Troubleshooting

A) Problem:  

When the DM3000P is on "STANDBY" it does not come ON.

 

1) The pressure switch's positive pressure port is not connected.

 

 

Solution: Use the supplied tube and grommet and install one end of the tube to the supply (positive pressure) air duct and 
the other end of the tube to the pressure switch connection on electrical panel next to the power cord.

 

2) The pressure differential between the return (negative) air and the supply (positive) air of the forced air system is less than 18 Pa 

(0.07 in wg).

 

 

Solution: Check the static pressure difference by connecting the LOW pressure side of a manometer to the return air duct 
and the HIGH pressure side of the manometer to the supply air duct. If it reads less then 18 Pa (0.07 in wg), the pressure 
switch will not work. The only remedy is to set the rocker switch to "CONTINUOUS". Check this differential pressure on all 
available speeds of the forced air system.

B) Problem:  

When the DM3000P is on "STANDBY" it does not turn OFF.

 

1) Other exhaust equipment in the house may interfere with the operation of the DM3000P by creating pressure differences in the 

forced air system's duct work.

 

 

Solution: If this is a constant problem, disconnect the positive pressure tube from the DM3000P to the supply air duct. 
Check if the DM3000P turns ON when the forced air system is on and turns OFF when the forced air system is OFF.

Depending on the furnace and the duct design, the negative static pressure in the duct may not be more than 17Pa (0.07"WC). As such, the pressure 
switch will not activate the DM3000P while it is on "STANDBY" mode.

Summary of Contents for HEPA DM 3000P

Page 1: ...n of the National Building Code and or ASHRAE s Good Engineering Practices Fantech reserves the right to modify at any time and without notice any or all of its products features designs components and specifications to maintain their technological leadership position Please visit our website www fantech net for more detailed technical information United States 10048 Industrial Blvd Lenexa KS 6621...

Page 2: ...fects Even reliable products will experience occasional failures and this possibility should be recognized by the user If these products are used in a life support ventilation system where failure could result in loss or injury the user should provide adequate back up ventilation supplementary natural ventilation or failure alarm system or acknowledge willingness to accept the risk of such loss or...

Page 3: ...3 fantech Table of content INTRODUCTION 4 SPECIFICATION 4 OPERATION 4 INSTALLATION 5 Installation instructions 5 TROUBLESHOOTING 6 SERVICE 7 FILTER REPLACEMENT 7 PARTS LIST 16 ...

Page 4: ...m in mm DM 3000P 16 406 20 508 10 1 2 268 Operation Your Fantech HEPA filtration system incorporates three stages of filtration Air is drawn from the house via one of the installation examples found in this manual by a powerful efficient EBM fan The air is cleaned as it passes through the filters where it is then reintroduced back into the home cleaned of the majority of harmful particles The DM30...

Page 5: ...lation or other obstacles Attach HEPA unit to mounting plate with screws Installing Grommet and Tubing First drill a 1 4 to 5 16 diameter hole in the duct wall on the supply air side of the furnace duct Carefully insert the grommet into the hole Drilling a metal duct may produce burrs Be careful not to cut or pricked by the burrs or the duct Make a mark a distance of1 2 from one end of the tubing ...

Page 6: ...the supply air duct If it reads less then 18 Pa 0 07 in wg the pressure switch will not work The only remedy is to set the rocker switch to CONTINUOUS Check this differential pressure on all available speeds of the forced air system B Problem When the DM3000P is on STANDBY it does not turn OFF 1 Other exhaust equipment in the house may interfere with the operation of the DM3000P by creating pressu...

Page 7: ...ain depending on the amount of particulate in the air and the maintenance of the Stage 1 pre filter As an added service Fantech offers an online filter replacement reminder service Just go to www fantech net and for Reminder Service and follow the links All you need to enter is your e mail address the product model and a description of the environment Very Clean Clean Moderate The Service will sen...

Page 8: ...8 fantech Notes ...

Page 9: ... bâtiment du Canada ou aux méthodes d ingénierie appropriées de l ASHRAE Fantech se réserve le droit de modifier partiellement ou entièrement en tout moment et sans préavis les caractéristiques la conception les composants et les spécifications de ses produits afin de conserver sa position de leader de technologie S il vous plaît visitez notre site siteweb www fantech net pour des informations tec...

Page 10: ...s pannes occasionnelles et cette possibilité devrait être reconnue par l utilisateur Si ces produits sont utilisés dans un système de ventilation qui maintien des fonctions vitales où une défaillance pourrait entraîner des pertes ou des blessures l utilisateur doit fournir une ventilation de secours adéquate une ventilation supplémentaire naturelle un système d alarme de défaillance ou d accepter ...

Page 11: ...11 fantech Table des matières INTRODUCTION 12 SPÉCIFICATION 12 OPÉRATION 12 INSTALLATION 13 Instructions d installation 13 DÉPANNAGE 14 SERVICE 15 CHANGEMENT DES FILTRES 15 LISTE DES COMPOSANTE 16 ...

Page 12: ...pi de Corde prise de 3 fourches Modèle A B C po mm po mm po mm DM 3000P 16 406 20 508 10 1 2 268 Opération Votre système de filtration HEPA de Fantech est un système de filtration à trois étages L air de la maison est aspiré voir les différents exemples d installation dans le présent manuel à l aide d un ventilateur EBM puissant et efficace L air passe dans les filtres pour y être épuré et est ens...

Page 13: ...ssion au conduit est correctement inséré dans le conduit d évacuation Le bout du tube devrait être libre d obstructions telle que de l isolant etc Attacher l unité HEPA avec les vis sur la plaque Installation du canon isolant et du tube Percez un trou de _ po à 5 16 po 6 35 à 7 94 mm dans le conduit sur le côté de l approvisionnement d air Insérez soigneusement le canon isolant dans le trou Attent...

Page 14: ...t inférieure à 18 Pa 0 07 po d eau le commutateur de différence de pression ne fonctionnera pas Il faudra alors placer l appareil on mode continue CONTINUOUS Vérifier cette différence de pression à toutes les vitesses disponibles sur le système de chauffage et ou de climatisation B Problème Quand le DM3000P est en mode d attente STANDBY le système ne s éteint jamais 1 Le fonctionnement de produits...

Page 15: ...nelle à la quantité d aérocontaminants et à l entretien du préfiltre de l étage 1 Comme un service supplémentaire Fantech offre un service en ligne de rappel de remplacement de filtre Allez juste à www fantech ca et pour le Reminder Service et suivez les liens Tout que vous devez entrer est votre adresse de E mail le modèle de produit et une description de l environnement très propre propre modéré...

Page 16: ...M3000P 40217 1 Duct Plate Adapter 401462 3 Motor Assembly 40323 4 Hepa Filter 40193 5 Pre Carbon Filter 40195 6 Capacitor 10uF 410040 7 Control Switch 410213 9 Latch 410312 Pressure Switch 411226 Hepa Filter Box of 12Pcs 40194 Pre Carbon Filter Box of 24Pcs 40196 ...

Page 17: ...17 fantech Notes ...

Page 18: ...18 fantech Notes ...

Page 19: ...19 fantech Notes ...

Page 20: ... to make technical changes For updated documentation please refer to www fantech net Fantech Fantech se réserve le droit de faire des changements tech niques Pour de la documentation à jour s il vous plaît se référer au www fantech net ...

Reviews: