F-35-53-CE

TROUBLESHOOTING

Note:

The code will repeat every 3 seconds. Removing 

power from the control will clear the fault code.

Internal Control Failure

If the control detects a software or hardware error, all outputs 

are turned off and the red LED displays a Steady On condition. 

If this condition persists after an attempt to restart, then the 

control must be replaced.

WARNING

Risk of Explosion or Fire

The 35-53CE control cannot be serviced by the 

user. If any control faults are detected, the 35-53 

control must be replaced by qualified service 

personnel. Risk of explosion or fire can result if 

the control module has been opened or with any 

attempts to repair it, and the warranty is void.

Troubleshooting Guide

Symptom

Recommended Actions

1. Dead

A. Miswired
B. Transformer/battery fault
C. Fuse/circuit breaker fault
D. No voltage at PWR or AIR
E. Bad control

2. Thermostat on - no blower 
output

A. Miswired or failed air flow 

switch

B. Faulty thermostat, no 

voltage at thermostat 
terminal TH

C. Faulty control

3. Airflow Switch input okay, but 
no TFI after purge delay

A. Miswired
B. Faulty control

4. Valve on, no spark

A. Valve coil open
B. Open valve wire
C. Faulty control 

(check voltage between V1 
and GND)

5. Flame okay during TFI, no 

flame sense (after TFI)

A. Faulty electrode
B. Faulty HV wire
C. Poor ground at burner
D. Faulty control (check flame 

current)

Fault Conditions - Red diagnostic LED

LED Indication

Fault Mode

Off

Normal

Steady On

Internal Control Failure

1 flash 

Airflow / Limit Fault

2 flashes 

False Flame

3 flashes

Ignition Lockout Fault

5 flashes

Low Voltage Fault *

Low Voltage Fault is below 8.7 VDC

Summary of Contents for 35-53CE Series

Page 1: ...s the blower function if not required allowing one part to address all service or OEM needs Agency Certifications EN298 CE 584099 Classification BMRVXN Mobile Applications DC supply type A B C Code Compliant to AS 4625 2008 AS 4622 2004 CAN CSA E60730 1 ANSI Z21 20 CAN CSA C22 2 No 60730 2 5 Compliant with current RoHS standards SPECIFICATIONS Input Power Control 9 2 to 15 VDC from a stor age batt...

Page 2: ...stic LED will indicate the fault code for igni tion lockout 3 Flashes Flame Failure FLAME FAILURE RECYCLE MODE Standard With the Recycle after Loss of Flame option upon loss of flame the gas valve is de energized and the control proceeds to inter purge before attempting to relight the flame Multi try models permit three tries for ignition including inter purges If the burner relights normal operat...

Page 3: ...t has been exposed to water must be replaced WARNING All wiring must be done in accordance with both local and national electrical code and by a trained service technician Wiring must be at least 18 AWG rated for 105 C or higher WARNING The 35 53CE uses voltages of shock hazard potential Wiring and initial operation must be done by qualified service technician WARNING Operation outside specificati...

Page 4: ...wer Relay Figure 2 Local Sense without Blower Relay Figure 3 Remote Sense with Blower Relay Figure 4 Remote Sense without Blower Relay DIMENSIONS INTEGRAL STANDOFF 4 250 3 750 250 3 250 2 750 250 6 PIN EDGE CONNECTOR 1 25 NOM 218 MAX 250 Q C H V TERMINAL 164 010 DIA 4 MOUNTING HOLES ...

Page 5: ...lectrode Location Proper location of electrode assembly is important for optimum system performance The electrode assembly should be located so that the tips are inside the flame envelope and about 1 2 inch 1 2 cm above the base of the flame as shown Notes Ceramic insulators must not be in or close to the flame Electrode assemblies must not be adjusted or disassembled Electrodes are NOT field adju...

Page 6: ...s void Troubleshooting Guide Symptom Recommended Actions 1 Dead A Miswired B Transformer battery fault C Fuse circuit breaker fault D No voltage at PWR or AIR E Bad control 2 Thermostat on no blower output A Miswired or failed air flow switch B Faulty thermostat no voltage at thermostat terminal TH C Faulty control 3 Airflow Switch input okay but no TFI after purge delay A Miswired B Faulty contro...

Page 7: ... X X X X DESCRIPTION Trial for Ignition Time 1 5 econds 3 7 econds 5 10 econds 7 25 econds S S S S Inter Purge 0 None 1 15 econds 3 25 econds S S Product Designation 2 CE EN298 Standard Recycle 3 CE EN298 Special Configuration A 3 in this location indicates a special configuration Consult Fenwal controls for operating characteristics of this control Pre Purge 0 None 1 15 Seconds 3 25 Seconds Tries...

Page 8: ...3 SERIES 35 60 61 63 608 SERIES 35 65 66 SERIES 35 9X The object of the declaration described above is in conformity within the relevant union harmonization legislation Gas Appliance Regulation EU 2016 426 Low Voltage Directive 2014 35 EC EMC Directive 2014 30 EC Rohs 2011 65 EU The following harmonized standards and technical specifications have been applied EN298 2012 Automatic Burner Control sy...

Reviews: