Technical data

rated supply voltage

mail linia (1-2 terminals)

battery (1-4 terminals)

10÷12 V DC*

maximum permissible voltage

 (1-2, 1-3 terminals)

400 V AC

contacts

3×NO

maximum switching current of internal contacts

AC-1

16 A/250 V

AC-15

3 A/250 V

voltage threshold**

lower (adjustable)

150÷210 V

upper

270 V

hysteresis

5 V

switch-off time

lower threshold (adjustable)

1÷15 sec

0.3 sec

switching time

0.3 sec

time to qualify the line as a good

10 sec

generator start time

5÷120 sec

durability of relay contacts

>10⁵ switchings

power consumption

1.5 W

working temperature

-25÷50°C

connection

2.5 mm² screw termianls

tightening torque

0.4 Nm

dimensions

3 modules (52 mm)

mounting

on the TH-35 mm rail

protection level

IP20

*    

recommended battery type: URLA, voltage 12 V, capacity 1.2 Ah

** 

at voltage over 300 V, the load is disconnected in no more than 0.1 seconds

230 V AC

generator (1-3 terminals)

230 V AC

upper threshold

CE declaration

Declaration of CE conformity of the device can be downloaded 
from the product page from the website:

 

 www.fif.com.pl.

AL failure indication

load off
normal operation

incorrect contact configuration
(voltage at the Uk output)

relay lock

(input 5 connected to the neutral line)

on

off

4 blinks/sec

short switching on

L i L' phase status indicators

reduced voltage/lack of voltage
voltage too high
line connected to the reception
qualification of the line as good
voltage correct, phase is not used

off

4 blinks/sec

on

short switching off

short switching on

START generator status indicators

generator off
generator start

countdown of the pause time 
between a restart attempt

normal operation
generator error

off

short switching off

short switching on

on

4 blinks/s