CONVERSIONS

High Altitude

In the United States, the modifications for high altitude are
based on a 4 percent reduction of input capacity for every

the impact of altitude for selected elevations. Ratings
shown apply to the highest elevation in range. 

Consult with local fuel suppliers or authorities to determine
local regulations or customs.

In Canada, the furnace may be converted for high altitude
(2000 - 4500 feet) by changing the burner orifices. Use Kit
No. 30552. The kit contains both natural gas and L.P. gas

Natural to L.P. Gas

This series furnace is manufactured as a natural gas (sea
level) appliance. It may be converted to L.P. gas with the use

L.P. to Natural Gas

Although the furnace is manufactured initially as a natural
gas appliance, if after an L.P. Gas conversion it becomes
necessary to convert back to natural gas, and if the original

WARNING

NEVER PURGE A GAS LINE INTO THE COMBUSTION
CHAMBER.

NEVER USE A MATCH, TAPER, CIGARETTE LIGHTER,
FLAME OR ANY OTHER IGNITION SOURCE TO CHECK
FOR LEAKS IN A GAS LINE.

FAILURE TO ADHERE TO THIS WARNING CAN CAUSE A
FIRE OR EXPLOSION RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY, OR LOSS OF LIFE.

Gas piping that has not been pressure tested, from the
manual shutoff valve to the furnace gas valve for example,
should be leak tested using an electronic combustible gas
detector, a commercially prepared leak detector such as Gas
Leak Detector® or Search®, or other locally approved
method. A leak detector solution can be prepared by mixing
a small quantity of dish detergent with water and daubing
it onto the gas piping and connections.

Conversion Steps

To convert from sea level to high altitude, from natural gas
to L.P. gas, or from L.P. gas to natural gas, follow these
steps:
Turn off gas supply to the furnace if applicable.
1.  Shut off electrical power to the furnace if applicable.
2.  Remove the upper front door to expose the gas train and

burner assembly.

3.  Unfasten the ground joint union between the gas valve

and gas supply piping if applicable.

4. Unfasten the burner manifold pipe from the burner

assembly. It is held in place by 2 screws on either end of
the manifold pipe.

5.  Remove the existing orifices with a 7/16 inch socket, box

or open-end wrench. Install the replacement orifices. The
orifice spuds are brass, and do not normally require pipe
dope. A light grease may be used to lubricate the
threads. The orifice spuds have tapered threads; do not
over-tighten them.
If completing a fuel conversion, remove the protective
screw cap from the gas valve regulator adjustment.
Remove the regulator adjustment screw by turning it
counterclockwise. Remove the existing regulator springs.

6.  Install the new regulator springs. 

GAS VALVE

Outlet Pressure
Post Set Screw

Regulator
Vent

Inlet Pressure
Post Set Screw

On/Off Switch

Regulator
Adjustment

3 Pin Connector

Regulator
Adjustment

If converting the gas valve, the regulator spring is

tapered. The tapered end (small end) is inserted back
into the gas valve regulator adjustment cavity.

NOTE

7. Reinstall the adjustment screw. Give it 3 full clockwise

turns initially. Do not reinstall the protective screw cap yet.

8.  Reinstall the burner manifold pipe assembly following

steps 4, 5, and 6 in reverse order.

29

of Kit No.194301570001(contact manufacturer for availability). 
The kit contains the orifices needed for all models, the 
regulator spring for the gas valve, and a label to affix adjacent 
to the appliance rating plate to alert subsequent 
service technicians of the conversion.

parts are unavailable, Kit No. 194301580001 may be 
purchased. It is similar in nature and content to the L.P. Gas 

 conversion kit.

1000 feet above sea level. Table on page 30 illustrates

orifices; see Table on page 30.

Summary of Contents for FV95A054

Page 1: ...erence USER S INSTRUCTION GUIDE INSTALLATION OPERATION AND MAINTENANCE MANUAL Model Serial Number Date of Purchase For future reference write down the model serial number and date of purchase Use thes...

Page 2: ...ng Piping Length 18 Pipe Using A Concentric Venting Kit 19 Exhaust Vent 20 Exhaust Vent 21 Non Direct Vent Furnace Installations 22 Direct Vent Piping Termination 17 CONDENSATE DRAINS 25 Drain Hose In...

Page 3: ...he furnace Furnace for heating the home located in the attached garage for example 8 A gas fired furnace for installation in a residential garage must be installed so that the burners and ignitor are...

Page 4: ...ING BIRTH DEFECTS AND OTHER REPRODUCTIVE HARM UL AND CUL RECOGNIZED CO DETECTORS ARE RECOMMENDED FOR ALL BUILDINGS EQUIPPED WITH FOSSIL FUEL BURNING APPLIANCES ALL CO DETECTORS SHOULD BE INSTALLED IN...

Page 5: ...wall horizontal vented gas fueled equipment It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon mo...

Page 6: ...be required 4 Existing ductwork should be assessed for its air handling capabilities For residential applications the recommended air velocity of a supply air trunk duct is 700 feet per minute fpm an...

Page 7: ...pounds Polyurethane and similar derivatives fumes Printer s inks paint removers furniture strippers varnishes varsol toluene etc Water softener salts and chemicals LOCATION of UNIT General 1 The furna...

Page 8: ...ER COMBUSTIBLE MATERIAL EXCEPT WOOD INSTALLATION ON COMBUSTIBLE MATERIAL CAN RESULT IN FIRE CAUSING PROPERTY DAMAGE PERSONAL INJURY OR DEATH DANGER COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINS...

Page 9: ...revent entraining combustion gases from an adjacent fuel burning appliance or entraining combustion air for this furnace 5 Ensure that there is adequate space and accessibility for the air filter 6 If...

Page 10: ...ce cabinet to prevent twisting or sagging General Considerations When choosing an installation position the installer must consider the following connections Combustion air intake Exhaust vent Gas pip...

Page 11: ...pling bands 12 Tighten the vent clamp and secure in place using the screws provided FIGURE A RIGHT INDUCER POSITION FIGURE B LEFT INDUCER POSITION SUGGESTED METHOD FOR SUSPENDING HORIZONTAL FURNACE AL...

Page 12: ...ducer drain connector will angle toward the front of cabinet with the second nested inside directed towards the top panel The 108 000 BTUH will require an extension between the inducer and the first e...

Page 13: ...of the cabinet WARNING WHEN INSTALLED IN THE DOWNFLOW POSITION ON A COMBUSTIBLE FLOOR SUBBASE KIT 30476 IS REQUIRED FAILURE TO INSTALL SUBBASE KIT COULD RESULT IN FIRE DEATH OR SERIOUS INJURY The open...

Page 14: ...w that is not provided If exhaust vent exits the left side panel the pipe can be routed straight outside the cabinet The pipe exiting the cabinet in any installation should be long enough to install t...

Page 15: ...area from which the combustion and ventilation air will be drawn negative pressure could be a problem if natural infiltration from the outdoors does not match the rate at which air is exhausted IMPOR...

Page 16: ...ng salons Antistatic fabric softeners used in clothes dryers Carbon tetrachloride Chlorinated cleaners and waxes Chlorine and bromine based swimming pool chemicals Deicing salts or chemicals e g rock...

Page 17: ...ED TO THE FURNACE WITH SHEET METAL SCREWS TAPE THE SHEET METAL SEAMS IN THE VICINITY OF THE FURNACE WITH DUCT TAPE OR SIMILAR MATERIAL WHEN THE FURNACE IS MOUNTED ON A PLATFORM WITH RETURN AIR THROUGH...

Page 18: ...OLLOW ALL VENTING GUIDELINES MAY RESULT IN ERRATIC FURNACE OPERATION FREEZE UP OF THE VENTILATION AIR PIPING OR SOOTING OF THE FURNACE DANGER SOLVENT CEMENTS AND PRIMERS ARE HIGHLY FLAM MABLE PROVIDE...

Page 19: ...r location or installa tion can cause structural or exterior finish damage to the building Caulk all cracks seams or joints within a 6 foot radius of the termination Direct Vent Piping Termination Gen...

Page 20: ...overhangs is a minimum of 1 foot vertically for each foot horizontally up to 6 feet As a protection against freezing do not expose a 3 x 2 reducing coupling to outdoor ambient temperatures Any adjacen...

Page 21: ...ntric vent terminal there must be a minimum of 12 clearance to grade or antici pated snow level There are no means available to raise the terminal externally If planning to use this terminal kit see T...

Page 22: ...o use one the screen may actually encourage the formation of rime ice which could cause the intake to become blocked in certain weather conditions Horizontal Exhaust Vent Termination Horizontal vents...

Page 23: ...quired if venting vertically through a roof The end of the exhaust pipe must be 12 higher than the entrance of the combustion air intake terminal The exhaust pipe extending through the roof must exten...

Page 24: ...NT IN CANADA In addition to the general guidelines in Canada the non direct vent exhaust shall not terminate Directly above a paved sidewalk or paved driveway which is located between two single famil...

Page 25: ...appliances 10 000 Btuh 4 ft 121 cm below or to side of supply inlet to building or the 3 kW 12 in 30 cm for appliances opening 1 ft 30 cm above combustion air inlet to any other 10 000 Btuh 3 kW and...

Page 26: ...air 6 in 15 cm for appliances 10 000 Btuh 6 in 15 cm for appliances 10 000 Btuh supply inlet to building or the 3 kW 12 in 30 cm for appliances 3 kW 9 in 23 cm for appliances combustion air inlet to...

Page 27: ...clamp to approximately 1 8 from the end of the hose 5 Fasten each drain hose to its inlet by tightening the hose clamps 6 Cut each drain hose near the blower division panel at the point where kinking...

Page 28: ...HORIZONTAL FLOW RIGHT CONDENSATE TRAP CONDENSATE TRAP HORIZONTAL FLOW LEFT UPFLOW DOWNFLOW CONDENSATE CONDENSATE TRAP TRAP FIGURE 11 FIGURE 12 FIGURE 13 FIGURE 14 26...

Page 29: ...Secure the condensate drain trap to the side of the fur nace using the mounting holes that were just drilled 5 Install one rubber grommet provided into each of the drain holes and then insert the 90 d...

Page 30: ...VALVE AND GAS VALVE DURING ANY PRESSURE TESTING THAT EXCEEDS 1 2 P S I G 3 45 KPA w c 12 inches w c is recommended These pressures must be maintained while all other gas fired appliances are operatin...

Page 31: ...o the furnace if applicable 1 Shut off electrical power to the furnace if applicable 2 Remove the upper front door to expose the gas train and burner assembly 3 Unfasten the ground joint union between...

Page 32: ...600 1 95mm 1 20mm 2000 3000 79200 75240 51480 48906 1 90mm 1 15mm 90 000 3000 4000 75600 71820 49140 46683 1 90mm 1 10mm 5 4000 5000 72000 68400 46800 44460 1 85mm 1 10mm 5000 6000 68400 64980 44460 4...

Page 33: ...manifold first examine the gas piping system to ensure that it is correctly sized Pipe sizing is specified in ANSI Z223 1 NFPA 54 in the U S or the B148 Natural Gas and Propane Installation Code in Ca...

Page 34: ...are rated 120 VAC 60 Hz 1 phase The amperage rating is indicated on the furnace rating plate Each furnace requires a dedicated overcurrent device either a circuit breaker or a Type D time delay fuse...

Page 35: ...the main burners directly See the lighting instructions on the furnace To Start The Furnace 1 Remove the burner compartment access door 2 Shut off the electrical power to the furnace and set the room...

Page 36: ...rops causing the room thermostat heating contacts to close 2 If pressure switch contacts are closed and have failed to open since the last cycle all subsequent steps will fail to occur 3 The induced b...

Page 37: ...e determine the air temperature rise of the furnace Insert a duct thermometer in the supply air duct The ther mometer should be placed as close as practical to the fur nace but out of the line of sigh...

Page 38: ...ded that the heating airflow be set for the Nominal Plus setting when the furnace is matched for this cooling capacity Furnace is set at the factory for maximum cooling capacity and DIP switches must...

Page 39: ...ommended that the Plus temperature rise is between 35 and 65 degrees F Heating Make adjustments to the controller with the electrical power off WARNING front blower shroud from furnace How To Remove T...

Page 40: ...OR LOSS OF LIFE MAINTENANCE This is a critical connection Small amounts of corrosion can significantly increase the internal resistance of the connection A relatively small increase in resistance can...

Page 41: ...ION WARNING heat and make a retrial for high every 5 or 10 minutes switch does not pull in the controller will continue in low finished and during the trial for ignition the high pressure If there is...

Page 42: ......

Page 43: ...t trips 1 hour lockout Too many low pressure switch trips after ignition 1 hour lockout 1 hour lockout Reset by cycling power or thermostat CHECK and REPAIR 1 Replace Integrated Furnace Control 2 Roll...

Page 44: ...ignition period If main flame is not sensed during trial for ignition system will shut off HSI element and main gas flow then go through another purge period and initiate another ignition trial A tota...

Page 45: ...5 7 0 187 67 1 21752 8720 7 67 57 7 7 5 0 187 6 2 217 18286 2 7 23 5 7 21 7 7 5 0 187 6 2 217 18286 2 7 23 5 7 21 25 0 187 67 1 25 6 1 67 7 50267 7 803 5 1 6 72 6 7 72 0 187 725 8 7 6 77 1 8720 7 67...

Page 46: ...E DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING LEAVE THE BUILDING IMMEDIATELY IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A PHONE OUTSIDE THE BUILDING FOLLOW THE GAS SUPPLIER S...

Page 47: ...must be in place during normal furnace operation Attempting to operate the furnace with missing doors or panels could lead to the creation of carbon monoxide gas 4 If the furnace is installed in a con...

Page 48: ...valve Ensure that the Gas Valve Control is in the ON position see Figure 3 at right 9 Replace the burner access door ensuring that it is properly in place 10 Restore the electric power to the furnace...

Page 49: ...2 Pull the filter out the front 3 Replace with a fresh filter and reconnect power to the furnace The filter will have an arrow indicating proper airflow direction DO NOT OPERATE YOUR FURNACE OR AIR C...

Page 50: ...nored The furnace achieves its mid efficiency in two general areas First there is no wasteful standing pilot The furnace consumes no gas in between cycles Secondly the furnace is designed to allow ver...

Reviews: