F-35-63

August 2015

FEATURES

Safe start with DETECT-A-FLAME

®

 flame sensing 

technology

Custom pre-purge and inter-purge timings

*

Single or three trials for ignition

Mounts on standard 4-in. junction box

System  diagnostic  LED

Flame current test points

Local or remote flame sensing

Automatic reset option

**

APPLICATIONS

Commercial cooking

Gas furnaces

Unit  heaters

Water  heaters

Other applications requiring intermittent pilot

DESCRIPTION

The 35-63 is a 24 VAC intermittent pilot (spark-to-pilot) ignition 
control. The control uses a microprocessor circuit to provide 
precise, repeatable timing and operating sequences. On-board 
diagnostics with LED output makes troubleshooting easy and 
ensures safe and efficient operation.

Export Information (USA)

Jurisdiction: EAR
ECCN: EAR99

Agency Certifications

*

 Pre-purge time cannot exceed inter-purge time on CE 

Approved models.

**

 Automatic reset is not allowed for CE Approved models.

SPECIFICATIONS

Recognized under the UL component program, UL 
372. Software certified to ANSI/UL 1998. UL File 
MH8817

Design certified to ANSI Z21.20, CAN/CSA C22.2
No. 199-M89

CE Approved to EN 298:2003

Code Compliant to:

AS 4625 - 2008
AS 4622 - 2004

Input Power

Control: 18-30 VAC 50/60Hz 
(Class 2 Transformer)

Input Current

300 mA @24 VAC with main and 
pilot gas valve relays energized 
(control only)

Main Gas Valve

2.0A max (continuous)

Pilot Gas Valve

2.0A max (continuous)

Operating Temperature

-40°F to +176°F 
(-40°C to +80°C)

Storage Temperature

-40°F to +185°F
(-40°C to +85°C)

Flame Sensitivity

0.7 

µ

A minimum

Flame Failure Response

0.8 seconds maximum

Flame Detector Self-check 
Rate

Once per second minimum

Gas Types

Natural, LP, or manufactured

Spark Rate:

Remote
Local

50/60 sparks/sec
25/30 sparks/sec

Size (LxWxH)
with enclosure

5.69 x 3.94 x 1.87 inches 
(14.45 x 10.01 x 4.75 cm)

Moisture Resistance

Conformal coated to operate non-
condensing to 95% R.H. Module 
should not be exposed to water

Ingress Protection

Not rated, protection provided by 
appliance in which it is installed

Tries for Ignition

One or three try versions available

Trial for Ignition Periods

15, 30, 60, 90 seconds available

Pre-purge and 
lnter-purge Timings

0, 15, 30, 45 seconds 
or 4 minutes available

SERIES 35-63

24 VAC Microprocessor-Based

Intermittent Pilot Ignition Control

R

Summary of Contents for 35-63

Page 1: ... MH8817 Design certified to ANSI Z21 20 CAN CSA C22 2 No 199 M89 CE Approved to EN 298 2003 Code Compliant to AS 4625 2008 AS 4622 2004 Input Power Control 18 30 VAC 50 60Hz Class 2 Transformer Input Current 300 mA 24 VAC with main and pilot gas valve relays energized control only Main Gas Valve 2 0A max continuous Pilot Gas Valve 2 0A max continuous Operating Temperature 40 F to 176 F 40 C to 80 ...

Page 2: ... additional ignition trials before de energizing the pilot valve and entering lockout The LED will indicate the fault code for ignition lockout FLAME FAILURE RE IGNITION MODE If the established pilot flame signal is lost while the burner is operating the control will respond within 0 8 seconds by de energizing the main gas valve and energizing the H V spark for the TFI period in an attempt to reli...

Page 3: ...oper and dangerous operation A functional checkout of a replacement control should always be performed WARNING This product uses voltages of shock hazard potential Wiring and initial operation must be performed by a qualified service technician WARNING Operation outside specifications could result in failure of the Fenwal product and other equipment with potential for injury to people and property...

Page 4: ...urement Flame current is the current that passes through the flame from sensor to ground To measure flame current connect a True RMS or analog DC micro ammeter to the FC and FC terminals Readings should be 1 0 µA DC or higher If the meter reads negative or below 0 on scale meter leads are reversed Re connect leads with proper polarity Alternately a Digital Voltmeter may be used to measure DC volta...

Page 5: ...X 3 750 250 3 250 010 5 000 010 2 250 250 164 010 DIA 450 MAX 015 031 062 4 MOUNTING GND TH W V1 P1 IND V1 V2 S1 475 HOLES 500 MAX 2 000 MAX 475 2 MOUNTING HOLES 187 010 DIA 2 250 S1 V2 IND V1 V1 P1 TH W 5 688 5 000 010 359 3 250 010 344 1 750 MAX GND DS1 FC FC 3 375 010 1 125 063 3 375 010 3 968 2 MOUNTING 234 010 DIA HOLES Note All dimensions are in inches ...

Page 6: ... of Flame 2 Standard CE Approved Model 3 Special CE Approved Model 5 Re ignition After Loss of Flame 9 Special Configuration Pre Purge Time 0 None 1 15 Seconds 2 30 Seconds 3 45 Seconds 4 4 Minutes Number of Ignition Trials Flame Sense Method and Lockout Reset Method 0 Single Try Local Sense 1 Single Try Remote Sense 2 Single Try Local Sense 3 Single Try Remote Sense 5 Three Tries Local Sense 6 Th...

Reviews: