159
EN
cod. 3541T170 - Rev. 00 - 09/2019
System Type - Parameters Menu
There are 23 parameters, indicated by the letter
“P”,
which are not modifiable from Remote Timer Control.
Notes
1. * These parameters are active only when two controllers are connected to a single display ACP01.
2. ** These parameters are active only when the system operates with input 0-10Vdc.
3.2 Commissioning
B
Checks to be done at first lighting, and after all maintenance operations that invol-
ved disconnection from the systems or work on safety devices or parts of the
boiler:
Before lighting the boiler
•
Open any on-off valves between the boiler and the systems.
•
Check the tightness of the gas system, proceeding with caution and using a soap and water solution to detect any
leaks in connections.
•
Check correct prefilling of the expansion tank (ref. sec. 4.4).
•
Fill the water system and make sure all air contained in the boiler and the system has been vented, by opening the
air vent valve on the boiler and any vent valves on the system.
•
Fill the condensate trap and check correct connection of the condensate elimination system.
•
Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
•
Check correct connection of the electrical system and efficiency of the earthing system
•
Make sure the gas pressure value for heating is that required.
•
Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler
Parameter
Description
Range
FORCE B
80
FORCE B
120
FORCE B
150
P.01
Heating request selection
0-5
0
0
0
P.02
Cascade sensor selection
0=Disabled,
1 or 2=Enabled
0
0
0
P.03
No function
0-1
0
0
0
P.04
3-way valve time
0-255 seconds
0
0
0
P.05
Activation timer*
0-255 minutes
1
1
1
P.06
Deactivation timer*
0-255 minutes
5
5
5
P.07
Activation power*
0-100%
70
70
70
P.08
Deactivation power*
0-100%
25
25
25
P.09
Hydraulic separator function
OFF
= Disabled,
ON
=
Enabled
OFF
OFF
OFF
P.10
System filling function
OFF
= Disabled,
ON
=
Enabled
OFF
OFF
OFF
P.11
3-way valve selection
2/3
= 2 or 3 wires
2
= 2 wires
2/3
2/3
2/3
P.12
0-10Vdc Heating OFF voltage (Temperature Control)**
0.1-10 Vdc
2.5
2.5
2.5
P.13
0-10Vdc Heating ON voltage (Temperature Control)**
0.1-10 Vdc
3.0
3.0
3.0
P.14
0-10Vdc Max. voltage (Temperature Control)**
0.1-10 Vdc
10
10
10
P.15
0-10Vdc Min. temperature (Temperature Control)**
0-100°C
20
20
20
P.16
0-10Vdc Max. temperature (Temperature Control)**
0-100°C
90
90
90
P.17
0-10Vdc Heating OFF voltage (Power Control)**
0.1-10 Vdc
2.5
2.5
2.5
P.18
0-10Vdc Heating ON voltage (Power Control)**
0.1-10 Vdc
3.0
3.0
3.0
P.19
0-10Vdc Max. power (Power Control)**
0.1-10 Vdc
10
10
10
P.20
0-10Vdc Min. power (Power Control)**
0-100%
0
0
0
P.21
0-10Vdc Max. power (Power Control)**
0-100%
100
100
100
P.22
Enable DHW Slave boiler (Autocascade)
OFF
= Disabled,
ON
=
Enabled
OFF
OFF
OFF
P.23
Continuous comfort Slave boiler (AX5200SQ)
OFF
= Disabled,
ON
=
Enabled
OFF
OFF
OFF