C5
PREPARATION OF PIPING
Pipe Length, Elevation and refrigerant charge
Cutting The Pipe And The Cables.
• Measure the distance between the
indoor and the outdoor units.
• Cut the pipe length about 10% more
than the measured distance.
• Cut the electrical cable with about 2
metres more than the measured dis-
tance.
• Each outdoor unit comes with a
refrigerant charge that is sufficient for
use with interconnecting tubing up to
7.5 metres.
• If the required interconnecting tube
exceeds 5 metres, for each additional
metre, add the amount of refrigerant
according to the table as shown below.
Max. Piping
Length per
Indoor Unit
Max. Elevation
per Indoor Unit
• The recommended maximum allowable
tubing length between indoor and
outdoor is 15 metres.
• The recommended maximum allowable
elevation between indoor and outdoor is
5 metres.
Liquid Pipe
Size
1/4”
Additional
Refrigerant
3/8”
21 g/m
57 g/m
Summary of Contents for E1FC418N6G
Page 1: ...ISSUED ON 1 APRIL 2003 FEDDERS LARGE SPLIT UNIT R407C SERVICE MANUAL ...
Page 3: ...SECTION A SPECIFICATIONS ...
Page 5: ...SECTION B PARTS LIST AND EXPLODED VIEWS ...
Page 10: ......
Page 11: ......
Page 12: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ...SECTION C INSTALLATION ...
Page 21: ...SPLIT TYPE AIR CONDITIONER INSTALLATION MANUAL For 18 000 24 000 Btu C1 ...
Page 39: ...SECTION D TROUBLE SHOOTING ...
Page 40: ...D1 ...
Page 42: ...SECTION E WIRING DIAGRAM ...
Page 43: ...E1 ...
Page 44: ...E2 ...
Page 45: ...E3 ...
Page 46: ...E4 ...
Page 47: ...SECTION F TECHNICAL DATA ...
Page 68: ...F21 ...
Page 69: ...F22 ...
Page 70: ...F23 ...
Page 71: ...F24 ...
Page 72: ...F25 ...
Page 73: ...F26 ...
Page 74: ...F27 ...
Page 75: ...F28 ...