730110
K0
6
ES1613
Page
3.2.
Method of installation
(
1
)
Names of parts mounting base is as follows.
(
2
)
Please install a Mounting Base to “install holes” with two screws M3 which is more than 15mm
length.
(
3
)
Please put both insert guides together, and insert the Detector Attachment into Mounting Base. And
Turn a Detector Clockwise until make a sound with "a snick".
・
Incorrect loading of the equipments can cause a malfunction, failure or drop.
・
Tighten the screw in the specified torque range.
(torque 0.5N
・
m: Reference value)
・
Under tightening can cause a drop, short circuit or malfunction.
・
Over tightening can cause a drop, short circuit or malfunction due to damage to
the screw or he equipments and malfunction and fire.
・
Put Insert guides, Detector Terminal and Attachment together correctly.
It causes trouble.
・
Do not turning a detector too much. Also do not make a lack of insertion.
・
Do not remove a detector, Fire can not be detected.
・
Do not use detector which have impacted. And also do not paint or cover a
detector.
!
Warning
!