3.2 Connecting the cable
- 13 -
While the UPS is operating:
“Abnormalities of input voltage” is detected and the battery operation is performed. If the
UPS is connected to an input power supply which gets out of this range frequently, by
repeating the charge and discharge of the battery, the battery will be in an empty state
or will become the cause of deterioration.
Note: The input frequency is automatically selected according to the region where the
UPS will be used.
2. Select the size and length (one way) of input/output cables with reference to
the table below.
Product type
Cable type
Wire size
Length
14 mm
2
10 m or less
Input
100 V
22 mm
2
20 m or less
14 mm
2
10 m or less
100 V
22 mm
2
20 m or less
M-UPS050AD1S
Output
200 V
14 mm
2
20 m or less
Input
200 V
14 mm
2
20 m or less
14 mm
2
10 m or less
100 V
22 mm
2
20 m or less
M-UPS050AD2S
Output
200 V
14 mm
2
20 m or less
Input
100 V
38 mm
2
20 m or less
22 mm
2
10 m or less
100 V
38 mm
2
20 m or less
M-UPS075AD1S
Output
200 V
22 mm
2
20 m or less
Input
200 V
22 mm
2
20 m or less
22 mm
2
10 m or less
100 V
38 mm
2
20 m or less
M-UPS075AD2S
Output
200 V
22 mm
2
20 m or less
Input
100 V
60 mm
2
20 m or less
38 mm
2
10 m or less
100 V
60 mm
2
20 m or less
M-UPS100AD1S
Output
200 V
38 mm
2
20 m or less
Input
200 V
38 mm
2
20 m or less
38 mm
2
10 m or less
100 V
60 mm
2
20 m or less
M-UPS100AD2S
Output
200 V
38 mm
2
20 m or less