22
DOMIcompact F 30 D
Terminal Position
P
D, E
Q
Q
l
B
C
A
G
F
L
J
H
H
K
N
N
M
M
Q
Minimum Dimensions of Flue Terminal Positions
Directly below an opening, air brick,
opening windows, etc.
Above an opening, air brick,
opening windows, etc.
Horizontally to an opening, air brick,
opening windows, etc.
Below gutters, soil pipes or drain pipes
Below balconies or car port roof
Below eaves
From a vertical drain pipe or soil pipe
From an internal or external corner
From a surface facing the terminal
From a terminal facing the terminal
From the wall on which the terminal is mounted
From a vertical structure on the roof
Above intersection with roof
Horizontally from a terminal on the same wall
Vertically from a terminal on the same wall
From an opening in the car port (e.g. door,
window) into the dwelling
Above ground roof or balcony level
300mm
300mm
300mm
200mm
75mm
200mm
150mm
100mm
300mm
600mm
300mm
300mm
150mm
1200mm
1200mm
1500mm
N/A
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
NOTE
N/A = Not applicable
In addition, the terminal must not be nearer than 300mm to an opening in the
building fabric formed for the purpose of accommodating a built-in element
such as a window frame.
Fig. 13