· MANUFACTURING FOR INDUSTRIAL AUTOMATION
14
13.
Configuration menu
13.1 Function codes
The fastest way to configure the instrument, is to select a predefined
configuration code (see section 8). At the ‘
Configuration code
’ (
codE
)
parameter use keys ‘
UP
’ (
5
) and ‘
LE
’ (
3
) to move up and down
through the list of codes. Locate the desired code, and press ‘
SQ
’ (
<
).
The instrument shows the ‘
codE
’ parameter. Press ‘
LE
’ (
3
) to exit the
‘
configuration menu
’. The instrument stores the new configuration,
applies a ‘
power-up
’ routine and returns to the ‘
normal mode
’ of operation
(see section 12.2).
Selecting a ‘
reserved
’ code or ‘
----
’ returns to the previous menu without
changes.
When entering the ‘
Function code
’ (
codE
) parameter, the active
‘
configuration code
’ is displayed. If the actual configuration does not
match any of the configuration codes, code ‘
uSEr
’ is displayed.
There are different codes for 4/20 mA output (codes from 010 to 099)
and 0/10 Vdc output (codes from 110 to 199) (see section 8).
Custom input and output signal ranges can be configured at the
‘
Advanced scaling
’ section of the ‘
configuration menu
Configuration code
13.2
Initial configuration
At the ‘
Input configuration
’ (
InP
) menu entry, configure the reading
mode and the input signal range.
If you have already selected a configuration code (see section
13.1), the input signal has been already selected and there is
no need to manually select the ‘
Mode
’ (
ModE
) or ‘
Signal range
’
(
rAnG
) parameters again.
At the ‘
Mode
’ (
ModE
) parameter select ‘
cELL
’
for load cell measurement,
or select
‘
MV
’ for millivolt measurement. See section 7.2 and 7.3 for an
explanation of the differences between both modes.
At the ‘
Signal range
’ (
rAnG
) parameter select the input signal range.
Input signal ranges can also be configured by selecting a pre-defined
configuration code (see section 13.1).
For an example on how to calculate the appropriate input signal range
for a given load cell, see section 7.7.
To customize to an intermediate range (for example 0/7.5 mV) see
section 13.4. To manually select the output signal see section 13.3.
At the ‘
Excitation voltage
’ (
V.EXc
) parameter select ‘
oFF
’ to disable the
excitation voltage. Excitation voltage is set to ‘
on
’ when selecting the
‘
cELL
’ mode, and set to ‘
oFF
’ when selecting the ‘
MV
’ mode at the ‘
Mode
’
(
ModE
) parameter.
13.3 Output range
At the ‘
Output range
’ (
out
) menu entry, select the output signal range to
4/20 mA (value ‘
420
’) or to 0/10 Vdc (value ‘
010
’).
The output signal range selected can be later customized to operate in a
reduced range of signal (see section 13.4).
Output range
Input conf.
Mode
Load cell mode
Millivolt mode
Signal range
0/5 mV
0/10 mV
0/15 mV
0/20 mV
0/25 mV
0/30 mV
0/40 mV
Excitation voltage
Excitation voltage
0/50 mV
0/60 mV
0/70 mV
0/80 mV
±10 mV
±20 mV
±30 mV
±40 mV
±50 mV
±60 mV
±70 mV
±80 mV
±5 mV
Summary of Contents for I4 Series
Page 24: ......