background image

ECONCEPT TECH 25 A

11

EN

cod. 3540I301  -  05/2008  (Rev. 00)

2. Installation

2.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH
ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRE-
SCRIPTIONS OF NATIONAL STANDARDS AND LOCAL REGULATIONS AND THE RULES OF PROPER WORK-
MANSHIP

2.2 Place of installation

The combustion circuit is sealed with respect to the place of installation, therefore the unit can be installed in any room.
However, the place of installation must be sufficiently ventilated to prevent the creation of any dangerous conditions in
case of even small gas leaks. This safety precaution is required by EEC Directive no. 90/396 for all gas units, including
those with a so-called sealed chamber.
Therefore the place of installation must be free of dust, flammable materials or objects or corrosive gases. The room
must be dry and not subject to freezing.
The boiler is arranged for wall mounting and comes standard with a hooking bracket. The wall fixing must ensure stable
and effective support for the generator.

A

If the unit is enclosed in a cabinet or mounted alongside, a space must be provided for removing the casing
and for normal maintenance operations

2.3 Plumbing connections

Important

The heating capacity of the unit must be previously established by calculating the building's heat requirement according
to the current regulations. The system must be provided with all the components for correct and regular operation. It is
advisable to install shutoff valves between the boiler and heating system allowing the boiler to be isolated from the sys-
tem if necessary.

B

The safety valve outlet must be connected to a funnel or collection pipe to prevent water spurting onto the floor
in case of overpressure in the heating circuit. Otherwise, if the discharge valve cuts in and floods the room,
the boiler manufacturer cannot be held liable.
Do not use the water system pipes to earth electrical appliances.

Before installation, carefully wash all the pipes of the system to remove any residuals or impurities that could affect prop-
er operation of the unit.

B

Also, a filter must be installed on the system return pipe to prevent impurities or sludge from the system clog-
ging and damaging the heat generators.
The filter MUST be installed when replacing generators in existing systems. The manufacturer declines any
liability for damage caused to the generator by failure to install or inadequate installation of this filter.

Carry out the relevant connections according to the diagram in sec. 4.1 and the symbols given on the unit.

Summary of Contents for ECONCEPT TECH 25 A

Page 1: ...3540I301 cod 3540I301 05 2008 Rev 00 ECONCEPT TECH 25 A INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ... regulations and the manufacturer s instructions Incorrect installation or poor maintenance can cause damage or physical injury The manufacturer de clines any responsibility for damage caused by er rors in installation and use or by failure to follow the manufacturer s instructions Before carrying out any cleaning or maintenance op eration disconnect the unit from the electrical power supply using...

Page 3: ... 2 3 Plumbing connections 11 2 4 Gas connection 13 2 5 Electrical connections 14 2 6 Fume ducts 15 2 7 Condensate drain connection 19 3 Service and maintenance 20 3 1 Adjustments 20 3 2 Start up 22 3 3 Maintenance 22 3 4 Troubleshooting 24 4 Technical data and characteristics 26 4 1 Dimensions and connections 26 4 2 General view and main components 27 4 3 Plumbing circuit 28 4 4 Technical data tab...

Page 4: ...e is suitable for indoor installation or outdoors in a partially protected place according to EN 297 A6 with temperatures to 5 C 15 C with optional antifreeze kit The boiler is arranged for connection to an external storage tank for hot water production optional In this manual all the functions relevant to domestic hot water production are only active with the optional hot water tank connected as ...

Page 5: ...hot water under the tap de tails 8 and 9 fig 1 The display detail 11 fig 1 shows the actual hot water outlet temperature and during DHW standby time the mes sage d1 fig 3 Exclude hot water storage tank economy Hot water storage tank temperature maintaining heating can be excluded by the user If excluded domestic hot water will not be delivered The hot water tank can be deactivated by the user ECO ...

Page 6: ...ready to operate automatically whenever domestic hot water is drawn or in case of a room thermostat demand Turning the boiler off Press the button detail 7 fig 1 for 5 seconds fig 5 Turning the boiler off When the boiler is turned off the electronic board is still powered Domestic hot water and heating operation are disabled The antifreeze system remains activated To relight the boiler press the b...

Page 7: ...nter changeover Press the button detail 6 fig 1 for 2 seconds fig 7 The display activates the Summer symbol detail 10 fig 1 the boiler will only deliver domestic hot water The anti freeze system remains activated To deactivate Summer mode press the button detail 6 fig 1 again for 2 seconds Heating temperature adjustment Operate the heating buttons details 3 and 4 to adjustfig 1the temperature from...

Page 8: ...f the heat ing system is decreased according to a fixed compensation curve With Sliding Temperature adjustment the temperature set with the heating buttons details 3 and 4 fig 1 becomes the maximum system delivery temperature It is advisable to set a maximum value to allow system adjustment throughout its useful operating range The boiler must be adjusted at the time of installation by qualified p...

Page 9: ...made from the Remote Timer Control menu and the boiler control panel Summer Winter changeover Summer mode has priority over a possible Remote Timer Control heating demand Eco Comfort selection On disabling DHW from the Remote Timer Control menu the boiler selects the Economy mode In this condition the button detail 7 fig 1 on the boiler panel is disabled On enabling DHW from the Remote Timer Contr...

Page 10: ... minimum the boiler card will activate fault F37 fig 14 fig 14 Low system pressure fault Operate the filling cock detail 1 fig 15 and bring the system pressure to a value above 1 0 bar fig 15 Filling cock A Once the system pressure is restored the boiler will activate the 120 second air venting cycle indicated on the display by FH At the end of the operation always close the filling cock detail 1 ...

Page 11: ...ng and for normal maintenance operations 2 3 Plumbing connections Important The heating capacity of the unit must be previously established by calculating the building s heat requirement according to the current regulations The system must be provided with all the components for correct and regular operation It is advisable to install shutoff valves between the boiler and heating system allowing t...

Page 12: ... very large systems or with frequent replenishing of water in the system If partial or total emptying of the system be comes necessary in these cases it is advisable to refill it with treated water Antifreeze system antifreeze fluids additives and inhibitors The boiler is equipped with an antifreeze system that turns on the boiler in heating mode when the system delivery water temperature falls un...

Page 13: ... delivery 210 Boiler return 2 4 Gas connection B Before making the connection ensure that the unit is arranged for operation with the type of fuel available and carefully clean all the pipes of the gas system to remove any residues that could affect good functioning of the boiler The gas must be connected to the relative connector see fig 31 in conformity with current standards with rigid metal pi...

Page 14: ...he others B The user must never change the unit s power cable If the cable gets damaged switch off the unit and have it changed solely by professionally qualified personnel If changing the electric power cable use solely HAR H05 VV F 3x0 75 mm2 cable with a maximum outside diameter of 8 mm Room thermostat optional B CAUTION The room thermostat must have clean contacts CONNECTING 230 V TO THE TERMI...

Page 15: ...onfigurations may be expressly limited or not permitted by local regulations standards or laws Before proceeding with installation check and carefully observe the above mentioned prescriptions Also comply with the provisions concerning the positioning of wall and or roof terminals and the minimum distances from windows walls ventilation openings etc B This C type unit must be installed using the f...

Page 16: ...d causing dripping fig 22 Starting accessory for coaxial ducts Before proceeding with installation check with table 2 that the maximum permissible length is not exceeded bearing in mind that every coaxial bend gives rise to the reduction indicated in the table For example a Ø 60 100 duct comprising a 90 bend 1 horizontal metre has a total equivalent length of 2 metres Table 2 Max length coaxial du...

Page 17: ...mum permissible length has not been exceeded by means of a simple calculation 1 Establish the layout of the system of split flues including accessories and outlet terminals 2 Consult the table 4 and identify the losses in meq equivalent metres of every component according to the instal lation position 3 Check that the sum total of losses is less than or equal to the maximum permissible length in t...

Page 18: ...lar or quadrangular cross section with a vertical progression and with no constrictions Have the ducts conveying the hot fumes adequately distanced or isolated from combustible materials Be connected to just one unit per floor Be connected to just one type of unit or all and only forced draught units or all and only natural draught units Have no mechanical suction devices in the main ducts Be at a...

Page 19: ...oiler is equipped with a trap to drain condensate Fit the inspection connection A and the flexible tube B pressing it in about 3 cm and securing it with a clamp Fill the trap with approx 0 5 l of water and connect the flexible tube to the elimination system fig 26 Condensate drain connection ...

Page 20: ...hamber 3 Release the fixing clip C and remove the gas pipeA from the fan venturi assembly 4 Replace the nozzle B inserted in the gas pipe with that contained in the conversion kit 5 Reassemble the gas pipe A with the clip and check the seal of the connection 6 Apply the plate contained in the conversion kit near the dataplate 7 Refit the sealed chamber and casing 8 Modify the parameter for the typ...

Page 21: ...ill be displayed alongside fig 28 TEST mode heating power 100 To deactivate TEST mode repeat the activation sequence In any case the TEST mode is disabled automatically after 15 minutes Heating power adjustment To adjust the heating power switch the boiler to TEST mode see sec 3 1 Press the heating buttons de tails 3 and 4 fig 1 to increase or decrease the power min 00 max 100 Press the RESET butt...

Page 22: ...er production phases Check proper boiler lighting by doing several tests turning it on and off with the room thermostat or remote control Using a combustion analyser connected to the boiler fume outlet check that the CO2 content in the fumes with the boiler operating at max and min output corresponds to that given in the technical data table for the corresponding type of gas Make sure the fuel con...

Page 23: ...points shown in fig 30 To take the measurement 1 Open the air and fume sampling points 2 Insert the probes 3 Press the and buttons for 5 seconds to activate TEST mode 4 Wait 10 minutes for the boiler to stabilise 5 Take the measurement For natural gas the CO2 reading must be between 8 7 and 9 For LPG the CO2 the reading must be between 9 5 and 10 A Analyses made with an unstabilised boiler can cau...

Page 24: ... Card fault Check the card A03 Overtemperatureprotection activated Heating sensor damaged Check the correct positioning and operation of the heating sensor No water circulation in the sys tem Check the circulating pump Air in the system Vent the system A04 Fume exhaust duct safety activated Fault F07 generated 3 times in the last 24 hours See fault F07 A05 Fan protection activated Fault F15 genera...

Page 25: ...ly trouble Check the electrical system F35 Mains frequency fault Power supply trouble Check the electrical system F37 Incorrect system water pressure Pressure too low Fill the system Water pressure switch not con nected or damaged Check the sensor F39 External probe fault Probe damaged or wiring shorted Check the wiring or replace the sensor Probe disconnected after acti vating the sliding tempera...

Page 26: ...chnical data and characteristics 4 1 Dimensions and connections fig 31 Dimensions and connections 1 Heating system delivery 3 Gas inlet 5 Heating system return 6 Safety valve drain 700 400 82 74 56 48 84 56 44 180 232 118 180 229 80 80 120 120 195 330 1 3 6 5 ...

Page 27: ...r 36 Automatic air vent 44 Gas valve 56 Expansion tank 74 Heating system cock 82 Detection electrode 95 Diverter valve 114 Water pressure switch 161 Condensing heat exchanger 186 Return sensor 188 Ignition electrode 191 Fume temperature sensor 193 Trap 196 Condensate tray 201 Mixing chamber 209 Boiler delivery 210 Boiler return 250 System delivery filter 278 Double sensor Safety Heating 201 56 22 ...

Page 28: ...6 Automatic air vent 44 Gas valve 56 Expansion tank 74 Heating system cock 95 Diverter valve 114 Water pressure switch 154 Condensate outlet 161 Condensing heat exchanger 186 Return sensor 193 Trap 196 Condensate tray 209 Boiler delivery 210 Boiler return 210 Boiler return 241 By pass 278 Double sensor Safety Heating 56 44 32 11 10 7 95 241 114 36 186 161 278 193 154 16 250 196 209 210 74 14 ...

Page 29: ...t water production kW 5 2 Gas supply pressure G20 mbar 20 Max gas delivery G20 m3 h 2 86 Min gas delivery G20 m3 h 0 56 Gas supply pressure G31 mbar 37 Max gas delivery G31 kg h 2 11 Min gas delivery G31 kg h 0 41 Efficiency class directive 92 42 EEC NOx emission class 5 NOx Max working pressure in heating bar 3 PMS Min working pressure in heating bar 0 8 Max heating temperature C 95 tmax Heating ...

Page 30: ...NCEPT TECH 25 A 30 EN cod 3540I301 05 2008 Rev 00 4 5 Diagrams Loss of head Head of circulators A Boiler losses of head 1 2 3 Circulator speed 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H2O A 3 2 1 ...

Page 31: ...g pump 44 Gas valve 72 Room thermostat 82 Detection electrode 95 Diverter valve 114 Water pressure switch 138 External probe 139 Remote timer control 155 DHW temperature probe optional 186 Return sensor 188 Ignition electrode 191 Fume temperature sensor 278 Double sensor heating safety 256 Modulating heating circulating pump signal 72 95 155 114 191 16 186 188 82 T T 278 139 138 256 32 16 44 N L 2...

Page 32: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...

Reviews: