9
SETTINGS AND ADJUSTMENTS
1) INITIAL CONTROLS POSITIONS
(see paragraph “front control panel”, page 6)
D
at central area (comfort zone).
E
fully rightwards at “MAX” position (same
temperatures for night and day).
H
at Automatic 1 (nighttime economy/day-
time comfort).
F
at position 2 for radiator heating, or at po-
sition 0,5 for panel heating.
B
at central position (pump shutdown delay
of about 30 minutes).
2) Set the boiler thermostat so to keep water temper-
ature at approx. 80 - 90°C, then turn the system on.
3) After 24 hours the ambient temperature of a stand-
ard room shall be equal to 20°C. If temperature is
lower turn slightly knob F counterclockwise, if it is
higher turn knob F clockwise.
Check again temperature after 24 hours. If required
keep on adjusting knob F position like indicated in
the table below until obtaining 20°C in the room, with
whatever outside temperature (it is recommended
to check temperature in the afternoon and early in
the morning since outside temperature changes for
sure).
NOTE
knob F shall be used to select the required
straight line in diagram A, i.e. the pointer indicates the
straight line slope on the diagram.
4) Under these conditions the control unit is set on
the system and knob F shall no longer be operated.
To obtain the required operating modes according to
the plate data, just use knobs D , E , G .
5) Then set the clock as described in paragraph
“QUARTZ CLOCK DAILY PROGRAMMING”