Installation & Operating Instructions
ııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııı
Page 17
www.fptgroup.com
Fenner is a registered trademark of J.H. Fenner & Co. Limited
ııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııııı
Page 16
www.fptgroup.com
Fenner is a registered trademark of J.H. Fenner & Co. Limited
Installation & Operating Instructions
Analog speed input with 1 preset speed
and motor thermistor trip
Local or remote analog speeds
(2 analog inputs)
Push button fwd/rev/stop with fast stop
using 2nd deceleration ramp
8.2. K
EYPAD MODE
(P-12 = 1
OR
2)
E
XAMPLE
W
IRING
Remote push button speed control with
fwd/rev
Analog speed input with 2 preset speeds
By default if the enable signal is present the drive will not Enable until the START button is pressed. To automatically enable
the drive when the enable signal is present set P-31 = 2 or 3. This then disables the use of the START & STOP buttons
NOTE
8.3. MODBUS
CONTROL MODE
(P12 = 3
OR
4)
Further information the MODBUS RTU Register Map information and communication setup; please refer to the Advanced
User Guide.
8.4. U
SER
PI
CONTROL MODE
(P-12 = 5
OR
6)
E
XAMPLE
W
IRING
Remote closed loop PI feedback control
with Local Preset speed 1
Remote closed loop PI feedback control
with Local Analog speed input
Remote closed loop PI feedback control
with Local Preset speed 1 and motor
thermistor trip
By default the PI reference is set for a digital reference level set in P-45.
When using an Analog reference set P-44 = 1 (analog) and connect reference signal to analog input 1 (T6).
The default settings for proportional gain (P-41), integral gain (P-42) and feedback mode (P-43) are suitable for most HVAC
and pumping applications.
The analog reference used for PI controller can also be used as the local speed reference when P15=1.
NOTE
Further information on configuring the PI controller for typical feedback applications; please refer to the Advanced User Guide.
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0, 1,
Open: Stop (disable)
Closed : remote UP
Closed : remote DOWN
Open : Forward
5,
Closed: Run (enable)
push-button
push-button
+24V : Reverse
8..12
2
Open: Stop (disable)
Closed : remote UP
Closed : remote DOWN
Open : Keypad speed ref
Closed: Run (enable)
push-button
push-button
+24V : Preset speed 1
Open: Stop (disable)
Closed : remote UP
External trip input :
Closed : remote DOWN
Connect external
3
1)
Closed: Run (enable)
push-button
Open: Trip, Closed: Run
push-button
thermistor type PT100 or
similar to digital input 3
4
Open: Stop (disable)
Closed : remote UP
Open : Keypad speed ref
Analog input 1
Closed: Run (enable)
push-button
Closed : Analog input 1
Open: Stop (disable)
Open : Forward run
External trip input :
Open : Keypad speed ref
Connect external
6
1)
Closed: Run (enable)
Closed : Reverse run
Open: Trip, Closed: Run
+24V : Preset speed 1
thermistor type PT100 or
similar to digital input 3
Open: Forward Stop
Open: Reverse Stop
External trip input :
Open : Keypad speed ref
Closing digital inputs 1
7
Closed: Forward Run
Closed: Reverse Run
Open: Trip, Closed: Run
+24V : Preset speed 1
and 2 together carries out
a fast stop (P-24)
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0..2,
Run and stop commands
4..5,
Open: Stop (disable)
No effect
No effect
No effect
given via the RS485 link
8..12
Closed: Run (enable)
and Digital input 1 must be
closed for the drive to run.
Open: Stop (disable)
Open : Master speed ref
External trip input :
Connect external
3
1)
Closed: Run (enable)
Closed : Preset speed 1
Open: Trip, Closed: Run
No effect
thermistor type PT100 or
similar to digital input 3
6
1)
Open: Stop (disable)
Open : Master speed ref
External trip input :
Analog input reference
Master Speed Ref - start
Closed: Run (enable)
Closed : Analog input
Open: Trip, Closed: Run
and stop controlled via
RS485. Keypad Speed Ref
Open: Stop (disable)
Open : Master speed ref
External trip input :
No effect
- drive auto runs if digital
7
1)
Closed: Run (enable)
Closed : keypad speed ref Open: Trip, Closed: Run
input 1 closed, depending
on P-31 setting
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0, 2,
Open: Stop (disable)
Open : PI control
PI feedback analog input
No effect
4..5,
Closed: Run (enable)
Closed : Preset speed 1
8..12
1
Open: Stop (disable)
Open : PI control
PI feedback analog input
Analog input 1
Closed: Run (enable)
Closed : Analog input 1
3, 6,
Open: Stop (disable)
Open : PI control
External trip input :
Connect external
7
1)
Closed: Run (enable)
Closed : Preset speed 1
Open: Trip, Closed: Run
PI feedback analog input
thermistor type PT100 or
similar to digital input 3
Fenner QDE User Guide 9/5/08 9:24 AM Page 17