Effective: January 2020

F-35-53-CE

3

MOUNTING AND WIRING

The 35-53CE is not position sensitive and can be mounted 

vertically or horizontally. The control may be mounted on any 

surface and fastened with #6 sheet metal screws. Secure the 

control in an area that will experience a minimum of vibration 

and remain below the maximum ambient temperature of 176°F 

(80°C).
All connections should be made with UL approved, 105°C rated, 

18 gauge stranded wire with .054” minimum insulation thick

-

ness. Refer to the appropriate wiring diagram when connecting 

the 35-53CE to other components in the system.

TERMINAL DESIGNATIONS

CAUTION

Label all wires prior to disconnection when ser

-

vicing or replacing controls. Wiring errors can 

cause improper and dangerous operation. A 

functional checkout of a replacement control 

should always be performed.

CAUTION

The control must be mounted and located in a 

manner which protects components from expo

-

sure to water (dripping, condensate, spraying, 

rain). Any control that has been exposed to 

water must be replaced.

WARNING

All wiring must be done in accordance with both 

local and national electrical code, and by a 

trained service technician. Wiring must be at 

least #18 AWG rated for 105°C or higher.

WARNING

The 35-53CE uses voltages of shock hazard 

potential. Wiring and initial operation must be 

done by qualified service technician.

WARNING

Operation outside specifications could result in 

failure of the Fenwal product and other equip

-

ment with injury to people and property.

WARNING

Do not disconnect battery or any electrical loads 

while the automatic gas ignition control is pow

-

ered.

Name

Description

Terminal Type

Location

Wire 

Color**

PWR

*

+12 VDC 

Power

3/16” male Q.C.

BLO

*

Blower

1/4” male Q.C.

AIR

*

Airflow Switch

6 Pin Edge 

Connect

1

Red

TH

*

Thermostat

6 Pin Edge 

Connect

2

Orange

NC

NC Contact

6 Pin Edge 
Connect

3

Blue

V1

Gas Valve

6 Pin Edge 
Connect

4

Brown

TEST/
SENSE

Local Sense

Unused

5

-

Remote Sense

6 Pin Edge 
Connect

5

Black

GND

Ground

6 Pin Edge 
Connect

6

Yellow

HV

H.V. Spark

1/4” male Q.C.

*

 For applications without blower control, AIR terminal is used to pro

-

vide +12 VDC power. PWR, BLO, and TH are not used.

**

 Colors for Fenwal Controls wire harnesses

Summary of Contents for 35-53CE Series

Page 1: ...s the blower function if not required allowing one part to address all service or OEM needs Agency Certifications EN298 CE 584099 Classification BMRVXN Mobile Applications DC supply type A B C Code Compliant to AS 4625 2008 AS 4622 2004 CAN CSA E60730 1 ANSI Z21 20 CAN CSA C22 2 No 60730 2 5 Compliant with current RoHS standards SPECIFICATIONS Input Power Control 9 2 to 15 VDC from a stor age batt...

Page 2: ...stic LED will indicate the fault code for igni tion lockout 3 Flashes Flame Failure FLAME FAILURE RECYCLE MODE Standard With the Recycle after Loss of Flame option upon loss of flame the gas valve is de energized and the control proceeds to inter purge before attempting to relight the flame Multi try models permit three tries for ignition including inter purges If the burner relights normal operat...

Page 3: ...t has been exposed to water must be replaced WARNING All wiring must be done in accordance with both local and national electrical code and by a trained service technician Wiring must be at least 18 AWG rated for 105 C or higher WARNING The 35 53CE uses voltages of shock hazard potential Wiring and initial operation must be done by qualified service technician WARNING Operation outside specificati...

Page 4: ...wer Relay Figure 2 Local Sense without Blower Relay Figure 3 Remote Sense with Blower Relay Figure 4 Remote Sense without Blower Relay DIMENSIONS INTEGRAL STANDOFF 4 250 3 750 250 3 250 2 750 250 6 PIN EDGE CONNECTOR 1 25 NOM 218 MAX 250 Q C H V TERMINAL 164 010 DIA 4 MOUNTING HOLES ...

Page 5: ...lectrode Location Proper location of electrode assembly is important for optimum system performance The electrode assembly should be located so that the tips are inside the flame envelope and about 1 2 inch 1 2 cm above the base of the flame as shown Notes Ceramic insulators must not be in or close to the flame Electrode assemblies must not be adjusted or disassembled Electrodes are NOT field adju...

Page 6: ...s void Troubleshooting Guide Symptom Recommended Actions 1 Dead A Miswired B Transformer battery fault C Fuse circuit breaker fault D No voltage at PWR or AIR E Bad control 2 Thermostat on no blower output A Miswired or failed air flow switch B Faulty thermostat no voltage at thermostat terminal TH C Faulty control 3 Airflow Switch input okay but no TFI after purge delay A Miswired B Faulty contro...

Page 7: ... X X X X DESCRIPTION Trial for Ignition Time 1 5 econds 3 7 econds 5 10 econds 7 25 econds S S S S Inter Purge 0 None 1 15 econds 3 25 econds S S Product Designation 2 CE EN298 Standard Recycle 3 CE EN298 Special Configuration A 3 in this location indicates a special configuration Consult Fenwal controls for operating characteristics of this control Pre Purge 0 None 1 15 Seconds 3 25 Seconds Tries...

Page 8: ...3 SERIES 35 60 61 63 608 SERIES 35 65 66 SERIES 35 9X The object of the declaration described above is in conformity within the relevant union harmonization legislation Gas Appliance Regulation EU 2016 426 Low Voltage Directive 2014 35 EC EMC Directive 2014 30 EC Rohs 2011 65 EU The following harmonized standards and technical specifications have been applied EN298 2012 Automatic Burner Control sy...

Reviews: