FEMA ELECTRÓNICA . Series M . M40-P

8

1.10 Configuration menu (cont.)

The instrument provides several functions to personalize the reading 
of the display values

• the ‘

Fixed Digits

’ (‘

FIX.d

’) allows to fix each digit to a fixed value. 

As an example, fix the least significant digit to a ‘0’ in order to block 
noisy  fluctuations.  To  fix  a  digit,  all  digits  to  its  right  must  be  also 
fixed. Value ‘-’ means that the digit is not fixed.

• the ‘

Average filter

’ (‘

AVr

’) function allows to reduce reading oscil-

lations due to noisy signals. It applies a recursive filter on the reading 
value. To activate the average filter set ‘

AVr

’ to ‘

on

’ and assign the fil-

ter strength between ‘0.0’ and ‘99.9’. Higher values activate stronger 
filter. Stronger filters slow down the reading changes.

•  the  ‘

Steps

’  (‘

StEP

’)  function  allows  to  define  minimum  reading 

steps, which will be done in steps of 1, 2, 5, 10, 20 or 50 counts.

Example - selecting a step of 20 configures the reading to change in 
steps of 20 counts (‘1420’, ‘1440’, ‘1460’, ...).

• the ‘

Left Zero

’ (‘

LZEr

’) function lights all zeros to the left.

• the ‘

Dummy zero

’ (‘

rZEr

’) function lights an additional right zero. 

This zero is fixed. Reading remains in the following format : ‘XXXX0’.

• the ‘

Memory of maximum

’ (‘

MAX

’) function displays the maximum 

reading value stored in memory. It also provides a way to reset the 
value. This parameter is eligible for configuration through the ‘Fast 
access
’ menu (see section 1.10.6).

 • the ‘

Memory of minimum

’ (‘

MAX

’) function displays the minimum 

reading value stored in memory. It also provides a way to reset the 
value. This parameter is eligible for configuration through the ‘Fast 
access
’ menu (see section 1.10.6).

• the ‘

Peak & hold

’ (‘

P.hLd

’) function visualizes and hold the maxi-

mum reading. For test-break applications, where the meter always 
increases its value until the unit under test breaks and the signal falls 
down. The meter maintains the maximum reading before the signal 
fell down.

To free the ‘hold’ reading, press any of the front key pad or wait the 
time configured at the ‘

time

’ parameter.

   Time 0  

hold disabled (Off)

   Time 1 a 3999  seconds waiting

   Time 4000 

infinite hold

While ‘hold’ is active, the instrument alarms are still associated to 
the input signal, therefore still providing control to disconnect the 
application once the test has finished.

1.10.4 Display filters

Left zeros

Steps

Average filter

0.0 to 99.9

Display

Fixed digits

Fix digits

Memory of 

maximum

Memory of 

minimum

‘Dummy’ zero

Peak & Hold

Time (Sec.)

Summary of Contents for M40-P

Page 1: ...za tion fast access to alarm setpoints tare function on power up function measure function configu rable reading brightness Universal AC and DC power Up to 3 optional modules for output and control re...

Page 2: ...mum reading password protection 5 brightness levels 1 1 How to order M40 P Model Power Option1 Others H Option2 Option3 R1 1 relay AO analog output RTU Modbus RTU S4 RS 485 S2 RS 232 empty H 85 265Vac...

Page 3: ...44 92 Panel cut out 16 8 75 Passive voltage signal 0 10Vdc 10Vdc Active voltage signal 0 10Vdc 10Vdc Common Signal Active current loop 4 20mA 20mA Passive current loop 4 20mA 20mA Vexc Signal Common S...

Page 4: ...n 2 1 7 Technical specifications Ranges Accuracy Zin Max signal overload Offset drift span drift includes offset drift 4 20mA 0 05 FS 11Ohm 100mA permanent 10ppm C 25ppm C 0 10Vdc 0 05 FS 932KOhm 100V...

Page 5: ...Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the chang...

Page 6: ...instrument is being installed on the field providing a fast and easy way to compensate offset signals To operate the Field correction F cor function for the offset cor rection generate the minimum inp...

Page 7: ...ys due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set point value is...

Page 8: ...xed Reading remains in the following format XXXX0 the Memory of maximum MAX function displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eli...

Page 9: ...the front of the instrument gives access to a list of functions configurable by the operator See section 1 8 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu...

Page 10: ...n tArE menu allows to operate the instrument for load cell and weight applications The tare function assigns the actual input signal value to a reading of 0 Kilos by adding an inter nal offset It does...

Page 11: ...o access the configuration menu key SQ The fast access menu is not password pro tected 1 10 12 Function Password At the Brightness LIGh menu select the light intensity for the front leds With this fun...

Page 12: ...a description of each menu entry Scaling Input low Display low Input high Display high Alarm1 Setpoint Hysteresis Setpoint2 Active Alarm type Activation delay Deactivation delay Left zeros Steps Avera...

Page 13: ...of segments Value 2 to 20 Input0 Display0 Input1 Display1 On power up Delay Tare Seconds Option1 Configuration menu for the module installed at Opt 1 Option2 Configuration menu for the module install...

Page 14: ...tion for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock...

Page 15: ...unction Excitation voltage 20Vdc Password off Brightness 3 strument must be assured Do not expose the instrument to excess of humidity Maintain clean by using a humid rag and do NOT use abrasive produ...

Page 16: ...1 Opt 3 Power A B C A B C A B C Signal The AO module provides 1 analog output with 4 20mA or 0 10Vdc configurable output range Output current loop configurable as ac tive the instrument provides the e...

Page 17: ...s module for Series M of panel meters ASCII protocol with Master Slave architec ture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visib...

Page 18: ...ASCII characters codes 32 to 255 directly visible using hyperterminal or similar programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrum...

Page 19: ...FEMA ELECTR NICA Series M M40 P 19 T h i s p a g e b l a n k...

Page 20: ...the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front IP65 protection...

Page 21: ...holder 4 1 THM benchtop housing Adapter96x96mmfor96x48mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel meter...

Page 22: ...FEMA ELECTR NICA Series M M40 P 22 Notes...

Page 23: ...FEMA ELECTR NICA Series M M40 P 23 Notes...

Page 24: ...info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instr...

Reviews: