Starting the system
Starting the system
Starting the system
Starting the system
3.1.1.
Setting of control unit
Please verify whether the number of detectors which it is connected with the DET. NUMBERS
switch which is on the panel front is same.
When setting is different, trouble indication is lighting.
3.1.2.
Power on
When the supply of power or power switch is pushed, the power light(green LED) lights up,
the system operates starts.
3.1.3.
Register at time of power on
ON
Power supply OFF
Maximum 120 seconds
State of
Control unit
Initialize
※1
,Wait・Registration
※2
Supervision
※1 After power on, the alarm LED and the trouble LED blink sequentially.
※2 Control unit supplying power to the detector which is connected, starts communication.
Control unit inspects the address of all detectors which are connected, registers the detector
automatically.
When detectors of a quantity which is set in 120 seconds are registered, supervision is started.
When a quantity which is set with control unit and the number of detectors which are registered
are different it makes trouble.
Caution
!
!
!
!
・Pay attention to the sharp edge and the like when you handle control
unit. It becomes cause of the wound.
・Do not operate switch with sharp and hard ones like a ball pen top.
It makes surface sheet make a tears.
・Do not touch by hand where the oil is attached and the chemicals are
attached. The surface seat deteriorates and softens.