3.4.
Electric specifications
(1)
Name of item
: Control unit
(2)
model
: FC1-DY
: FC1-HY
(3)
Rating
: DC24V 0.15A
(4)
Range of working
voltage
: DC24V ±10%
(5)
Connectable detector
Numbers
: Up to 31.
(6)
Method of setting up
connectable detector
counts
: It sets making use of the driver from the operation
panel.
When setting up 0 or 32, the trouble LED is made to light
up as a trouble state.
(7)
Set up for receiving
the alarm signals
: 5%/m
(8)
External wiring
resistance
: Less than 10Ω
(9)
Start up time
: After the power on and after the maximum of 2 minutes
start of supervision.
(10)
Signal contact output : Alarm contact output
Contact type
State
Between
COM and NO
Between
COM and NC
Normal supervision
Close
Open
Alarm or Power off
Open
Close
Zone alarm
Close
Open
: Trouble contact output
Contact type
State
Between
COM and NO
Between
COM and NC
Normal supervision
Close
Open
Trouble occurs or Power off
Open
Close
・Please install the power supply only for the control unit as
much as possible.
・Please give the noise in the power supply to the control unit
as 1Vp-p or less.
・Please correspond with the power supply filter etc, when there
is a noise.
!
!
!
!
Warning
Caution
!
!
!
!
Caution
!
!
!
!
Please do not connect the detector of the same address. It becomes
not be able to watch normally.
External wiring value of resistance please do not wire above 10
Ω. Supervision stops impossible normally.