Commissioning
Installation instructions
25
NOTE!
Operation of a gas oven:
The control device must be configured especially for the operation of a
gas oven.
It is possible to connect a gas burner (burner 1) to phase U and gas
burner (burner 2) to phase V. Phase W in this variant is meant for the
exhaust. Phase V for the burner 2 is switched off at a temperature dif-
ference of 5 K below the set temperature.
The exhaust is active while the gas burner is heating.
6.5
Functional test of the sensor
NOTE!
– If the sensor or the sensors have not been properly connected then a
signal is sounded and an error message is displayed on the display.
→
See also the operating manual.
◼
Check the display of the temperature measurement value in the “Basic Settings - In-
fo -
Sensor” menu. If required, compare the displayed value with the value on a ref-
erence temperature measuring device. After approximately 10 minutes of operation
the displayed temperature must increase significantly.
◼
In case of the bathing option "Sauna with humidity
” and a connected humidity sen-
sor, check the displayed value of the humidity sensor. If required, compare the dis-
played value with the value on a reference humidity measuring device. After approx-
imately 10 minutes of operation of the evaporator, the displayed humidity value must
increase significantly.
◼
If two temperature sensors (oven, bench or combined bench sensor) are connected,
then after 10 minutes of operation of the heating system, the temperature displayed
for the oven sensor should be higher than that of the bench sensor. If required,
change the connections in the sauna control.