background image

7

INSTALLATION

EV02F CONTROL UNIT INSTALLATION

Fully loosen the fastening bolt to release the base of 

the control unit. Lever on the slots with a screwdriver 

to remove the base.

Secure the control unit terminal base to the wall (or 

according to the mounting systems described in the 

previous page) in a dry room, free from dripping.

EC11 OUTSIDE PROBE INSTALLATION

Install the outside probe in a vertical position on the 

north or north-west wall of the building at about 2.5 

metres at least from the ground. Install the probe far 

from  heat  sources  (windows,  aerators,  flues,  etc.) 

and protruding parts.

 

EC12  (contact  probe)  AND  EC13  (immersion 

probe) DELIVERY PROBE INSTALLATION

Install  the  contact  probe  EC12  onto  the  water  pipe 

with the clamp provided for the purpose and with heat 

conducting  paste  interposed  in  order  to  guarantee 

proper heat conduction.

The immersion probe EC13 must be fitted in the pip

-

ing with the sheath filled with mineral oil or silicone 

grease.

NOTE The delivery probes must be mounted down-

stream the mixing valve at least 1.5 metres from the 

valve, preferably after an elbow.

If the circulation pump is placed on the delivery side, 

install the probe downstream the pump.

3- OR 4-WAY MIXING VALVE INSTALLATION

Install  the  mixing  valve  at  boiler  top  edge  level,  in 

handy position.

Check for no seizing between shutter and valve body 

by operating the mixing valve manually; restore me

-

chanical connection between servo control and valve 

body.

When  at  closed  position  the  mixing  valves  do  not 

guarantee  perfect  seal,  it  is  therefore  necessary  to 

install suitable gate valves or check valves on radia-

tor circuits in order to enable valve removal without 

having to drain the circuit.

Summary of Contents for EV02F

Page 1: ...e set programming determines the delivery water temperature value to be sent to the system to keep the set ambient temperature constant The control unit is fitted with quartz clock for daily programmi...

Page 2: ...in insulat ing material with transparent cover Protection IP40 installation wall flush or rear panel mounting TECHNICAL DATA Control unit consumption 5VA Supply voltage 230V 10 50Hz Compliance with CE...

Page 3: ...re similar to those tabulated below Resistance values as a function of temperature EC11 OUTSIDE PROBE TEMPERATURE RESISTANCE C DELIVERY PROBES EC12 EC13 TEMPERATURE RESISTANCE C 40 8629 35 7853 30 711...

Page 4: ...ff with the exception of the an tifreeze protection in the antifreeze operating mode and at night in the AUTOMATIC 2 operating mode To make the most of the remaining heat accumulated during the daytim...

Page 5: ...ervo controls powered with 230 V 50 Hz Circulation pump supply Servo control Supply voltage Common Open Close Delivery probe EC12 EC13 Outside probe EC11 230 V 50 Hz Circulation pump supply Circulatio...

Page 6: ...mfort Automatic 2 nightime antifreeze daytime comfort Screw for mechanical connection between electronic panel and terminal base Quartz clock for daily programming FRONT CONTROL PANEL L H G F E A A B...

Page 7: ...the purpose and with heat conducting paste interposed in order to guarantee proper heat conduction The immersion probe EC13 must be fitted in the pip ing with the sheath filled with mineral oil or si...

Page 8: ...8 EXAMPLES OF HYDRAULIC CONNECTIONS FOR MIXING VALVES 3 WAY SECTOR POWER OPERATED MIXING VALVE 3 WAY ROTOR POWER OPERATED MIXING VALVE 4 WAY ROTOR POWER OPERATED MIXING VALVE...

Page 9: ...turn slightly knob F counterclockwise if it is higher turn knob F clockwise Check again temperature after 24 hours If required keep on adjusting knob F position like indicated in the table below unti...

Page 10: ...NAL INSTRUCTIONS WINTER MODE DUTY Open the circulation pump gate valves Start the pump If the system is equipped with mixing valve operate the valve manually to remove any sediment deposi ted inside t...

Page 11: ...etely then turn the system off b stop water circulation pump c close circulation pump gate valves to prevent hot water infiltration into radiator circuits during the sum mer since mixing valves do not...

Reviews: