cod. 3541V481 - Rev. 00 - 06/2021
b29
Restore Factory Values
See *** '* Restore Factory Values' on page 333 ***.
0
P30
Heating ramp
10÷80
(ex. 10=20°C/min, 20=12°C/min, 40=6°C/min, 80=3°C/min)
40
P31
Heating standby time
0-10 minutes
4
P32
Heating Post-Circulation
0-255 minutes
15
P33
Pump operation
0
= Continuous pump (active only in winter mode)
1
= Modulating pump
1
P34
Pump modulation DeltaT
0 ÷ 40°C
20
P35
Modulating pump min. speed
30 ÷ 100%
30
P36
Modulating pump start speed
90 ÷ 100%
90
P37
Modulating pump max. speed
90 ÷ 100%
100
P38
Pump deactivation temperature during
Post-Circulation
0 ÷ 100°C
55
P39
Pump activation hysteresis temperature
during Post-Circulation
0 ÷ 100°C
25
P40
Heating user max. setpoint
20 ÷ 90°C
80
P41
Max. output in heating
0 ÷ 100%
BLUEHELIX HITECH RRT 18 H
=
75
BLUEHELIX HITECH RRT 28 H
=
100
BLUEHELIX HITECH RRT 34 H
=
100
P42
Anti-Legionella function frequency
0
= OFF
1÷7
= Days
0
P43
Hot water tank hysteresis
0 ÷ 80°C
2
P44
Hot water tank preparation flow
0 ÷ 100°C
80
P45
DHW standby time
30 ÷ 255 seconds
120
P46
DHW user max. setpoint
40 ÷ 70°C
65
P47
DHW pump Post-Circulation
0 ÷ 255 seconds
30
P48
Max. output in DHW
0 ÷ 100%
BLUEHELIX HITECH RRT 18 H
=
75
BLUEHELIX HITECH RRT 28 H
=
100
BLUEHELIX HITECH RRT 34 H
=
100
P49
Not implemented
--
--
P50
Not implemented
--
--
P51
Hot water tank Off Delta
0 ÷ 20°C
10
P52
Not implemented
--
5
P53
Not implemented
--
10
P54
System pre-circulation time
0 ÷ 60 seconds
30
P55
System filling mode
0
= Disabled
1
= Automatic
0
P56
Minimum system pressure limit value
0-8 bar/10 (Only for boilers with water pressure sensor)
4
P57
System nominal pressure value
5-20 bar/10 (Only for boilers with water pressure sensor)
7
P58
Maximum system pressure limit value
25-35 bar/10 (Only for boilers with water pressure sensor)
28
P59
Not implemented
--
--
P60
Frost protection power
0 ÷ 50% (0 = minimum)
0
P61
Minimum power
0 ÷ 50% (0 = minimum)
0
P62
Fan minimum speed
DO NOT MODIFY
(The parameters are automatically updated)
G20/G230:
BLUEHELIX HITECH RRT 18 H
= 47
BLUEHELIX HITECH RRT 28 H
= 47
BLUEHELIX HITECH RRT 34 H
= 49
G30/G31:
BLUEHELIX HITECH RRT 18 H
= 49
BLUEHELIX HITECH RRT 28 H
= 49
BLUEHELIX HITECH RRT 34 H
= 48
Index
Description
Range
Default
Summary of Contents for 0T4D1AWA
Page 1: ...INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...
Page 39: ...334 EN cod 3541V481 Rev 00 06 2021 fig 40 ...
Page 45: ...340 EN cod 3541V481 Rev 00 06 2021 fig 48 fig 49 fig 50 ...
Page 53: ...348 EN cod 3541V481 Rev 00 06 2021 4 4 Technical data table ...
Page 54: ...349 EN cod 3541V481 Rev 00 06 2021 ...
Page 55: ...350 EN cod 3541V481 Rev 00 06 2021 ...
Page 56: ...351 EN cod 3541V481 Rev 00 06 2021 ...
Page 59: ......
Page 60: ......
Page 61: ......