background image

12

BALANCING STEPS

 

Use balancing chart located on the 

door of the HRV

STEP #1:

 Identify the desired airflow using the provided 

chart. From the desired airflow (left column) identify the 
pressure reading needed by simply following the line. In the 
event where multiple choices are available for the same 
airflow, we recommend using the pressure reading from the 
lowest speed on the chart. Make sure to set the unit at the 
correct speed before performing the next step.

STEP #2:

 Measure the pressure reading by connecting a 

manometer on the LOW and HIGH pressure ports located 
on the duct connection. Refer to 

Illustration #1.

 If the pres-

sure reading is LOWER than the desired value, adjust the 
balancing dampers by turning the adjustable arm counter 
clockwise until the correct corresponding pressure value is 
reached. Refer to 

Illustration #2

 Do the same for both the 

SUPPLY and ExHAUST airflows. If the pressure reading is 
HIGHER than desired when the damper is fully opened, please check the distribution system for any anomalies that could increase the 
resistance in the distribution system.

•  Because the house is tightly sealed, adjusting one airflow may 

affect the other airflow as well. It is recommended to check each 
airflow again to make sure the value did not dramatically change 
during the balancing procedure. Make adjustments as necessary.

•  The pressure reading from the duct connection refers to the total 

pressure loss from the distribution system. A well designed distri-
bution system should have a total pressure loss between 0.4” 
(100Pa) and 0.6” (150Pa). The pressure reading can therefore be 
used as troubleshooting of the distribution system. If pressure 
reading is higher than 0.6” (150Pa), we recommend that you 
inspect the system and check for closed grilles, blocked exterior 
hoods or twisted flexible duct.

STEP #3:

 Secure the adjustable arm by tightening the set screw as shown in 

Illustration #3

.

HIGH

LOW

LOW

HIGH

SUPPLY

EXHAUST

Adjustment lever (in front)

Set screw (on top)

Illustration #1

Illustration #3

Illustration #2

BALANCING CHART (example only)

Airflow

Normal Speed

Reduced Speed

CFM L/s

∆In W.G.  

Pressure reading

∆Pa

∆In W.G.  

Pressure reading

∆Pa

110

52

0.36

91

100

47

0.46

114

90

42

0.55

137

80

38

0.64

161

70

33

0.74

184

0.13

32

65

31

0.78

195

0.16

40

60

28

0.83

207

0.19

48

55

26

0.87

219

0.22

55

50

24

0.92

230

0.25

63

Summary of Contents for 405335

Page 1: ...ications to maintain their technological leadership position Item 405335 Rev Date 110512 United States 10048 Industrial Blvd Lenexa KS 66215 Phone 800 747 1762 913 752 6000 Fax 800 487 9915 913 752 64...

Page 2: ...ment i e Gas Furnaces Oil Furnaces Wood Stoves etc Products are designed and manufactured to provide reliable performance but they are not guaran teed to be 100 free of defects Even reliable products...

Page 3: ...STALLATION Weatherhood Location 9 Installing the ducting to the weatherhood 9 INTERIOR DUCTING INSTALLATION General Tips 9 Installing duct to HRV 9 Supply Exhaust Air Grilles Location 9 HRV INSTALLATI...

Page 4: ...rea Bedrooms 0 1 2 3 4 5 6 7 7 Ft2 m2 CFM L s CFM L s CFM L s CFM L s CFM L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 45 21 60 28 75 35 90 42 105 50 3001 4500 279 1 418 60 28 75 35...

Page 5: ...as of the home requiring local exhaust bathroom kitchen laundry room 2 Fresh air is distributed directly to habitable rooms in the house bed rooms living room 3 The HRV s airflow must be balanced afte...

Page 6: ...tribution of the fresh air it is recommend ed that the furnace blower be set to run continuously or interconnected with HRV 2 Stale air is drawn from key areas of the home bathroom kitchen laun dry ro...

Page 7: ...operate when ventilation from HRV is required The fur nace should be set to run continuously or interlocked with HRV See page 15 2 A minimum separation of 1m 39 is recommended between the two direct...

Page 8: ...er liner which acts as a vapor barrier must be completely sealed to the outer wall and the HRV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal t...

Page 9: ...e duct to prevent leakage between the ducting and the duct connection In the case of solid ducting slide duct over duct connection screw in place and seal SUPPLY AIR GRILLES LOCATION In homes without...

Page 10: ...ur warranty Mounting Wall Mount 1 Attach bracket to wall 2 Lift unit slide nuts into slots on bracket 3 Tighten screws to secure unit to bracket 4 Ensert the safety screws place wall bumpers to level...

Page 11: ...r is operating at normal speed during the balancing sequence When reading with a mechanical type manometer Magnehelic make sure the manometer is placed on a level surface For optimal performance HRV u...

Page 12: ...the distribution system Because the house is tightly sealed adjusting one airflow may affect the other airflow as well It is recommended to check each airflow again to make sure the value did not dram...

Page 13: ...on a third time and the system will run continuously on HIGH speed W EDF1R Press button once for continuous LOW speed Press button twice and the unit will cycle 20 minutes ON 40 minutes OFF and repeat...

Page 14: ...14 Wiring diagram Wiring diagram of complete unit inside of access panel Observe polarity on all accessory controls where applicable...

Page 15: ...ction to a Cooling System On some newer furnaces and older thermostats energizing the R and G terminal at the furnace has the effect of energizing the Y at the thermostat and thereby turning on the co...

Page 16: ...conserver sa position de leader de technologie No de l article 405335 Date de r vision 071912 tats Unis 1048 Industrial Blvd Lenexa KS 66215 T l phone 800 747 1762 913 752 6000 T l copieur 800 487 991...

Page 17: ...ntilateur r cup rateur de chaleur VRC au moyen de la proc dure d quilibrage du pr sent manuel Il importe de toujours valuer l interaction du VRC avec les appareils de chauffage vacuation fournaise gaz...

Page 18: ...cement des hottes 23 Installation de l ensemble des conduits avec hottes 23 INSTALLATION DES CONDUITS INT RIEURS Conseils pratiques 24 Installation des conduits sur le VRC 24 Emplacement des grilles d...

Page 19: ...ieme D bit d air recommand Superficie Chambres coucher 0 1 2 3 4 5 6 7 7 Pi2 m2 Pi3 min L s Pi3 min L s Pi3 min L s Pi3 min L s Pi3 min L s 1500 139 30 14 45 21 60 28 75 35 90 42 1501 3000 139 1 279 4...

Page 20: ...pir partir des endroits cl s de la maison salle de bains cuisine buanderie 2 L air frais est distribu parmi les pi ces habitables chambres coucher salon 3 Le d bit d air du VRC doit tre confirm sur pl...

Page 21: ...n cessaire de faire fonc tionner le ventilateur de la fournaise pendant que le VRC est en marche 2 Air vici est aspir des endroits cl s de la maison salle de bain cui sine buanderie Voir page 30 3 L...

Page 22: ...fournaise doit fonctionner continuellement ou bien le fonctionnement du VRC doit tre syn chronis avec le ventilateur de la fournaise 2 Une s paration minimum de 1m 36 po est recommand e entre les deux...

Page 23: ...t scell sur le mur ext rieur et le VRC l aide de ruban ou de produit de calfeutrage D posez un cordon de produit de calfeutrage de premi re qualit du mastic d isolation acoustique de pr f rence pour s...

Page 24: ...rochets Ensuite installez un attache c ble par dessus le conduit flexible afin de pr venir des fuites entre le conduit et le collet Dans le cas d un conduit galvanis faites le glisser sur le collet vi...

Page 25: ...appareil et mettre les crous dans les ouvertures sur le support 3 Serrer les vis afin de s curiser l appareil au support 4 Ins rer les vis de s curit et poser les amortisseurs afin de mettre l appare...

Page 26: ...manom tre analogique Magnehelic assurez vous que le manom tre est plac sur une surface plane Afin d assurer une performance optimal le VRC devrait tre r quilibr apr s toute r novation majeure ou apr s...

Page 27: ...sistance dans le syst me de distribution Parce que la maison est bien scell e le r glage d un d bit d air peut affecter le d bit d autres aussi Il est donc recommand de v rifier chaque d bit d air no...

Page 28: ...n pour une vitesse basse continuelle Appuyez le bouton une seconde fois l appareil fera un cycle de 20 minutes ON 40 minutes OFF et r p ter Appuyez le bouton une troisi me fois et le syst me fonctionn...

Page 29: ...29 SH MAS LECTRONIQUES Sch ma lectrique de l appareil au complet situ l int rieur du paneau d acc s Respectez la polarit sur tous les accessoires de contr le le cas ch ant...

Page 30: ...tation de la borne Y du thermostat et cons quem ment la mise sous tension du syst me de refroidissement Si votre syst me est muni d un tel type de thermostat vous devez respecter le c blage de verroui...

Reviews: