3
APPLICATIONS INCLUDE:
• Indoor Pools
• Night Clubs
• Spa's
• Locker Room
• Health Centers
• High humidity Applications
POWER & WEIGHT
• Volts
120V
• Amperage
5.4 Amps Total
• Weight
80.3 Kg (177 Lbs)
• Shipping Weight
98 Kg (217 Lbs)
• Blowers (x2)
115V, 60 Hz, 2.7 Amps
• Phase
Single
SHR 8005R
Light Commercial HRV
The Fantech SHR8005R is
designed to provide an economi-
cal solution for high humidity
applications such as indoor
swimming pools, spas and fit-
ness facilities. The higher humid-
ity generation rate in these appli-
cations leads to annoying window
condensation, mold and struc-
ture deterioration. It’s designed to reduce the occurrence of
condensation in the indoor environment by first operating in
recirculation mode, moving air around the structures, sweeping
windows dry and eliminating troublesome cold spots, then
switching to air exchange mode as needed. Air exchange mode
simply exhausts humid air to the outside and replaces it with
drier air from outside. The airstreams are separated by an
energy efficient heat recovery core which uses the energy in the
exhaust air to lower the load on the HVAC system. Automatic
defrost and provisions for condensation are standard.
SPECIFICATIONS
CASE
20 gauge G90 galvanized steel coated with baked
powder paint, insulated with 25mm (1 inch) and 50mm (2
inch) on outdoor air side foil-faced high density polystyrene
foam for condensation control.
BLOWERS
Two (2) maintenance-free Ebm-Papst™ backward
inclined motorized impellers with permanently lubricated sealed
ball bearings and (TOP) thermal overload protected.
HEAT RECOVERY CORES
The heat recovery cores are fixed plate
cross-flow heat exchanger using 1100 alloy aluminum and
capable of transferring sensible heat between air streams.
The heat recovery cores are engineered with a turbulence
inducing geometry in order to maximize heat transfer while
allowing an effective evacuation of condensate. The plates are
hemmed to avoid cross-contamination of airstreams.
FILTERS
The exhaust and fresh air streams are protected by
MERV1 washable filters constructed to meet UL Class2.
Optional MERV6 filters are direct replacement to the MERV1.
Use of MERV6 filters will add an additional system pressure
of 72 Pa (0.29in.wg) at 378 l/s (800cfm).
MOUNTING
Unit can be rod mounted or seated on a
platform. Flanged connections are provided for suitable
ductwork connections. Unit shall be adaptable for easy
service of electrical components.
CONTROLS
External three (3) position (Low/Standby/Medium)
rocker switch that will offer continuous ventilation. Compatible
with all Fantech HRV controls.
FROST CONTROL
During the defrost sequence, a motorized
damper temporarily blocks the incoming fresh air stream so
that the warm air from the building can circulate through the
HRV. The exhaust blower shuts down and the supply blower
switches into high speed to maximize the effectiveness of the
defrost strategy.
SERVICEABILITY
Unit has hinged or screwed access panels on
front and back. Cores, filters, motors and drain pan are
serviceable from either sides of the unit. Fan assemblies are
mounted on a removable sliding base. Heat recovery cores are
mounted in slide-out rails for ease of inspection, removal and
cleaning. Accessibility to the electrical box is maintained for
any unit installation.
0
50
100
150
200
250
275
300
350
400
450
500
550
600
650
700
750
800
850
900
950
2007-10-01
Thermal Effectiveness
10%
30%
50%
70%
90%
0
400
800
1200
Airflow (cfm)
Effectiveness
0
189
378
566
Airflow (l/s)
0
50
100
150
200
250
275
300
350
400
450
500
550
600
650
700
750
800
850
900
950
2007-10-01
Airflow Performance
0.0
0.4
0.8
1.2
1.6
0
400
800
1200
Airflow (cfm)
External Static Pressure, (in wg)
0
99
199
298
0
189
378
566
Airflow (l/s)
External Static Pressure (Pa)
High
Medium
Low
Recirculation
Airflow Performance
Airflow (l/s)
Airflow (cfm)
Airflow (cfm)
E
xt
e
rn
a
l
S
ta
ti
c
P
re
s
s
u
re
,
(i
n
w
g
)
E
xt
e
rn
a
l
S
ta
ti
c
P
re
s
s
u
re
(
P
a
)
Thermal Effectiveness
Airflow (l/s)
E
ff
e
ct
iv
e
n
e
s
s
Summary of Contents for SHR 14105R