3.2.

 

Method of installation 

1

Names of parts mounting base is as follows. 

 

 

 

 

 

 

 

 

 

 

2

Please  install  a  Mounting  Base  to  “install  holes”  with  two  screws  M3  which  is  more  than  15mm 

length. 

 

 

 

 
 

 

 

3

Please put both insert guides together, and insert the Detector Attachment into Mounting Base. And 

Turn a Detector Clockwise until make a sound with "a snick". 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Incorrect loading of the equipments can cause a malfunction, failure or drop. 

Tighten the screw in the specified torque range.   

(torque 0.5N

m: Reference value)

 

Under tightening can cause a drop, short circuit or malfunction. 

Over tightening can cause a drop, short circuit or malfunction due to damage to 

the screw or he equipments and malfunction and fire.

 

Put Insert guides, Detector Terminal and Attachment together correctly.   

It causes trouble. 

Do not turning a detector too much. Also do not make a lack of insertion. 

Do not remove a detector, Fire can not be detected.   

Do  not  use  detector  which  have  impacted.  And  also  do  not  paint  or  cover  a 

detector.

 

 

Warning

 

 

 

Warning

 

 

Summary of Contents for F1H-Q-RYW1K

Page 1: ...nual we have shown the important notice in order for you to use the device just and the method of handling this system In additional to you read this manual well before the utilization understanding well and use After you read in the place where it seen with it is seen with anytime please to be sure to keep ...

Page 2: ...ge Table of contents 1 Safety Instructions 3 2 Name and Function of each section 4 3 Install 5 4 Specification 8 5 Maintenance and Inspection 10 6 Parts of Replacement 13 7 Term of replacement 13 8 Disposal 13 9 Support 14 ...

Page 3: ... moving and falling etc at your corporation breakdown and the loss with inadequate handling 3 When cause of breakdown due to the reason other than the payment item 4 Error in regard to use of the consumer breakdown and the loss with repairing remodeling other than our company and error connecting Furthermore the guarantee referred to here being something which means the guarantee of the payment it...

Page 4: ...730110 K0 4 ES1613 Page 2 Name and Function of each section ...

Page 5: ...ronmental specification It causes trouble Do not install wrong location The smoke detector cannot detect a smoke Be sure to install the detector away from sources of electrical noise such as high voltage and high current switches Isolation from electric noise source such as power line The signal conductor which is connected to the detector please wires over 20cm separating from the power line Case...

Page 6: ...lfunction failure or drop Tighten the screw in the specified torque range torque 0 5N m Reference value Under tightening can cause a drop short circuit or malfunction Over tightening can cause a drop short circuit or malfunction due to damage to the screw or he equipments and malfunction and fire Put Insert guides Detector Terminal and Attachment together correctly It causes trouble Do not turning...

Page 7: ... between Relay and Relay Relay and Power supply Do not place obstacle as wiring etc near the slit of the detector It will disturb inflow of smoke Please provide a dedicated power supply as much as possible This Detector does not have over voltage protection device Before using Please add an external over current circuit breaker Smoke detectors are detecting light scattered by smoke particles in th...

Page 8: ...ow 6 3 Sensitivity Depend on Type of Product 0 5 m Nominal 4 State Indication LED RED LED State of LED Normal mode 10 seconds interval Alarm mode 1 seconds interval Trouble mode Off not blinking Alarm will override trouble 5 Output Alarm Trouble Relay Output Capacity of Relay DC24V 0 5A Resistance loading State depends on Type of relay Type Contact Normal mode Alarm mode Trouble mode Power OFF AA ...

Page 9: ...etector becomes trouble condition before exceeding correctable limit 4 2 Mechanical Specification 1 quantity of suction 1L min 2 Filter Medium efficiency particulate airlifter Over 70 rate of collection 3 External Φ28 H57mm Installation Base 10mm is contained 4 Mass Approx 25g Installation Base is contained 5 Main Material ABS resins 4 3 Environmental Specification 1 Operating Temperature Range 10...

Page 10: ...ors Move the wire to check Connectors must not be loose Change the connector cable 4 Behavior Normal supervision Detector State Indication LED Check Visually Blink 10 seconds interval Check the State Indication LED behavior Please do not touch the terminal while the unit is energized It may get an electric shock Please do the cleaning and the increase tightening of the screw after the power supply...

Page 11: ...p p Meets the specification 6 Installation Common Securely locked Move the detector to check The detector must be installed securely Retighten the screws on the base with proper torque Obstacle near the inlet outlet of detector Check Visually Obstacle must not be present Removed 7 Appearance Common Adhesion of dirt and foreign matter Check Visually Dirt and foreign matter must not be present Remov...

Page 12: ...unction Please use the dry cloth or wring the water out tightly cloth for the cleaning After Cleaning Do not leave a foreign substance such as sawdust or wiring debris on a detector Such debris could cause erroneous operation Do not clean with a solvent such as a ph balanced detergent Bleach Benzene Thinner Alcohol It causes the detector surface is damaged Caution ...

Page 13: ...pull it out until it clicks 7 Term of replacement Since deterioration over time of the suction fan may vary with temperature Life of this product depends on the operating temperature of the product 10 45 Recommended Temperature Range 5 years 46 60 3 years 8 Disposal This product is as general industrial waste disposal Disposal methods are specific criteria depending on each municipality Do not wir...

Page 14: ...613 Page 9 Support Please inquire about this product to Fenwal Controls of Japan Co Ltd Tokyo headquarters Fenwal Controls of Japan Co Ltd 1 5 10 Iidabashi Chiyoda Tokyo 102 0072 Japan Tokyo headquarters 81 3 3237 3565 ...

Reviews: