INSTALLATION EXAMPLES

10

Magnehelic

Magnehelic

Gauge

Duct

Air

Flow

Pitot

Tube

A

The duct’s airflow veloc-
ity is generally meas-
ured with a magnehelic
gauge and a pitot tube.

• To avoid airflow turbu-

lence and incorrect
readings, the airflow
velocity should be meas-
ured on steel ducting a
minimum of 3 duct
cross-section from the
unit or elbow and before
any transition.

• The balancing procedure consists of measuring the exhaust air leaving the system and the supply air entering the system and

ensuring that these two are equal. A deviation of 10% or less is acceptable.

AIR FLOW BALANCING

A

*

Pitot tube and gauge

Note: 

A professional air balancer should be contacted to commission the system properly.

A skilled HVAC Tech may complete the balance of air providing they possess the proper
equipment. Call Fantech Technical support for assistance.

INSTALLING BYPASS MODULE (BPM)

REFER TO BPM INSTALLATION, OPERATION AND MAINTENANCE
DOCUMENT FOR INSTRUCTIONS

INTERIOR WALL

EXTERIOR WALL

EXTERIOR WALL

POOL HRV

MECHANICAL ROOM

EXTERIOR WALL

RECIRCULATION

BACKDRAFT DAMPER

MDH1 Control

EDF1R Control

INTERIOR WALL

EXTERIOR WALL

EXTERIOR WALL

POOL HRV

EXTERIOR WALL

RECIRCULATION

BACKDRAFT DAMPER

RETURN          
  GRILL

MDH1 Control

EDF1R Control

MECHANICAL ROOM

Installation with Grille

Summary of Contents for SHR 14105R

Page 1: ...er operating at a higher static After installation the compatibility of the two pieces of equipment must be con firmed by measuring the airflow s of the Heat Recovery Ventilators It is always importan...

Page 2: ......

Page 3: ...evacuation of condensate The plates are hemmed to avoid cross contamination of airstreams FILTERS The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL Clas...

Page 4: ...he unit has access doors on the front and back Also the main control panel may be moved from front to back allowing for ducting layout Outdoor or Recirculated Air Indoor Air Standard Configuration as...

Page 5: ...LTERS The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL Class2 Optional MERV6 filters are direct replacement to the MERV1 Use of MERV6 filters will add a...

Page 6: ...ont or the back of the cabinet 63mm 2 5 PORT CONFIGURATION The unit has access doors on the front and back Also the main control panel may be moved from front to back allowing for ducting layout Stale...

Page 7: ...MODES OF OPERATION Intermittent operation can be obtained by toggling the switch located on outside of cabinet External low voltage contacts allow for high speed operation when an optional remote con...

Page 8: ...ming required service maintenance Care must be taken to locate the recirculation port in an area that will not cause any unwanted contaminant to be drawn into the liv ing space during recirculation an...

Page 9: ...nual INSTALLING DUCTS TO FROM INSIDE Direct Connection to Furnace Air handler return duct Should you wish to hard duct the supply air directly into the cold air return of the HVAC systems remember to...

Page 10: ...eviation of 10 or less is acceptable AIR FLOW BALANCING A Pitot tube and gauge Note A professional air balancer should be contacted to commission the system properly A skilled HVAC Tech may complete t...

Page 11: ...or light coil solution d Install clean cores making sure the matting sur faces have one sealing edges between each cores to minimize leaks e Install the clean filters f Replace access door Note Core i...

Page 12: ...D WHITE BLACK WHITE UNI CTRL JUMPER SETTINGS OFF ON ON OFF ON OFF ON J4 J6 J5 J7 J1 J2 J3 GROUND N WHITE L BLACK FUSE SPECIFICATION FAH0800 HCE PCB REPLACEMENT FAH0900 FAH1400 FAH1200 TYPE FUSE RATING...

Reviews: