off If it becomes necessary it is permissible to use antifreeze fluid additives and inhibitors only if the manufacturer of th...

Page 13: ... delivery 210 Boiler return 2 4 Gas connection B Before making the connection ensure that the unit is arranged for operation with the type of fuel available and carefully clean all the pipes of the gas system to remove any residues that could affect good functioning of the boiler The gas must be connected to the relative connector see fig 31 in conformity with current standards with rigid metal pi...

Page 14: ...he others B The user must never change the unit s power cable If the cable gets damaged switch off the unit and have it changed solely by professionally qualified personnel If changing the electric power cable use solely HAR H05 VV F 3x0 75 mm2 cable with a maximum outside diameter of 8 mm Room thermostat optional B CAUTION The room thermostat must have clean contacts CONNECTING 230 V TO THE TERMI...

Page 15: ...however possible that some setups are expressly limited or not permitted by law standards or local regulations Before proceeding with installation check and meticulously observe the above mentioned prescriptions In addition comply with the provisions concerning the positioning of wall and or roof end pieces and the minimum distances from windows walls ventilation openings etc B This C type unit mu...

Page 16: ...d causing dripping fig 22 Starting accessory for coaxial ducts Before proceeding with installation check with table 2 that the maximum permissible length is not exceeded bearing in mind that every coaxial bend gives rise to the reduction indicated in the table For example a Ø 60 100 duct comprising a 90 bend 1 horizontal metre has a total equivalent length of 2 metres Table 2 Max length coaxial du...

Page 17: ...maximum permissible length has not been exceeded by means of a simple calculation 1 Completely establish the layout of the system of split flues including accessories and outlet terminals 2 Consult the table 4 and identify the losses in meq equivalent metres of every component according to the instal lation position 3 Check that the sum total of losses is less than or equal to the maximum permissi...

Page 18: ...lar or quadrangular cross section with a vertical progression and with no constrictions Have the ducts conveying the hot fumes adequately distanced or isolated from combustible materials Be connected to just one unit per floor Be connected to just one type of unit or all and only forced draught units or all and only natural draught units Have no mechanical suction devices in the main ducts Be at a...

Page 19: ...oiler is equipped with a trap to drain condensate Fit the inspection connection A and the flexible tube B pressing it in about 3 cm and securing it with a clamp Fill the trap with approx 0 5 l of water and connect the flexible tube to the elimination system fig 26 Condensate drain connection ...

Page 20: ...hamber 3 Release the fixing clip C and remove the gas pipeA from the fan venturi assembly 4 Replace the nozzle B inserted in the gas pipe with that contained in the conversion kit 5 Reassemble the gas pipe A with the clip and check the seal of the connection 6 Apply the plate contained in the conversion kit near the dataplate 7 Refit the sealed chamber and casing 8 Modify the parameter for the typ...

Page 21: ... air vent valve on the boiler and any vent valves on the system Fill the condensate trap and check correct connection of the condensate elimination system Make sure there are no water leaks in the system DHW circuits connections or boiler Check correct connection of the electrical system and efficiency of the earthing system Make sure the gas pressure value for heating is that required Make sure t...

Page 22: ...scale When cleaning do not use chemical products or wire brushes The electrode must be free of scale and properly positioned The gas and water systems must be airtight The water pressure in the cold water system must be about 1 bar otherwise bring it to that value The circulation pump must not be blocked The expansion tank must be filled The gas flow and pressure must correspond to that given in t...

Page 23: ...rement 1 Open the air and fume sampling points 2 Insert the probes 3 Press the and buttons for 5 seconds to activate TEST mode 4 Wait 10 minutes for the boiler to stabilise 5 Take the measurement For natural gas the CO2 reading must be between 8 7 and 9 For LPG the CO2 the reading must be between 9 5 and 10 A Analyses made with an unstabilised boiler can cause measurement errors fig 30 Combustion ...

Page 24: ... Card fault Check the card A03 Overtemperatureprotection activated Heating sensor damaged Check the correct positioning and operation of the heating sensor No water circulation in the sys tem Check the circulating pump Air in the system Vent the system A04 Fume exhaust duct safety activated Fault F07 generated 3 times in the last 24 hours See fault F07 A05 Fan protection activated Fault F15 genera...

Page 25: ...ly trouble Check the electrical system F35 Mains frequency fault Power supply trouble Check the electrical system F37 Incorrect system water pressure Pressure too low Fill the system Water pressure switch not con nected or damaged Check the sensor F39 External probe fault Probe damaged or wiring shorted Check the wiring or replace the sensor Probe disconnected after acti vating the sliding tempera...

Page 26: ...hnical characteristics and data 4 1 Dimensions and connections fig 31 Dimensions and connections 1 Heating system delivery 3 Gas inlet 5 Heating system return 6 Safety valve drain 700 450 97 74 74 48 83 74 44 180 240 118 180 229 76 134 120 120 195 330 1 3 6 5 ...

Page 27: ...r 36 Automatic air vent 44 Gas valve 56 Expansion tank 74 Heating system cock 82 Detection electrode 95 Diverter valve 114 Water pressure switch 161 Condensing heat exchanger 186 Return sensor 188 Ignition electrode 191 Fume temperature sensor 193 Trap 196 Condensate tray 201 Mixing chamber 209 Boiler delivery 210 Boiler return 250 System delivery filter 278 Double sensor Safety Heating 56 22 161 ...

Page 28: ...6 Automatic air vent 44 Gas valve 56 Expansion tank 74 Heating system cock 95 Diverter valve 114 Water pressure switch 154 Condensate outlet 161 Condensing heat exchanger 186 Return sensor 193 Trap 196 Condensate tray 209 Boiler delivery 210 Boiler return 210 Boiler return 241 By pass 278 Double sensor Safety Heating 56 44 32 11 10 7 95 241 114 36 186 161 278 193 154 16 250 196 209 210 74 14 ...

Page 29: ...ower kW 6 3 Gas feed pressure G20 mbar 20 Max gas delivery G20 m3 h 3 68 Min gas delivery G20 m3 h 0 69 Gas feed pressure G31 mbar 37 Max gas delivery G31 kg h 2 73 Min gas delivery G31 kg h 0 51 Efficiency class directive 92 42 EEC NOx emission class 5 NOx Max working pressure in heating bar 3 PMS Min working pressure in heating bar 0 8 Max heating temperature C 95 tmax Heating water content litr...

Page 30: ... TECH 35 A 30 EN cod 3540I341 04 2008 Rev 00 4 5 Diagrams Circulating pumps head pressure loss A Boiler pressure losses 1 2 3 Circulating pump speed 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H2O A 3 1 2 ...

Page 31: ...4 Gas valve 72 Room thermostat 82 Detection electrode 95 Diverter valve 114 Water pressure switch 138 External sensor 139 Remote timer control 155 Hot water temperature sensor optional 186 Return sensor 188 Ignition electrode 191 Fume temperature sensor 278 Double sensor heating safety 256 Modulating heating circulator pump signal 72 95 155 114 191 16 186 188 82 T T 278 139 138 256 32 16 44 N L 23...

Reviews: