F17
6.
Defrosting in HEAT mode
(applicable on Heat Pump Unit only)
a) Defrost starting conditions
When all conditions of i) ~ iii) are satisfied, defrosting operation starts.
i) The indoor coil thermistor read
≤
42
°
C
ii) The outdoor coil thermistor reads -4
°
C or below.
iii) The difference between the Indoor-coil Thermistor and Indoor air thermistor
≤
22
°
C.
Further information on defrost interval is described in (3).
b) Defrost termination conditions
When the condition of i) or iv) is satisfied, the defrosting operation stops.
iv) The defrost thermistor reads above 5
°
C.
v) The defrost time exceeds 8 minutes.
c) Defrost interval
The defrost interval time is determined as follows.
There should be a 30 minutes intervals between defrost cycle. During this intervals, No
detection of defrost is required. Detection of defrost will resume after the 30 minutes
intervals , upon condition meet, enter defrost cycle, otherwise continue detection for
defrost.
Summary of Contents for E1FC418N6G
Page 1: ...ISSUED ON 1 APRIL 2003 FEDDERS LARGE SPLIT UNIT R407C SERVICE MANUAL ...
Page 3: ...SECTION A SPECIFICATIONS ...
Page 5: ...SECTION B PARTS LIST AND EXPLODED VIEWS ...
Page 10: ......
Page 11: ......
Page 12: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ...SECTION C INSTALLATION ...
Page 21: ...SPLIT TYPE AIR CONDITIONER INSTALLATION MANUAL For 18 000 24 000 Btu C1 ...
Page 39: ...SECTION D TROUBLE SHOOTING ...
Page 40: ...D1 ...
Page 42: ...SECTION E WIRING DIAGRAM ...
Page 43: ...E1 ...
Page 44: ...E2 ...
Page 45: ...E3 ...
Page 46: ...E4 ...
Page 47: ...SECTION F TECHNICAL DATA ...
Page 68: ...F21 ...
Page 69: ...F22 ...
Page 70: ...F23 ...
Page 71: ...F24 ...
Page 72: ...F25 ...
Page 73: ...F26 ...
Page 74: ...F27 ...
Page 75: ...F28 ...