VEK M2E-2

Operating instructions

10

03/06

FEIG ELECTRONIC GmbH

3.4. Diagnostic plug

For an optimum adjustment of the detector, please connect diagnostic device VEK FG2.
Diagnostic device VEK FG2 indicates all relevant data for initiation and service. It provides
information on the loop/detector system, so that we may then optimise the adjustments as
well as localise the cause for malfunctions. For further information, please refer to the
operating instructions of diagnostic device VEK FG2.

Warning

: please only plug in  the diagnostic cable when the detector is idle !

3.5. LED-display

The green LED indicates that the detector channel is ready for operation and sends out
important hints regarding initiation of the detector (failure, adjustment, frequency output) via
flash signals. The red LED indicates activation of the relay output in dependence on the
availability condition of the loop.

Green LED

Loop control

Red LED

Loop condition

Detector condition

Off

off

Reset or
Lack of supply voltage

Flashes

off

Adjustment

flashes after adjustment

-

Loop frequency output

On

off

Detector ready,
loop free

On

on

Detector ready,
loop occupied

Off

on

Loop failure

Pulsates

off

Loop free,
after temporary failure

Pulsates

on

Loop occupied,
after temporary failure

3.6.  Loop frequency output

After the detector has been readjusted, the loop frequency is indicated by flash signals of the
green LED. Approx. 1s after the successful readjustment,  the output starts with the  10kHz-
position of the frequency value. The green LED of the detector channel will flash 1 time per
10kHz loop frequency. After a 1s break, the 1kHz-position will be indicated in the same way.
In case that the units digit has the valency '0', 10 flash signals will be emitted. The duration
of the flash signals of the 1kHz-position is a little shorter than the one of the  10kHz- position.

Example of a 57kHz loop frequency:

5x 10kHz

7x 1kHz

entspricht: 57kHz

1s

Zehner

Einer

If both channels are adjusted at the same time, the frequency of channel 1 is indicated
before channel 2.

Summary of Contents for VEK M2E-2-B

Page 1: ...Operating instructions Traffic detector VEK M2E 2 FEIG ELECTRONIC GmbH Lange Stra e 4 35781 Weilburg Lahn...

Page 2: ...fforts errors may not be completely avoided we are always grateful for your useful tips The installation instructions given in this manual are based on advantageous boundary conditions FEIG ELECTRONIC...

Page 3: ...justment Reset 8 3 Outputs and LED display 9 3 1 Working principle of the relays 9 3 2 Contact conditions of the relays 9 3 3 Loop failure 9 3 4 Diagnostic plug 10 3 5 LED display 10 3 6 Output of loo...

Page 4: ...ontacts as outputs Relay triggering may be converted from static current to operating current principle by switch operation loop breach or loop closing message via LED signal indication of occurred an...

Page 5: ...3 0 04 f f OFF ON OFF ON 4 high 0 01 f f ON ON ON ON 2 2 Frequency The detector s working frequency may be selected in two common levels to be used for both channels The admissible frequency range is...

Page 6: ...will be supported in dependence on DIP switch 8 The directional pulse is mainly used in counting devices whereas the permanent direction signal is used for requests in gate and barrier control units I...

Page 7: ...ay 1 directional pulse Relays 1 permanent direction signal on 1 2 Relay 1 permanent direction signal remains 1 2 Relay 1 permanent direction signal remains 1 2 Relay 1 permanent direction signal off 1...

Page 8: ...e loop is occupied 2 5 Readjustment Reset The detector automatically carries out a loop frequency adjustment as soon as the power supply is switched on In case of a short term voltage loss 0 3s no rea...

Page 9: ...conditions of the relays For device categories please refer to chapter 8 The following chart illustrates the relay s condition depending on the selected relay working principle and the detector condi...

Page 10: ...Red LED Loop condition Detector condition Off off Reset or Lack of supply voltage Flashes off Adjustment flashes after adjustment Loop frequency output On off Detector ready loop free On on Detector r...

Page 11: ...y line 250 m Loop resistance 20 Ohm incl supply line Relay Break contact make contact for type E 250V AC 4A 1000 VA resistive load AC Minimum contact load 0 25mW 10mV 1mA Operating static current prin...

Page 12: ...r Arbeits Ruhestromprinzip Kanal 1 Schalter Arbeits Ruhestromprinzip Kanal 2 Service Reset 1 2 2 1 F 1 2 H 5min VEK M2E 1 2 3 4 5 6 7 8 Contact assignment 11 pole connector plug see also device catego...

Page 13: ...tor VEK M2E The perfect functioning of detector and relay outputs may be checked by seizing the loops After having passed the test successfully you may switch over to directional detection resp pulse...

Page 14: ...verriegelung aus ein Dauer Impulssignal Sperrzeit 10s 5s Schleifenzustand Schleifenkontrolle Kanal 1 Schleifenzustand Schleifenkontrolle Kanal 2 Schalter Arbeits Ruhestromprinzip Kanal 1 Schalter Arbe...

Page 15: ...2 D The time out is selected in the output mode relay locking with the help of DIP switch 8 In case of presence detection it can be used to choose the signal output for channel 2 DIP switch Output fun...

Page 16: ...8 7 9 8 7 9 Voltage off 8 7 9 8 7 9 In case of presence detection an inverted signal is emitted for this detector condition at channel 1 Some important hints regarding type VEK M2E 2 E No indication...

Page 17: ...VDE 0550 0551 VDE 0700 VDE 0711 VDE 0860 VDE 0105 as well as the rules for the prevention of accidents and fire VBG4 If an operation display goes out this is not a proof that the appliance is disconn...

Page 18: ...VEK M2E 2 Operating instructions 18 03 06 FEIG ELECTRONIC GmbH Notes...

Reviews: