Procedures/steps to be taken in the event of trouble occurrence

Procedures/steps to be taken in the event of trouble occurrence

Procedures/steps to be taken in the event of trouble occurrence

Procedures/steps to be taken in the event of trouble occurrence 

  

 

Control unit indications 

POWER 

TROUBLE 

7 Seg. LED 

Buzzer 

Smoke 

detector 

LED 

Contents of trouble 

Confirmation Items 

DTECTOR 
LED 
Lighting 

Corresponding 
detector’s 
address is 
indicated 

Intermittence 
rumble 

Blinking 10 
seconds 
interval 

or 

Corresponding 
detector’s LED 
turns off. 

-Communication line 
power failure 
-Internal abnormality 
of detector 
-Smoke detector 
sensitivity revision 
over 

-Replace the detector. 

OVER 
LED 
Lighting 

None 

Intermittence 
rumble 

Blinking 10 
seconds 
interval 
 

The number of detectors 
which have been 
recognized is greater 
than specification at 
the detector number 
switch of control unit. 

Make  the  specification 
of  the  detector  number 
switch and the number of 
connected 

detectors 

equal. 

UNDER 
LED 
Lighting 

None because 
the 
disconnection 
before the 
power supply 
on cannot 
recognize  
the address,  

or 

When the 
disconnection 
is detected 
after the 
power supply 
on, the broken 
wire detector 
address is 
displayed. 
 

Intermittence 
rumble 

Blinking 10 
seconds 
interval 

or 

Turning off 

-The number of 
detectors which have 
been recognized is less 
than specification at 
the detector number 
switch of control unit. 
-Broken wire of 
communication line 
-Broken wire inside 
detector 
-Falling off of 
detector 

-Make the specification 
of the detector number 
switch and the number of 
connected detectors 
equal. 
-Make sure of wiring 
which is to be correctly 
done. 
-Insert correctly the 
communication line into 
the Terminal Block of 
control unit. 
-Insert correctly the 
communication line into 
the Terminal Block of the 
detector. 
-Please verify whether 
the communication line 
has not been 
disconnected. 

SHORT 
LED 
Lighting 

None 

Intermittence 
rumble 

Turning off 

-Communication line 
short circuit 

The communication line 
is short. Just please 
wire. 

Lighting 

RECIEVER 
LED 
Lighting 

None 

Intermittence 
rumble 

Blinking 10 
seconds 
interval 

-Specification of 
detector number 
switches of control 
unit 0 or 32 or more. 
-The power switch or 
flash memory of control 
unit is abnormal. 

-Please verify the 
detector number switch 
setting of control unit. 
-In case of control unit 
trouble, please 
exchange. 

Turning 
off 

Turning 
off 

‘E’ or ‘E.’

 

 indication 

Continual  
rumble 

Turning off 

Control unit CPU error.  Because it is breakdown 

of control unit. 

 

 

 

 

Caution

 

! 

  

 

Doing the above-mentioned coping, case problem is not solved, please 

inform to the nearby Fenwal Controls of Japan Co., Ltd. 

The time of trouble occurrence, when you redo wiring or exchanging 

the detector, Do it after turning off power. 

Summary of Contents for FC1

Page 1: ...anual we have shown the important notice in order for you to use the device just and the method of handling this system In addition to you read this manual well before the utilization understanding well and use After you read in the place where it is seen with anytime please be sure to keep ES0911 K5 ...

Page 2: ...ecifications 19 3 6 Mechanical specifications 19 4 Procedures steps to be taken in the event of alarm occurrence 20 4 1 Alarm 20 4 2 Zone Alarm 20 5 Indication of the time of trouble 21 6 Procedures steps to be taken in the event of trouble occurrence 22 7 Detector 23 7 1 Connectable detector 23 8 Serial communication facility 24 9 Maintenance and Inspection 25 9 1 Daily Inspection 25 9 2 Periodic...

Page 3: ...ntrol unit which has impacted And also do not paint a control unit Do not soak a control unit in water and do not put a control unit into water It causes electric shock Do not use the method that not listed in this manual It causes trouble Caution This system only tells the outbreak of a fire This system is not Fire prevention systems And Fire extinguishing system Do not use at the place where it ...

Page 4: ...ponds next you exclude from the object of this guarantee Fire earthquake and the damage by wind and flood breakdown and the loss by the thunderbolt and other natural disasters etc After the shipping transporting and moving and falling etc at your corporation breakdown and the loss with inadequate handling When cause of breakdown due to the reason other than the payment item Error in regard to use ...

Page 5: ...trols the indicating LED and 7seg LED and the buzzer and signal contact according to the state of the detector and itself FC1 DY DIN rail mount type FC1 HY Surface mount type Communication line It is the line which shares the power supply and the communication line of the detector Detector The connectable detector is shown with the 7th section 2 1 2 Power Supply Power supply of the control unit is...

Page 6: ...surface mount type Using the two screw holes of the metallic parts for the installation of 2 places which are on the both side of control unit itself please install securely in the equipment Tighten the screw in the specified torque range Please ensure that equipment installed correctly Please you have to match the screw installations environments Incorrect loading of the equipments can cause a ma...

Page 7: ...for detector installation with the two screws M3 which is more than 15mm length And install the detector just in the mounting base Caution Caution Install and use with environmental temperature and the humidity which are within specification value If the control unit is not correctly installed it causes the malfunction the breakdown and the fall Please note it especially when using it with a lot o...

Page 8: ...es out other electric noise and separate from it Please do the wiring after the external power supply off It may get an electric shock or the control unit may break down Please use the terminal cover for the control unit when the unit is energized after do the wiring If the terminal cover is not used it may get an electric shock When miss wiring or connecting to a power supply different from ratin...

Page 9: ...ower on the alarm LED and the trouble LED blink sequentially 2 Control unit supplying power to the detector which is connected starts communication Control unit inspects the address of all detectors which are connected registers the detector automatically When detectors of a quantity which is set in 120 seconds are registered supervision is started When a quantity which is set with control unit an...

Page 10: ...ime becomes alarm state The alarm LED and the trouble LED blink sequentially while resetting the alarm one by one Also each segment LED of 7seg LED blinks in order one at a time c DET NUMBERS 10 Detector numbers switch X10 This is the switch whereby to set the connectable detector numbers by ten digits X10 Caution Caution After turning off the system until it turns on power supply again please pro...

Page 11: ...hen the alarm occurs alarm LED is indicated in preferentially from indication of other things g TROUBLE Trouble indication LED Yellow While trouble occurs in the system the trouble LED which corresponds to the contents of trouble lights up or blinks Details of trouble contents please refer to 6 Procedures steps to be taken in the event of trouble mode h Buzzer Embedded In case of alarm state it ru...

Page 12: ...occurrence 00 is indicated In addition As for 7seg LED indication 00 the scroll it indicates in the order where the alarm generates indication and the address indication to which the alarm occurs When control unit CPU error occurs E or E indicates Because this indication is breakdown of control unit please exchange Caution Caution Caution When trouble occurs in alarm state for alarm priority indic...

Page 13: ...Warning Please install the bundled terminal cover in order to prevent accident such as electric shock Use the proper screw driver bit for screw size Tighten inside of torque Do not input the power source other than DC 24V to the terminal Do not exceed the service voltage range It becomes cause of accident such as fire Making a mistake in polarity and connect the equipment breaks down Do not connec...

Page 14: ...t is off the non voltage contact point is output State of control unit contact Power on Open Power off Close Caution Caution Caution Warning Do not exceed the maximum of contact point voltage and the maximum of contact point electric current in this terminal It becomes cause of breakdown such as contact point depositing Do not exceed the maximum of contact point voltage and the maximum of contact ...

Page 15: ...ater than specification at the detector number switch of control unit c DET UNDER It lights up when the number of detectors which have been recognized is less than specification at the detector number switch of control unit Control unit the numbers of detectors recognizing few lights up similarly even when being disconnected of the communication line and broken wire inside the detector d PCL SHORT...

Page 16: ...730110 K0 16 ES0911 Page 3 3 Dimensions 3 3 1 FC1 DY 3 3 2 FC1 HY ...

Page 17: ... contact output Alarm contact output Contact type State Between COM and NO Between COM and NC Normal supervision Close Open Alarm or Power off Open Close Zone alarm Close Open Trouble contact output Contact type State Between COM and NO Between COM and NC Normal supervision Close Open Trouble occurs or Power off Open Close Please install the power supply only for the control unit as much as possib...

Page 18: ... continual sound priority 12 On off of power switch At the time of power switch operating when power source is turned on again please take the interval of 1 minute or more When while the power switch is on main power source is stopped directly when main power source is turned on again please take the interval of 1 minute or more Warning Do not disassemble the equipment Electric shock short circuit...

Page 19: ...echanical specifications 1 External form W125 D104 H40 FC1 DY W121 D104 H40 FC1 HY 2 Main material SPCC t1 0 black paint 3 Mass Approximately 420g Warning Do not use at the place where it exceeds environmental specification and the place where the volatilization gas and the corrosiveness gas occur It becomes cause of breakdown such that it stops operating normally ...

Page 20: ...m occurs when the alarm signal AON from the detector is received by the control unit 1 The alarm LED lights up 2 The buzzer continual sound rumbles 3 The alarm signal contact is output 4 The alarm detector address is indicated in 7seg LED indication 4 2 Zone Alarm The zone alarm is one of alarm information That occurs when address recognition becomes impossible in communication obstacle and contro...

Page 21: ...tion When the primary factor of trouble is a detector the state indicating lamp of the detector which is trouble state red LED it goes out When warning is output verifying trouble to following 6 the coping method at the time of trouble occurrence please correspond When there is a trouble primary factor in the detector the state indicating LED red LED of the detector which is trouble state goes out...

Page 22: ...val or Turning off The number of detectors which have been recognized is less than specification at the detector number switch of control unit Broken wire of communication line Broken wire inside detector Falling off of detector Make the specification of the detector number switch and the number of connected detectors equal Make sure of wiring which is to be correctly done Insert correctly the com...

Page 23: ...pression official operation density 5 m Mounting base FBR Y Smoke Detector SRU 3SH ESD photoelectric expression official operation density 5 m Mounting base FDB ADS Heat Detector F21 Fixed temperature type Alarming Fixed temperature range is 70 158F Mounting base FBR Y Repeater SRU C Non voltage contact supervision Installation metallic parts Repeater SRU Z Non voltage contact supervision DC24V 1A...

Page 24: ...tion facility Serial communication facility Serial communication facility Serial communication facility This control unit has a serial communication function Please inquire about this facility to the Fenwal Controls of Japan Co Ltd Tokyo headquarters ...

Page 25: ... Retighten Screws should not be loose Retighten the terminal screws with the proper torque 4 Behavior Power LED Check visually The LED must be ON Green Normal Supervision The Control unit The rest of LED except the Power LED Check visually The LED must be Off Please refer to section 6 Buzzer Listening The buzzer must be off The Detector State indic1ation LED Check visually Blinking 10 seconds inte...

Page 26: ...ratings of each equipment Changed to the voltage within the ratings 5 Installation Common Looseness rattling Move the module to check The module must be installed solidly Retighten the screws If the modules are loose fix it with screws 6 Appearance Common Dirt and foreign matter Check visually Dirt and foreign matter must not be present Remove and clean Damage Check visually There is no damage on ...

Page 27: ...inal while the unit is energized It may get an electric shock Please do the cleaning and the increase tightening of the screw after the power supply off If not the power supply off it may get an electric shock Do not soak a detector in water and do not put a detector into water It causes electric shock and trouble Under tightening can cause a drop malfunction Over tightening can cause a drop malfu...

Page 28: ...the state of normal supervision The control unit The rest of LED except the Power LED The LED must be Off Buzzer The buzzer must be off Signal contact output Not output The detector State indic1ation LED Blinking 10 seconds interval 2 Starting Functional Inspection Alarm LED The control unit Trouble LED Each LED blinks sequentially one by one Reset switch pushing of the control unit 7seg LED Funct...

Page 29: ...minutes The control unit The rest of LED except the Power LED The LED must be Off Buzzer The buzzer must be off Signal contact output Not output The detector State indic1ation LED Blinking 10 seconds interval Please inquire of our company when it doesn t return normal supervision Please confirm the return to the state of normal supervision to Functional Inspection Caution ...

Page 30: ...al Disposal methods are specific criteria depending on each municipality 11 11 11 11 Support Support Support Support Please inquire about this control unit to the Fenwal Controls of Japan Co Ltd Tokyo headquarters Fenwal Controls of Japan Co Ltd 1 5 10 Iidabashi Chiyoda Tokyo 102 0072 Japan Tokyo headquarters 81 3 3237 3565 ...

Reviews: