Fantech SHR 14105R Installation Manual Download Page 8

8

INSTALLATION

Installing Drain Line

Through normal operation and including defrost mode, the HRV may produce some condensation. This water should flow into a nearby
drain, or be taken away by a condensate pump. The HRV and all condensate lines must be installed in a space where the tempera-
ture is maintained above freezing point. A “P” trap should be made in the drain line. This will prevent odors from being drawn back
up into the unit.

LOCATION 

The HRV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the HRV would be
located in the mechanical room, above a drop ceiling or an area close to the outside wall where the weatherhoods will be mounted.
Attic installations are not recommended due to extreme temperatures, and difficulty in performing, required service & maintenance.
Care must be taken to locate the recirculation port in an area that will not cause any unwanted contaminant to be drawn into the liv-
ing space during recirculation and defrost.

Connecting appliances to the HRV

It is not recommended, including:

- clothes dryer
- kitchen exhaust hoods
- combustion venting
- central vacuum system

These appliance may cause lint, dust or grease to collect in the HRV , damaging the unit.

NOTE:

Connecting any of these type of appliances to the HRV will invalidate your warranty

Install the drain hose, making a “P” trap

Model

A

B

C

D

E

F

G

SHR 8005R

23.8Kg (52.5lbs)

22.5Kg (49.6lbs)

390mm (15.4")

85Kg (187lbs)

20Kg (44lbs)

18.8Kg(41.3lbs)

448mm (17.6")

SHR 14105R

30.4Kg (67lbs)

27Kg (60lbs)

544mm (21.4")

109Kg (241lbs)

27.7Kg (61lbs)

24.3Kg (53.5lbs)

455mm (18")

A

B

F

E

D

C

G

TIP:

Flexible duct connectors should be

installed between the HRV and the galva-
nized ductwork.

The water should be
drained back into the
pool and not wasted

Tape

or Tie Wrap

Drain

Spout

Tee

Connector

Summary of Contents for SHR 14105R

Page 1: ...er operating at a higher static After installation the compatibility of the two pieces of equipment must be con firmed by measuring the airflow s of the Heat Recovery Ventilators It is always importan...

Page 2: ......

Page 3: ...evacuation of condensate The plates are hemmed to avoid cross contamination of airstreams FILTERS The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL Clas...

Page 4: ...he unit has access doors on the front and back Also the main control panel may be moved from front to back allowing for ducting layout Outdoor or Recirculated Air Indoor Air Standard Configuration as...

Page 5: ...LTERS The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL Class2 Optional MERV6 filters are direct replacement to the MERV1 Use of MERV6 filters will add a...

Page 6: ...ont or the back of the cabinet 63mm 2 5 PORT CONFIGURATION The unit has access doors on the front and back Also the main control panel may be moved from front to back allowing for ducting layout Stale...

Page 7: ...MODES OF OPERATION Intermittent operation can be obtained by toggling the switch located on outside of cabinet External low voltage contacts allow for high speed operation when an optional remote con...

Page 8: ...ming required service maintenance Care must be taken to locate the recirculation port in an area that will not cause any unwanted contaminant to be drawn into the liv ing space during recirculation an...

Page 9: ...nual INSTALLING DUCTS TO FROM INSIDE Direct Connection to Furnace Air handler return duct Should you wish to hard duct the supply air directly into the cold air return of the HVAC systems remember to...

Page 10: ...eviation of 10 or less is acceptable AIR FLOW BALANCING A Pitot tube and gauge Note A professional air balancer should be contacted to commission the system properly A skilled HVAC Tech may complete t...

Page 11: ...or light coil solution d Install clean cores making sure the matting sur faces have one sealing edges between each cores to minimize leaks e Install the clean filters f Replace access door Note Core i...

Page 12: ...D WHITE BLACK WHITE UNI CTRL JUMPER SETTINGS OFF ON ON OFF ON OFF ON J4 J6 J5 J7 J1 J2 J3 GROUND N WHITE L BLACK FUSE SPECIFICATION FAH0800 HCE PCB REPLACEMENT FAH0900 FAH1400 FAH1200 TYPE FUSE RATING...