background image

FEMA ELECTRÓNICA . Series M . M40-P

10

On power-up

Delay

Tare

Seconds

Tools

1.10 Configuration menu (cont.)

The ‘

On Power Up

’ (‘

on.Pu

’) menu configures functions to apply at 

start-up. It applies only to instrument restart after power loss. It does 
not apply to instrument restart due to change in configuration.

• parameter ‘

Delay

’ (‘

dLAy

’) assigns a waiting time in seconds. The 

instrument waits the configured time before starting normal func-
tion. During this waiting time, the display shows all decimal points 
on in flash mode, all alarms are in ‘oFF’ state, there is no signal acqui-
sition and there is no communications or control being performed. 
After  the  configured  time  is  over,  the  instrument  starts  in  normal 
function. Delay value between 0 and 200 seconds.

Application - the start-up process for an automation system implies 
that different parts of the system (engines, actuators, controllers, ...) 
have different start-up times. The ‘Delay’ function gives time to the 
instrument to wait until the slowest part of the system is fully func-
tional before executing actions on the system (signal reading, relay 
activation, ...)

• the ‘

Tare

’ (‘

tArE

’) functions allow to activate an automatic tare of 

the reading each time the instrument is restarted. See section 1.10.9 
for more information on the ‘tare’ function.

1.10.8 Menu ‘On Power Up’

The ‘

Tare function

’ (‘

tArE

’) menu allows to operate the instrument 

for load-cell and weight applications. The tare function assigns the 
actual input signal value to a reading of ‘0’ Kilos, by adding an inter-
nal offset. It does not modify the scaling parameters of the instru-
ment.

The ‘Tare’ function can be applied  pressing button ‘LE’ (

3

) at the 

front keypad (see section 1.10.10)The offset value is eligible for visu-
alization through the ‘Fast access’ menu (see section 1.10.6).

To work with load-cell applications it is important to first adjust the 
scaling of the instrument to the load-cell used.

Application - A load cell with 2 mV/V parameter, powered at 10 Vdc, 
with  nominal  weight  of  500 Kilos,  together  with  a  signal  converter 
that provides 4/20 mA signals for a 0/20 mV signal from the load-cell. 
The scaling to configure at the meter is 4/20 mA = 0/500.0 Kilos. Once 
the meter is scaled, the tare function can be used to ‘tare’ the reading 
to 0 Kilos.

• at the ‘

Reset

’ (‘

rSt

’) menu select ‘

yES

’ to reset the tare offset value 

in memory.

1.10.9 Menu ‘Tare function’

Tare function

Reset

Key LE

Tare

Alarm unlock

No function

1.10.10 Menu ‘Key LE’

The ‘LE’ (

3

) key at the front of the instrument can be configured to 

activate several functions. Only one function can be assigned to the 
‘LE’ (

3

) key

• the ‘

No function

’ (‘

nonE

’)

 

value assigns no function.

• the ‘

Tare

’ (‘

Tare

’) value assigns a tare function (see section 1.10.9).

• the ‘

Alarm unlock

’ (‘

A.Lck

’)

 

value assigns the manual unlock of the 

alarms function, for instruments with the ‘

Locked alarms

’ (‘

A.Lck

’) 

function activated (see section 1.10.3)

Summary of Contents for M40-P

Page 1: ...za tion fast access to alarm setpoints tare function on power up function measure function configu rable reading brightness Universal AC and DC power Up to 3 optional modules for output and control re...

Page 2: ...mum reading password protection 5 brightness levels 1 1 How to order M40 P Model Power Option1 Others H Option2 Option3 R1 1 relay AO analog output RTU Modbus RTU S4 RS 485 S2 RS 232 empty H 85 265Vac...

Page 3: ...44 92 Panel cut out 16 8 75 Passive voltage signal 0 10Vdc 10Vdc Active voltage signal 0 10Vdc 10Vdc Common Signal Active current loop 4 20mA 20mA Passive current loop 4 20mA 20mA Vexc Signal Common S...

Page 4: ...n 2 1 7 Technical specifications Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20mA 0 05 FS 11Ohm 100mA permanent 10ppm C 25ppm C 0 10Vdc 0 05 FS 932KOhm 100V...

Page 5: ...Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the chang...

Page 6: ...instrument is being installed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the offset cor rection generate the minimum inp...

Page 7: ...ys due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set point value is...

Page 8: ...xed Reading remains in the following format XXXX0 the Memory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eli...

Page 9: ...the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu...

Page 10: ...n tArE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does...

Page 11: ...o access the configuration menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this fun...

Page 12: ...a description of each menu entry Scaling Input low Display low Input high Display high Alarm1 Setpoint Hysteresis Setpoint2 Active Alarm type Activation delay Deactivation delay Left zeros Steps Avera...

Page 13: ...of segments Value 2 to 20 Input0 Display0 Input1 Display1 On power up Delay Tare Seconds Option1 Configuration menu for the module installed at Opt 1 Option2 Configuration menu for the module install...

Page 14: ...tion for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock...

Page 15: ...unction Excitation voltage 20Vdc Password off Brightness 3 strument must be assured Do not expose the instrument to excess of humidity Maintain clean by using a humid rag and do NOT use abrasive produ...

Page 16: ...1 Opt 3 Power A B C A B C A B C Signal The AO module provides 1 analog output with 4 20mA or 0 10Vdc configurable output range Output current loop configurable as ac tive the instrument provides the e...

Page 17: ...s module for Series M of panel meters ASCII protocol with Master Slave architec ture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visib...

Page 18: ...ASCII characters codes 32 to 255 directly visible using hyperterminal or similar programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrum...

Page 19: ...FEMA ELECTR NICA Series M M40 P 19 T h i s p a g e b l a n k...

Page 20: ...the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front IP65 protection...

Page 21: ...holder 4 1 THM benchtop housing Adapter96x96mmfor96x48mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel meter...

Page 22: ...FEMA ELECTR NICA Series M M40 P 22 Notes...

Page 23: ...FEMA ELECTR NICA Series M M40 P 23 Notes...

Page 24: ...info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instr...

Reviews: