TEMPERATURE PROBES

GENERAL FEATURES

-  EC--  series  temperature  probes  are  the  sensors 

used by the control unit to get the information requi-

red for its operation.

- The sensing element is made up of linearised NTC 

thermistors.

TECHNICAL DATA

- Cable clamp: G 1/4.

- Operating temperature: - 40 to 150°C.

-  Connection  between  probes  and  control  units  by 

means of double-wire cable, 1 mm2  min. section and 

1000 metres max. length (for higher lengths increase 

the cable section to keep resistance constant).

NOTE

: the control unit also works with probes EC01 

(outside probe), EC02 (contact probe) and EC03 (im-

mersion probe); resistance values are similar to those 

tabulated below.

Resistance values as a function of temperature:

EC11 OUTSIDE PROBE

TEMPERATURE    RESISTANCE 

°C                                   Ω

DELIVERY PROBES     EC12 EC13

TEMPERATURE           RESISTANCE 

°C                                          Ω

- 40                   8629

- 35                   7853

- 30                   7118

- 25                   6433

- 20                   5720

- 15                   5230

- 10                   4770

- 5                     4370

0                       4010

+ 5                    3700

+10                   3440

+15                   3210

+20                   3020

+ 20                           550

+ 30                           517

+ 40                           483

+ 50                           448

+ 60                           416

+ 70                           386

+ 80                           360

+ 90                           338

+100                          320

CONNECTIONS AND TESTS

ELECTRIC CONNECTIONS

Fit a small switch with 1A fuse valves on control unit 

supply line for protecting the servo control and turn-

ing off the power when removing the control unit from 

the base.

Electric connections between probes and control unit 

shall  be  performed  by  two-wire  cables  with  1  mm2 

section and max.  1000 metres length; if higher cable 

lengths are required, increase the cable section in or-

der to keep cable total resistance constant.

Summary of Contents for EV02F

Page 1: ...e set programming determines the delivery water temperature value to be sent to the system to keep the set ambient temperature constant The control unit is fitted with quartz clock for daily programmi...

Page 2: ...in insulat ing material with transparent cover Protection IP40 installation wall flush or rear panel mounting TECHNICAL DATA Control unit consumption 5VA Supply voltage 230V 10 50Hz Compliance with CE...

Page 3: ...re similar to those tabulated below Resistance values as a function of temperature EC11 OUTSIDE PROBE TEMPERATURE RESISTANCE C DELIVERY PROBES EC12 EC13 TEMPERATURE RESISTANCE C 40 8629 35 7853 30 711...

Page 4: ...ff with the exception of the an tifreeze protection in the antifreeze operating mode and at night in the AUTOMATIC 2 operating mode To make the most of the remaining heat accumulated during the daytim...

Page 5: ...ervo controls powered with 230 V 50 Hz Circulation pump supply Servo control Supply voltage Common Open Close Delivery probe EC12 EC13 Outside probe EC11 230 V 50 Hz Circulation pump supply Circulatio...

Page 6: ...mfort Automatic 2 nightime antifreeze daytime comfort Screw for mechanical connection between electronic panel and terminal base Quartz clock for daily programming FRONT CONTROL PANEL L H G F E A A B...

Page 7: ...the purpose and with heat conducting paste interposed in order to guarantee proper heat conduction The immersion probe EC13 must be fitted in the pip ing with the sheath filled with mineral oil or si...

Page 8: ...8 EXAMPLES OF HYDRAULIC CONNECTIONS FOR MIXING VALVES 3 WAY SECTOR POWER OPERATED MIXING VALVE 3 WAY ROTOR POWER OPERATED MIXING VALVE 4 WAY ROTOR POWER OPERATED MIXING VALVE...

Page 9: ...turn slightly knob F counterclockwise if it is higher turn knob F clockwise Check again temperature after 24 hours If required keep on adjusting knob F position like indicated in the table below unti...

Page 10: ...NAL INSTRUCTIONS WINTER MODE DUTY Open the circulation pump gate valves Start the pump If the system is equipped with mixing valve operate the valve manually to remove any sediment deposi ted inside t...

Page 11: ...etely then turn the system off b stop water circulation pump c close circulation pump gate valves to prevent hot water infiltration into radiator circuits during the sum mer since mixing valves do not...