6

Decimal point

1.10 Configuration menu

Press ‘SQ’ (

<

) for 1 second to access the ‘

configuration menu’. 

For a description on how to operate inside the menus see sec

-

tion 

1.8

. For a full vision of the ‘

configuration menu

’ structure 

see section 

1.11.

Scaling

Input low

Display low

Input high

Display high

To configure the initial set up of the instrument, select the input sig

-

nal range, the decimal point position, and scale the reading.
Access the ‘

Input

’ (‘

InP

’) menu to select the input signal range. Op

-

tions available are 4/20

mA, 0/10

Vdc, ±20

mA y ±10

Vdc. Select the 

rear jumper at position ‘4’ for Vdc or ‘5’ for mA 

(see section 1.5).

Access the ‘

Decimal point

’ (‘

dP

’) menu to select the decimal point 

position. Move the decimal point by pressing the ‘LE’ (

3

) key.

Scale the reading at the ‘

Scaling

’ (‘

ScAL

’) menu. There are four pa

-

rameters to configure :

• ‘

Input low

’ (‘

ILo

’) 

- minimum input signal, in mA or Vdc with 

two decimals.

• ‘

Display low

’ (‘

dLo

’)  - reading associated to the minimum input 

signal.
• ‘

Input high

’ (‘

IhI

’) 

- maximum input signal, in mA or Vdc with 

two decimals..

• ‘

Display high

’ (‘

dhI

’)  - reading associated to the maximum input 

signal.

The ‘

Field correction

’ (‘

F.cor

’) functions allows to correct the instru

-

ment scaling parameters, when the instrument is being installed on 

the field, providing a fast and easy way to compensate offset signals.
To operate the ‘

Field correction

’ (‘

F.cor

’) function for the offset cor

-

rection,  generate  the  minimum  input  signal  and  access  the  ‘

Field 

low

’ (‘

F.Lo

’) function. Then the following sequence will start

 

• message with signal type (‘

mA

’ or ‘

Vdc

’)

 

 

• message ‘

wait

’ (‘

WAIt

’) in flash mode

 

 

• after 5 seconds, message ‘

ok

’ (‘

oK

’) appears

 

 

• at this point, press key SQ (‘

<

‘)

 

 

• the menu returns to menu entry ‘

Field Low

’ (‘

F.Lo

’)

The instrument has read the input signal and automatically config

-

ures the ‘

Input low

’ (‘

I.Lo

’) for you.

Repeat the process generating the maximum input signal and access 

the ‘

Field high

’ (‘

F.hI

’) menu. The instrument will read the input sig

-

nal and automatically configure the ‘

Input high

’ (‘

I.hI

’) parameter to 

match the signal read.

Application - a 0/10 Bar pressure transmitter provides a 4/20 mA out-

put signal. At installation, the operator detects that the reading at 

0 Bar is 0.34 Bar and that at 10 Bar the reading is 10.72 Bar. Apply the 

Field correction

’ / ‘

F.Lo

’ function while reading is 0.34 Bar and the 

instrument will automatically correct the reading to 0.00 Bar. After-

wards, apply the ‘

Field correction

’ / ‘

F.Hi

’ function while reading is 

10.72 Bar and the instrument will automatically correct the reading 

to 10.00 Bar. 

1.10.1 

Initial set-up

1.10.2 

Field correction

Range de 4/20 mA

Range de 0/10 Vdc

Range de ±20 mA

Range de ±10 Vdc

Input

Field correction

Correction high

Correction low

Wait (5 sec.)

 (

<

Wait (5 sec.)

 (

<

Summary of Contents for S40-P

Page 1: ...linearization fast access to alarm setpoints tare function on power up function measure function configurable reading brightness Universal AC and DC power Up to 2 optional modules for output and contr...

Page 2: ...hold for test break applications see section 1 10 4 Multiple display filters memory for maximum and minimum reading password protection 5 brightness levels 1 1 How to order Index 1 Panel meter S40 P...

Page 3: ...connections Button UP Logo Alarms Units Button SQ Button LE Configuration menu see section 1 10 Fast access see section 1 10 6 1 6 Mechanical dimensions mm Signal see section 1 5 Jumpers see section...

Page 4: ...Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20 mA 0 05 FS 11 Ohm 100 mA permanent 10 ppm C 25 ppm C 0 10 Vdc 0 05 FS 932 KOhm 100 Vdc permanent 10 ppm C 25...

Page 5: ...Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the chang...

Page 6: ...ed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the offset cor rection generate the minimum input signal and access the Fi...

Page 7: ...e alarm relays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set po...

Page 8: ...ory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see...

Page 9: ...at the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP...

Page 10: ...rE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does not...

Page 11: ...menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this function it is possible to ada...

Page 12: ...on 1 10 for a description of each menu entry Scaling Input low Display low Input high Display high Alarm 1 Setpoint Hysteresis Setpoint 2 Active Alarm type Activation delay Deactivation delay Left zer...

Page 13: ...ng Activate Reset Number of segments Value 2 to 20 Input 0 Display 0 Input 1 Display 1 On power up Delay Tare Seconds Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configurati...

Page 14: ...el only You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock the lower clips marked with B...

Page 15: ...ay 0 seconds Tare off Key LE no function Excitation voltage 20 Vdc Password off Brightness 3 clean by using a humid rag and do NOT use abrasive products such as alcohols solvents etc General recommend...

Page 16: ...t 1 Power Signal A B C A B C The R1 module provides 1 relay output to to install at digital panel meters from Series S up to a maximum of 2 relays in a single meter Note for more than 2 relays per ins...

Page 17: ...ayed installation as it does not require soldering or special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more inform...

Page 18: ...uration Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_i pdf Protocol Modbus RTU Functi...

Page 19: ...up to 31 modules Frames codified in represent able ASCII characters codes 32 to 255 directly visible using hyper terminal or similar programs Access to display values alarm status memory of maximum a...

Page 20: ......

Reviews: