Adjust the parallel offset of the curves from 20 to 60 °C (fig. 29), through the parameter
“Offset1”
and confirm with the
OK button.
fig. 27 - Curve parallel offset
If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. Pro-
ceed by increasing or decreasing in steps of one and check the result in the room.
fig. 28 - Compensation curves
fig. 29 - Example of parallel offset of compensation curves
A
This parameter is used only if time programming has been activated. See *** 'Time programming' on page 128
***
Outside Temperature Heating OFF
Access the “Out Temp Heat Off” to activate the function: between 7°C and 30°C.
If activated, this function will deactivate the heating demand whenever the temperature measured by the external probe
is higher than the programmed value.
The heating demand will be reactivated as soon as the temperature measured by the external probe is lower than the
programmed value.