2.2.
Installation of control unit
2.2.1.
FC1-DY
FC1-DY is DIN rail mount type.
Loosen the screw of the metallic parts for the installation of 2 places which are on the
side of control unit itself. And put the control unit to the fixed 35mm width DIN rail.
Tighten the screw in the specified torque range. Please ensure that equipment installed
correctly.
(torque 1.00~1.35N・m: Reference value)
2.2.2.
FC1-HY
FC1-HY is surface mount type.
Using the two screw holes of the metallic parts for the installation of 2 places which are
on the both side of control unit itself, please install securely in the equipment.
Tighten the screw in the specified torque range. Please ensure that equipment installed
correctly.
Please you have to match the screw installations environments.
・ Incorrect loading of the equipments can cause a malfunction,
failure or drop.
・Tighten the screw in the specified torque range.
・Under tightening can cause a drop, malfunction.
・Over tightening can cause a drop, malfunction due to damage to
the screw or he equipments and malfunction.
!
!
!
!
Warning