45
Operations
Description, Specifications, Installation, and Operation Manual
Federal Signal
www.fedsig.com
POT Settings
Table 27 POT Settings on the Control Board
R69
Output level for 10 V/25 V and 8 Ω, 0.7 W Audio outputs,
(Default = Turn clockwise 20 turns or all of the way up.)
R103
Digital Voice Gain,
(Default = Turn clockwise 20 turns or all of the way up.)
Table 28 POT Settings on the Amplifier Board
VR1
Volume Control,
(Default = Turn clockwise 20 turns or all of the way up.)
Software Tests
Table 29 Software Tests
Power-up System Test
Function of microSD card.
Card is present and can be read from.
Quiet Test
25 V output at least 20 V
rms
.
Audio channel status.
Performed on command and polled for results.
Sounding Functions/P.A./
Digital Voice
TC1 Contact loop back from TC1 Relay outputs K4, K3, K2,
and K1 (JP18) to fire panel (TC2) and from fire panel to TC1
inputs (JP14).
TC1 Audio loop back from (JP10) to fire panel to (JP9).
Performed during activations and polled for results.
Low Battery
Battery voltage less than 11.3 V
Auto reports.
AC Power Fail
AC voltage less than 90 V.
If in 240 Vac mode, 180 V.
Auto reports.
Charger Fail
Charge voltage drops below 8.7 V.
Auto reports.
Configuring
For information on configuring, see the Commander Software Manual and the Informer-IP
Setup, Program, and User Manual.
To configure the UVRI-B, use the web browser interface. This method requires a
username and password for security.
Default Username and Password
The default username is the following:
config
The default password is the following:
UVRI-B
The config user has security rights to change the config user password.
NOTE: Usernames and passwords are case sensitive.