TROUBLESHOOTING

The Unit is NOT working:

• 

Why do you believe the dehumidifier is not working?

• 

Is the power ON?

• 

Has the breaker tripped? – Reset breaker

• 

If in a wet area, is the unit plugged into a GFI protected cir-
cuit? – Excessive moisture will trip GFI. Remove from area.

• 

Is the unit being run off a generator? - Check output does 
not fluctuate as the unit will not operate at low voltage.

• 

If  using  an  extension  cord  -  Is  the  cord  of  the  correct 
gauge for the distance run? (14 AWG up to 25’ and 12 
AWG over 25’). Note: Verify voltage while unit is starting. 
Start up will cause the highest current draw and largest 
voltage drop. Even if plugged directly to outlet there can 
be a significant voltage drop. Never assume the voltage is 
ok without verifying.

• 

Is the unit draining? – Check the condensate receptacle. 
If full, the float is up and the unit will not operate – drain 
receptacle. 

The unit continually ices up: Note that some ice buildup on the 

evaporator coils is normal but airflow should not be blocked.

• 

Is the fan working? – Fan not working, check run capacitor 
and fan unit.

• 

Is warm air blowing out the front of the unit? - No warm 
air, temperature may be too low. Raise temperature with 
supplementary source.

• 

Is  the  air  filter  clean  and  airflow  unobstructed?  –  Clean 
filter.  Unit  should  have  a  minimum  of  10”  clearance  all 
around it.

• 

Dirty evaporator coils? – Clean coils.

• 

Defrost  thermostat  loose  or  not  working?  –  Secure  or 
replace. 

• 

Defrost  timer  set  incorrectly  or  defective?  –  Reset  or 
replace.

• 

Temperature  in  the  operating  space  is  too  low?  -  Raise 
temperature with supplementary source.

Unit moves some water but not as much as expected:

• 

Air temperature and Relative Humidity have dropped - Check 
levels with calibrated humidity meter and/or thermostat. 

• 

Unit is in defrost cycle – Unit will start after cycle.

• 

Air filter dirty or airflow obstructed - Unit should have a 
minimum of 10” clearance all around it. Clean air filter and 
ensure adequate airflow/space around unit.

• 

Evaporator coils dirty – Clean coils.

• 

Restrictive or kinked exhaust ducting (if used) – Straighten 
out ducting.

• 

Defrost timer set incorrectly for conditions – Reset timer.

• 

Defrost thermostat defective - Replace

• 

Refrigerant charge is low – Have unit checked by qualified 
technician

• 

Defective compressor – Replace compressor by qualified 
technician as it requires recycling of refrigerant. 

Unit runs continuously for days:

• 

Unit is working removing water - High Relative Humidity 
in space.

• 

Humidity or water is getting into the space – Find source 
and stop it.

• 

Unit is undersized for space – Use larger unit or mul-
tiple units.

• 

Poor  air  movement  in  space  –  Use  air  movers  to 
increase movement.

Unit runs but does not pump water:

• 

Drain hose kinked or blocked – Straighten or unblock hose.

• 

Pump float stuck closed – Reset or replace.

• 

Pump not working – Check electrical operation with out-
side supply.

• 

Hose disconnected internally – Reconnect hose.

• 

Compressor capacitor bad – Check capacitor.

Fan runs but Compressor does not:

• 

Condensate pump not working – Check pump and float.

• 

Bad connection in pump circuit – Check connections.

• 

Bad compressor capacitor – Check capacitor.

• 

Defective compressor – Replace compressor by quali-
fied technician.

• 

Defective time delay or Thermistor – Check and/or replace.

Fan does not run. Compressor runs briefly but cycles on/off:

• 

Defective fan capacitor – Check capacitor. 

• 

Loose connection in fan circuit – Check connections.

• 

Fan obstructed and not turning – Remove obstruction.

• 

Defective fan – Replace fan.

Summary of Contents for GDC124CSS

Page 1: ...ORE INSTALLING UNIT DEHUMIDIFIER D SHUMIDIFICATEUR DESHUMIDIFICADOR Owner s Manual OPERATION AND MAINTENANCE MANUAL Operating Instructions 2 Guide d utilisation 6 Instrucciones de uso 10 Models Mod le...

Page 2: ...essing this button activates the hot gas defrost system This can be used to clear the evaporator coil of frost if required The button must be held depressed until the evaporator coil is cleared of fro...

Page 3: ...f children 2 3 4 1 Bent Handle 2 Wheel Axle 1 Wheel 2 Screw Handle 6 Hand Axle 1 Washer 2 Lynch Pin 2 Position up and open top Remove inserts and handl components Remove the unit Cut two vertical corn...

Page 4: ...ack WARNING Personal injury hazard Do not place fingers in ring area Ring is spring loaded and closes with force Wheel Handle Assembly Lower Door Second Handle Assembly ASSEMBLY Position unit on back...

Page 5: ...d Air temperature and Relative Humidity have dropped Check levels with calibrated humidity meter and or thermostat Unit is in defrost cycle Unit will start after cycle Air filter dirty or airflow obst...

Page 6: ...do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives specific legal rights and the purchaser ma...

Page 7: ...le serpentin vapora teur du givre au besoin Le bouton doit tre maintenu enfonc jusqu ce que le serpentin d vaporateur soit d barrass du givre Le d shumidificateur doit tre en position ON NOTE Mainten...

Page 8: ...n up and open top Remove inserts and handle components Remove the unit Cut two vertical corners CAUTION Do not damage unit with knife vaporateur Condenseur vaporateur Entr e de l air humide Flotteur R...

Page 9: ...relative ont baiss s V rifiez la temp rature et l humidit relative avec un hygrom tre calibr et ou un thermostat L appareil est en cycle de d givrage L appareil recom mencera apr s le cycle Filtre ai...

Page 10: ...Assemblage de la porte inf rieure et la deuxi me poign e ASSEMBLAGE Placez l appareil sur le dos Enlevez les quatre vis d exp dition et jetez les Placez l appareil avec le filtre air vers le haut Inst...

Page 11: ...ommages cons cutifs ou indirects de sorte que la limitation ou l exclusion ci dessus pourrait ne pas s appliquer vous Cette garantie donne des droits l gaux particuliers l acheteur et celuici peut avo...

Page 12: ...ara eliminar la escarcha del serpent n evaporador cuando sea necesario Mantenga el bot n apretado hasta que el serpent n evaporador no tenga escarcha El deshumidificador debe estar encendido ON NOTA M...

Page 13: ...ynch Pin 2 Position up and open top Remove inserts and handle components Remove the unit Cut two vertical corners CAUTION Do not damage unit with knife Evaporador Condensador vaporateur Entrada de air...

Page 14: ...rte trasera Desatornille los 4 tornillos de transporte ydes chelos Coloque la unidad con el filtro de aire hacia arriba Coloque uno de los tubos cortos en el eje de la rueda Inserte el asa curvada en...

Page 15: ...rde guardar el recibo como comprobante de venta 5 En algunos estados no se permite la exclusi n o limitaci n de da os consecuentes o secundarios en estos casos la limitaci n anterior podr a no aplicar...

Page 16: ...mpresor Condensate Pump Pompe condensats Bomba de condensado Condensate Pump Pompe condensats Bomba de condensado Fan Motor Moteur du ventilateur Motor del ventilador Fan Motor Moteur du ventilateur M...

Page 17: ...17...

Page 18: ...ents and specifica tions to maintain their technological leadership position United States 10048 Industrial Blvd Lenexa KS 66215 Phone 800 747 1762 913 752 6000 Fax 800 487 9915 913 752 6466 www fante...

Reviews: