background image

 

 

Electrical connection 

 

 

Installation instructions 

21 

 

5.4 

Light and Fan 

Light and fan 

 

 

ATTENTION! 
Light dimming: 

–  At the dimmable outputs of light, only 230V consumer which are suita-

ble for 

phase cut off

, will be permitted.  

Fan control: 

–  At the dimmable outputs of fan, only 230V consumer which are suita-

ble for 

phase cut on

, will be permitted.  

 

ATTENTION 

 

 

DANGER! 
Danger to life due to electric potential! 

Before starting any maintenance jobs, the control unit must be sepa-
rated from the mains at all poles! 

 

 

 

ATTENTION! 
Note ESD protection! 

Do not touch on electrical parts because of ESD protection.  
Take appropriate protections. Touch a grounded piece of metal as a 
minimum protection. 

 

 

You can deactivate the light and fan control using jumpers: 

 NoLu: Fan control (Terminal 1) activated. 
 NoLu: Fan control deactivated, only On/Off. 

 

 NoLi: Dimming of light (Terminal 3) activated. 
 NoLi: Dimming of light deactivated, only On/Off. 

 

The jumpers are located only on one side of the pins (as in the picture above) or they 
are in the by-pack kit of the control unit. 

 

Deactivate user menus for dimming with dip switches: 

 
DIP 4=ON, Menu for Fan control deactivated. 
DIP 5=ON, Menu for Light dimming deactivated. 

 

If the light dimming no longer works due to a defect in the lamp, the FET T1, T2 and 
possibly the fuse Si2 have been destroyed. When replacing the FET, place the new 
component back on the base in the correct position (note the metal flag). Make sure that 
all connections are correctly inserted into the base and press in carefully. 

If the fan control has been destroyed due to a defect, the same applies to triac “Tri1”. 

 

Summary of Contents for FNT2000 Series

Page 1: ...the control unit so that they are always accessible Technical changes and errors excepted illustration similar Serie FNTxx00 Installation instructions Sauna control Series FNT2000 FNT2200 Series FNT3...

Page 2: ...ation of sauna control unit 12 4 2 Installing the temperature and humidity sensor 13 4 2 1 Temperature sensor 13 4 2 2 Humidity Sensor 14 4 2 3 Installation and electrical connection 15 5 Electrical c...

Page 3: ...property damage DANGER indicates an imminent dangerous situation which could lead to loss of life or cause serious injuries if not avoided WARNING indicates a possible dangerous situation which can be...

Page 4: ...The sensor of the thermostat must be installed in such a way that it is not affected by the incoming cool air 1 2 Intended use This control Unit is exclusively meant for operation and control of sauna...

Page 5: ...l Due to their technical training knowledge and experience as well as the knowledge of the relevant regulations these persons are in a position to carry out the tasks as signed to them and to identify...

Page 6: ...ains before carrying out any work on it switch off the fuse in the distribution box and secure against restarting Check for zero potential The control device should be disconnected from the mains befo...

Page 7: ...C sensor short circuit at ca 25 C STB interruption at ca 140 C accordingly to DIN EN 60335 2 53 section 19 Humidity Sensor connecta ble No Yes Timer Yes Yes Week Timer No No Light dimmable trailing ed...

Page 8: ...er of leads H07RN FG2 5 heavy rubber hose 2 5 mm2 Power supply cables must be polychloroprene coated and should not be lighter than heavy polychloroprene coated flexible cables 230 400V cables for sup...

Page 9: ...ching capacity consumer 1 Only in controls with the bathing option Sauna with humidity 2 Only in controls with the bathing option Infrared NOTE FASEL additionally offers a extension power unit for loa...

Page 10: ...Technical Data 10 Installation instructions Figure 1 Cabling while installing the sauna control device not directly on the outer wall of the cabin...

Page 11: ...onsignment should not be accepted or accepted conditionally only Note down the scope of damage on the transport documents or on the delivery note of the transporter Initiate claim NOTE Claim damages a...

Page 12: ...al as a minimum protection 4 1 Installation of sauna control unit Installation The sauna control device should be installed sideways above and below at a distance of at least 5 cm from the walls or ot...

Page 13: ...s on the control This could be due to the following reasons Depending on the cabin the temperature differences from the floor to the ceiling or from the oven to the opposite wall can be up to 60 K and...

Page 14: ...pposite side of the oven S2 II same side offset to the Underbench oven U1 or adjacent wall This position for the sensor is only a recommendation for standard cabins Attention The system installer has...

Page 15: ...e bench sen sor 4 2 3 Installation and electrical connection 1 Lead the heat resistant signal cable for the sensor through the cable aper ture provided and through the bore of the securing plate 2 Pla...

Page 16: ...eck for zero potential The control device should be disconnected from the mains before opening the casing In case of damage to the insulation switch off the power supply im mediately and carry out the...

Page 17: ...you connect inductors like e g a magnet valve relay transformer throttle or engine the interferences of the consumers must be suppressed 5 2 Connecting the control device consumers and sensor 1 Conne...

Page 18: ...oven sensor for temperature and bench sensor for temperature Figure 5 Connection of cover guard for sauna oven detailed installation and connec tion Instructions refer the documentation provided by th...

Page 19: ...ical connection Installation instructions 19 Electrical circuit diagrams for sensor Figure 7 Connection of bench sensor for humidity Figure 8 Connection of combined bench sensor for temperature and hu...

Page 20: ...Electrical connection 20 Installation instructions 5 3 Electrical circuit diagram...

Page 21: ...the light and fan control using jumpers NoLu Fan control Terminal 1 activated NoLu Fan control deactivated only On Off NoLi Dimming of light Terminal 3 activated NoLi Dimming of light deactivated onl...

Page 22: ...responding to the require ments of the excess voltage category III for total disconnection Disconnect the unit from the mains before carrying out any work on it switch off the fuse in the distribution...

Page 23: ...manufacturers may be connected to this control if the technical data match These devices have their own operating instructions Please note the safety information technical data and instructions in the...

Page 24: ...ases L1 L2 and L3 have been connected to the appropriate terminals see circuit diagram Check the electrical consumers like the cabin light cleaning light and fans It must be possible to switch on and...

Page 25: ...ure measurement value in the Basic Settings In fo Sensor menu If required compare the displayed value with the value on a ref erence temperature measuring device After approximately 10 minutes of oper...

Page 26: ...e manufacturer and the legal regulations valid at the time of concluding the agreement are applicable Guarantee The guarantee period of the manufacturer starts from the time of dispatch by the manu fa...

Page 27: ...control should be carried out only by the tech nical experts Obtain spare parts from the installer or the dealer of the sauna unit For address see the invoice delivery note or the reverse of the manua...

Page 28: ...Notes Address of the contractor installer or the dealer of the sauna unit...

Reviews: